Maintenance

Maint

Maintenance

 

Maintenance Tasks

Task Completed

Level

Interval

 

Date/Initials

 

 

 

 

 

 

 

 

1. Disable the unit from operating per the first page warning.

 

 

 

 

 

 

 

2. Check the engine oil level. Adjust as necessary.

 

 

 

 

 

 

 

3. Check the engine coolant level. Adjust as necessary.

 

 

 

 

 

 

 

4. Check the battery electrolyte level if accessible. Adjust as

 

 

Every 6 months

 

necessary.

 

 

 

 

 

 

or

5. Check the diesel fuel supply level. Adjust as necessary.

 

 

50 hours of

 

 

 

 

 

 

operation

 

 

 

2

 

6.

Drain water and sediment from the diesel fuel tank.

 

 

(Requires

 

 

 

 

7.

Drain water from the diesel fuel line water separator if unit is equipped

 

 

approximately

 

 

1.5 man hours

 

with one.

 

 

per unit)

 

 

 

 

 

8. Check the air inlets and outlets for debris. Clean as necessary.

 

 

 

 

 

 

 

9. Visually inspect the unit looking for leaks, wear or damage, loose con-

 

 

 

 

nections or components, and corrosion. Correct as necessary.

 

 

 

 

 

 

 

10. Initiate an automatic start and transfer to load of the unit, and exer-

 

 

 

 

cise it for at least 1 hour looking for leaks, loose connections or com-

 

 

 

 

ponents, and abnormal operating conditions. Correct as necessary.

 

 

 

11. Return the unit to standby setup for operation when required.

 

 

 

 

 

 

Technician'sSignature

Date Inspection Completed

Unit Hour Meter Reading at Completion of the Inspection