Carrier 50TJ016-028 specifications Base Unit Operation

Page 23

Base Unit Operation

COOLING, UNITS WITHOUT ECONOMI$ER — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator-fan motor, compressor no. 1 and condenser fans start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compres- sor contactor no. 2 (C2) is energized and compressor no. 2 starts.

HEATING, UNITS WITHOUT ECONOMI$ER (If Acces- sory or Optional Heater is Installed) — Upon a call for heat- ing through terminal W1, IFC and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when ad- ditional heat is needed, HC2 is energized through W2.

COOLING UNITS WITH ECONOMI$ER — When the OAT is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor-fan motors (IFM) is energized and the EconoMi$er damper modulates to minimum position. The compressor contactor and OFC are energized to start the compressor and outdoor-fan motor (OFM). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized.

When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor air dampers to maintain a 55 F supply air set point. If the supply-air temperature (SAT) is greater than 57 F, the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 53 F, the outdoor air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 53 and 57 F, the EconoMi$er maintains its position.

If outdoor air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below.

NOTE: Compressors have a two-minute Minimum On and Minimum Off, which are accomplished by the strategies below.

1.If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), the compressor and OFC are ener- gized. The position of the EconoMi$er damper is main- tained at its current value.

2.If Y1 is energized for more than 20 minutes, and Y2 is not energized (whether or not a 2-stage thermostat is used), the compressor and OFC are energized. The posi- tion of the EconoMi$er damper is maintained at its cur- rent value.

3.If Y1 is energized, and compressor no. 1 is already ener- gized (see Step 2) and the room thermostat calls for Y2, compressor no. 1 continues to operate. If Y2 remains energized for more than 20 minutes, compressor no. 2 is energized.

NOTE: Compressor no. 2 cannot be energized unless there is a signal for Y2 from the space thermostat.

4.If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressors 1 and 2 are deen- ergized. Re-asserting Y2 will start compressor no. 1 and (after a 20-minute interstage delay) compressor no. 2.

5.If compressor no. 1 is energized and the thermostat is sat- isfied, compressor no. 1, the OFM, and IFM are deener- gized and the EconoMi$er modulates closed.

When the OAT is below the MECH CLG LOCKOUT set point, the compressors remain off.

FREEZE PROTECTION THERMOSTAT(S) — A freeze protection thermostat (FPT) is located on the top and bottom of the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once frost has melted, the compressor can be reenergized by resetting the compressor lockout.

HEATING, UNITS WITH ECONOMI$ER (If Accessory or Optional Heater is Installed) — When the room thermostat calls for heat, the heating controls are energized as described in the Heating, Units Without EconoMi$er section. The IFM is energized and the EconoMi$er damper modulates to the mini- mum position. When the thermostat is satisfied, the damper modulates closed.

UNITS WITH MOISTUREMISER DEHUMIDIFICATION PACKAGE — When thermostat calls for cooling, terminals G and Y1 and/or Y2 and the compressor contactor C1 and/or C2 are energized. The indoor (evaporator) fan motor (IFM), com- pressors, and outdoor (condenser) fan motors (OFM) start. The OFMs run continuously while the unit is in cooling. As shipped from the factory, both MoistureMiser dehumidification circuits are always energized.

If MoistureMiser circuit modulation is desired, a field- installed, wall-mounted humidistat is required. If the Mois- tureMiser humidistat is installed and calls for the Mois- tureMiser subcooler coil to operate, the humidistat internal switch closes. This energizes the 3-way liquid line solenoid valve coils (LLSV1 for circuit 1 and LLSV2 for circuit 2) of the MoistureMiser circuits, forcing the warm liquid refrigerant of the liquid line to enter the subcooler coils. See Fig. 30.

As the warm liquid passes through the subcooler coils, it is exposed to the cold supply airflow coming off the evaporator coils and the liquid is further cooled to a temperature approach- ing the evaporator coil leaving-air temperature. The state of the refrigerant leaving the subcooler coils is a highly subcooled liq- uid refrigerant. The liquid then enters a thermostatic expansion valve (TXV) where the liquid is dropped to the evaporator pressure. The TXVs can throttle the pressure drop of the liquid refrigerant and maintain proper conditions at the compressor suction valves over a wide range of operating conditions. The liquid proceeds to the evaporator coils at a temperature lower than normal cooling operation. This lower temperature is what increases the latent and sensible capacity of the evaporator coils.

The 2-phase refrigerant passes through the evaporators and is changed into a vapor. The air passing over the evaporator coils will become colder than during normal operation as a re- sult of the colder refrigerant temperatures. However, as it pass- es over the subcooler coils, the air will be warmed, decreasing the sensible capacity and reducing the sensible heat of the roof- top unit.

As the refrigerant leaves the evaporator, the refrigerant passes a subcooler control low-pressure switch (S-LPS1 for circuit 1 or S-LPS2 for circuit 2) in the suction line. This low- pressure switch will deactivate the MoistureMiser package when the suction pressure reaches 60 psig. The subcooler con- trol low-pressure switch is an added safety device to protect against evaporator coil freeze-up during low ambient opera- tion. The subcooler control low-pressure switch will only deactivate the 3-way liquid line solenoid valve in the Mois- tureMiser circuit. The compressors will continue to run as long as there is a call for cooling, regardless of the position of the subcooler control low-pressure switch. The 3-way solenoid valve and the MoistureMiser package will be reactivated only when the call for cooling has been satisfied, the subcooler con- trol low-pressure switch has closed above 80 psig, and a new call for cooling exists. The crankcase heaters on the scroll com- pressors provide additional protection for the compressors due to the additional refrigerant charge in the subcooler.

23

Image 23
Contents Safety Considerations ContentsInstallation Unit Roof Curb Details024 Unit Maximum Dimensions Shipping WeightFt-in 016 020Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 COMPRESSOR/MANUFACTURER Physical DataConcentric Duct Details NEC Make Electrical ConnectionsUnit Voltage GNDQty FLA ea Electrical DataMin Max RLA LRA50TJ Unbalanced 3-Phase Supply VoltageOptional Non-Fused Disconnect Wiring Make Outdoor-Air Inlet Adjustments016-028 Heat Anticipator SettingsUnit Stage Seal Strip Location Air Hood Cross-Sectional View Changeover Set Points EconoMi$er Switchover Control StrategyDefault Potentiometer Settings Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Unit Minimum CFM Maximum CFM START-UPAir Quantity Limits Fiop Fan Performance 50TJ016Fan Performance 50TJ020 Fan Performance 50TJ028 Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg 50TJ016Accessory/FIOP Static Pressure in. wg 50TJ020-028 Base Unit Operation Lubrication ServiceManufacturer Lubricant Evaporator Fan Service and ReplacementCondenser-Fan Adjustment Belt Tension Adjustment To adjust belt tensionFlash Code Cause Action Taken by ECONOMI$ER EconoMi$er AdjustmentEconoMi$er Control Module Flash Code Identification Protective Devices Cooling Charging Chart156/180 Electric Heat208/240 v Amps 200/230 v kW 71.3/82.3 117/135Typical Component Arrangement 50TJ024 Shown IFR HPSHTR IFCProblem Cause Remedy TroubleshootingCooling Service Analysis Problem Potential Cause Remedy EconoMi$er TroubleshootingMoistureMiser Dehumidification Subcooler Service Analysis Call for Free Catalog Service TrainingPage PRE-START-UP START-UP Checklist