Carrier 50TJ016-028 specifications Base Unit Dimensions, 50TJ016,020

Page 4

4

 

STD UNIT

ECONOMI$ER

CORNER

CORNER

CORNER

CORNER

DIM A

DIM B

DIM C

 

UNIT

WEIGHT

WEIGHT

 

(A)

 

(B)

 

(C)

 

(D)

 

 

 

 

 

 

 

 

 

 

 

 

 

Lb

Kg

Lb

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

Lb

 

Kg

Ft-in.

mm

Ft-in.

mm

Ft-in.

 

mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50TJ016

1550

703

80

36.3

391

 

177

365

 

166

384

 

174

410

 

186

3-5

1041

3-6

1067

1-10

 

559

50TJ020

1650

748

80

36.3

399

 

181

384

 

174

402

 

182

439

 

199

3-4

1016

3-6

1067

1- 8

 

508

NOTES:

 

1.

Refer to print for roof curb accessory dimensions.

2.

Dimensions in [

] are in millimeters.

3.

 

Center of gravity.

4.

 

Direction of airflow.

5.

Ductwork to be attached to accessory roof curb only.

6.

Minimum clearance:

 

Rear: 7-0

(2134) for coil removal. This dimension can be

 

 

reduced to 4-0(1219) if conditions permit coil removal from the

 

 

top.

 

 

Left side: 4-0(1219) for proper condenser coil airflow.

 

Front: 4-0(1219) for control box access.

 

Right side: 4-0(1219) for proper operation of damper and

 

 

power exhaust if so equipped.

 

Top: 6-0(1829) to assure proper condenser fan operation.

 

Local codees or jurisdiction may prevail.

7.

With the exception of clearance for the condenser coil and the

 

damper/power exhaust as stated in Note #6, a removable fence or

 

barricade requires no clearance.

8.

Dimensions are from outside of corner post. Allow 0-5/16(8) on

 

each side for top cover drip edge.

9.

See drawing 50TJ500352 for service option details.

POWER EXHAUST/BAROMETRIC RELIEF (ACCESSORY ONLY)

Fig. 4 — Base Unit Dimensions, 50TJ016,020

Image 4
Contents Installation Contents Safety Considerations Roof Curb Details UnitUnit Maximum Dimensions Shipping Weight Ft-in 016020 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details Make Electrical Connections Unit VoltageGND NECElectrical Data Min MaxRLA LRA Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect WiringUnit Stage Heat Anticipator Settings016-028 Seal Strip Location Air Hood Cross-Sectional View Default Potentiometer Settings EconoMi$er Switchover Control StrategyChangeover Set Points Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Air Quantity Limits START-UPUnit Minimum CFM Maximum CFM Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Accessory/FIOP Static Pressure in. wg 50TJ020-028 Accessory/FIOP Static Pressure in. wg 50TJ016Fan Rpm at Motor Pulley Settings Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentEconoMi$er Control Module Flash Code Identification EconoMi$er AdjustmentFlash Code Cause Action Taken by ECONOMI$ER Cooling Charging Chart Protective DevicesElectric Heat 208/240 v Amps 200/230 v kW 71.3/82.3117/135 156/180Typical Component Arrangement 50TJ024 Shown HPS HTRIFC IFRCooling Service Analysis TroubleshootingProblem Cause Remedy MoistureMiser Dehumidification Subcooler Service Analysis EconoMi$er TroubleshootingProblem Potential Cause Remedy Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP