Carrier 50TJ016-028 Belt Tension Adjustment To adjust belt tension, Condenser-Fan Adjustment

Page 26

Fig. 32 — 50TJ016 Evaporator-Fan

Motor Section

Belt Tension Adjustment — To adjust belt tension:

1.Loosen fan motor bolts.

2.Adjust belt tension:

a.Size 016 Units: Move motor mounting plate up or down for proper belt tension (1/2 in. deflection with one finger).

b.Size 020-028 Units: Turn motor jacking bolt to move motor mounting plate up or down for proper belt ten- sion (3/8 in. deflection at midspan with one finger [9 lb force]).

3.Tighten nuts.

4.Adjust bolts and nut on mounting plate to secure motor in fixed position.

Condenser-Fan Adjustment

50TJ016,020 UNITS (Fig. 34)

1.Shut off unit power supply.

2.Remove access panel(s) closest to the fan to be adjusted.

3.Loosen fan hub setscrews.

4.Adjust fan height on shaft using a straightedge placed across the fan orifice.

5.Tighten setscrews and replace panel(s).

6.Turn on unit power.

50TJ024,028 UNITS (Fig. 35)

1.Shut off unit power supply.

2.Remove fan top-grille assembly and loosen fan hub screws.

3.Adjust fan height on unit, using a straightedge placed across the fan orifice.

4.Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft.

5.Fill hub recess with permagum if rubber hubcap is missing.

NOTE: A 31/2-in. bolt and threaded plate are included in the installer’s packet. They should be added to the motor support chan- nel below the motor mounting plate to aid in raising the motor. The plate part number is 50DP503842. The adjustment bolt is 3/8-16 x 13/4 in.-LG.

Fig. 33 — 50TJ020-028 Evaporator-Fan

Motor Section

NOTE: Dimensions are in inches).

Fig. 34 — Condenser-Fan Adjustment,

50TJ016,020

NOTE: Dimensions are in inches.

Fig. 35 — Condenser-Fan Adjustment,

50TJ024,028

26

Image 26
Contents Safety Considerations ContentsInstallation Roof Curb Details Unit020 Unit Maximum Dimensions Shipping WeightFt-in 016 024Base Unit Dimensions, 50TJ016,020 Base Unit Dimensions, 50TJ024,028 Physical Data COMPRESSOR/MANUFACTURERConcentric Duct Details GND Make Electrical ConnectionsUnit Voltage NECRLA LRA Electrical DataMin Max Qty FLA eaUnbalanced 3-Phase Supply Voltage 50TJMake Outdoor-Air Inlet Adjustments Optional Non-Fused Disconnect Wiring016-028 Heat Anticipator SettingsUnit Stage Seal Strip Location Air Hood Cross-Sectional View Changeover Set Points EconoMi$er Switchover Control StrategyDefault Potentiometer Settings Motormaster I Control Installation 50TJ016 and 020 Only Wind Baffle Details Motormaster I Sensor Locations Unit Minimum CFM Maximum CFM START-UPAir Quantity Limits Fan Performance 50TJ016 FiopFan Performance 50TJ020 Fan Performance 50TJ028 Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure in. wg 50TJ016Accessory/FIOP Static Pressure in. wg 50TJ020-028 Base Unit Operation Service LubricationEvaporator Fan Service and Replacement Manufacturer LubricantBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentFlash Code Cause Action Taken by ECONOMI$ER EconoMi$er AdjustmentEconoMi$er Control Module Flash Code Identification Cooling Charging Chart Protective Devices117/135 Electric Heat208/240 v Amps 200/230 v kW 71.3/82.3 156/180Typical Component Arrangement 50TJ024 Shown IFC HPSHTR IFRProblem Cause Remedy TroubleshootingCooling Service Analysis Problem Potential Cause Remedy EconoMi$er TroubleshootingMoistureMiser Dehumidification Subcooler Service Analysis Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP