Carrier 38AU appendix Evacuation/Dehydration, Preliminary Charge

Page 17

The stub tube connections include 1/4-in SAE service fittings with Schrader valve cores (see Fig. 10). Before making any brazed connections to the unit service valves, remove both Schrader valve caps and cores and save for re-installation. Connect a source for nitrogen to one of these service fittings during tube brazing to prevent the formation of copper oxides inside the tubes at brazed joints.

 

Field Service

Factory

Access Port

(Schrader core)

High-Flow

 

Access Port

 

Service Valve

 

with Stem Cap

Sweat

 

Connection

C10203

Fig. 10 - Typical Piping Connection Assembly

When connecting the field tubing to the 38AU service valves, wrap the valves in wet rags to prevent overheating

Pressure-test all joints from outdoor unit connections over to the evaporator coil, using nitrogen as pressure and with soap-and-bubbles.

When pressure-testing is completed, remove the nitrogen source at the outdoor unit service valves and re-install the two Schrader valve cores. Torque the cores to 2-3 in-lbs (23-34 N-cm).

Evacuation/Dehydration —

Evacuate and dehydrate the connected refrigeration system(s) (excluding the 38AU unit) to 500 microns using a two-stage vacuum pump attached to the service ports outside the 38AU service valves, following description in GTAC II, Module 4, System Dehydration.

!WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause personal injury, death and/or equipment damage.

PuronR (R-410A) refrigerant systems operate at higher pressure than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment.

This unit is designed for use with Puron (R-410A) refrigerant. Do not use any other refrigerant in this system.

Puron (R-410A) refrigerant is provided in pink (rose) colored cylinders. These cylinders are available with and without dip tubes; cylinders with dip tubes will have a label indicating this feature. For a cylinder with a dip tube, place the cylinder in the upright position (access valve at the top) when removing liquid refrigerant for

charging. For a cylinder without a dip tube, invert the cylinder (access valve on the bottom) when removing liquid refrigerant.

Because Puron (R-410A) refrigerant is a blend, it is strongly recommended that refrigerant always be removed from the cylinder as a liquid. Admit liquid refrigerant into the system in the discharge line. If adding refrigerant into the suction line, use a commercial metering/expansion device at the gauge manifold; remove liquid from the cylinder, pass it through the metering device at the gauge set and then pass it into the suction line as a vapor. Do not remove Puron (R–410A) refrigerant from the cylinder as a vapor.

Preliminary Charge —

Before starting the unit, charge R-410A liquid refrigerant into the high side of each 38AU circuit through the liquid service valve(s). The amount of refrigerant added must be at least 80% of the operating charge listed in Tables 5 or 6 for LINEAR line length LESS the factory charge quantity (if factory shipping charge has not been removed). See example below.

Allow high and low side pressures to equalize. If pressures do not equalize readily, charge R-410A vapor (using spe- cial service manifold with expansion device) into the suc- tion line service port for the low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures.

Example: 38AUD*25 (RTPF)

60-ft (18.3 m) linear line length Equivalent line length 90-ft (27.4 m) Liquid Lift: 20-ft (6.1 m)

Select line sizes from Table 6 (38AUD): Liquid 1/2 in

Suction 1-1/8in. Charge

Circuit 1: 23.0 lbs (at 75-ft linear length)

Circuit 2: 22.0 lbs

80% of Operating Charge: Circuit 1: 0.80 x 23.0 = 18.4 lbs Circuit 2: 0.80 x 22.0 = 17.6 lbs Factory Shipping Charge: 15 lbs Field-Charge

Circuit 1: 18.4 - 15 = 3.4 lbs

Circuit 2: 17.6 - 15 = 2.6 lbs

For linear line lengths longer than 125 ft (38 m), contact your local Carrier representative for system charge value.

Step 6 — Install Accessories

Accessories requiring modifications to unit wiring should be completed now. These accessories may include Winter Start controls and Low Ambient controls. Refer to the instructions shipped with the accessory.

38AU

17

Image 17
Contents Contents Installation, Start---Up Service InstructionsReplacement/Retrofit R-22 to PuronR Safety ConsiderationsInstallation Guideline Unit Damage Hazard InstallationRtpf UnitMchx 38AUD*25 38AUZ*25Refrigerant TYPE‡ Unit Size 38AUCompressor Condenser FansNominal Capacity kW Pressurestat Settings kPa High CutoutRtpf Shipping Charge kg ScrollFace Area sq ft total Rows/Fins per inch FPI Rtpf Shipping Charge A/B lbOil Charge A/B oz Rtpf Shipping Charge A/B kg Operating Weight kg Novation Coil Al TubeOil Charge A/B L Qty...r/s Motor Hp Nema Diameter mmU Z a 2 5 a 0 G 6 a 0 a 0 a Matching 38AU Model To Evaporator Coil InstallationJobsite Survey Do not Bury Refrigeration LinesSlab Mount Provide Safety ReliefEquivalent Lengths for Common Fittings ft Check 38AU Model with Evaporator Coil Connections38AUZ 16-25 Piping Recommendations Single-Circuit Unit Liquid LiftSuction Riser Vertical Separation outdoor unit above indoor unit 38AUD 16-25 Piping Recommendations Two-Circuit UnitInsulate Suction Lines Hot Gas BypassRefrigerant Specialties Part Numbers Install Filter Driers and Moisture IndicatorsCapacity Control Liquid Line Solenoid Valve Install Liquid Line Solenoid ValveSelecting an Accumulator Make Piping ConnectionsPreliminary Charge Evacuation/DehydrationUnits with Factory-Installed Disconnect Field Power SupplyFire Hazard All UnitsElectrical Operation Hazard Convenience OutletsConvenience Outlet Utilization Notice Label Field Control WiringThermostat Control Transformer WiringUnbalanced 3-Phase Supply Voltage Unit Wire/Fuse or Hacr Breaker Sizing DataSTART-UP PRE-START-UPSystem Check Preliminary ChecksAdjust Refrigerant Charge Advanced Scroll Temperature Protection AstpUsing plotted operating point Start UnitFinal Checks 38AUZ*25 Check Compressor Oil Level38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Base Unit Controls Operating SequenceService Routine System MaintenanceRefrigeration System Equipment Damage HazardLiquid Line Filter Drier Field Refrigerant Access PortsFactory High-Flow Access Ports Input Terminal Voltage Comfort Alert Diagnostic ModuleLockout LED Status CodesCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View Repairing Novation Condenser Tube Leaks Novation Coil Cleaning and MaintenanceCoil Type Identification NOVATIONt TypeUnit Reliability Hazard Routine Cleaning of Round-Tube Plate Fin Rtpf CoilsReplacing NOVATIONt Condenser Coil Problem Solution Compressor does not RUN TroubleshootingCompressor Stops on HIGH-PRESSURE Switch Fastener Torque ValuesCompressor Running but Cooling Insufficient Problem Solution Compressor Cycles on LOW-PRESSURE SwitchUnit Operates TOO Long or Continuously System is NoisyAppendix B Wiring Diagram ListAppendix a Troubleshooting Low Ambient Option Factory InstalledAppendix C Operation38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 Rtpf Motormaster Sensor LocationDimensions --- MM Unit Baffle Wind Baffle DimensionDimensions --- Inches Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI II. PRE-START-UP Outdoor Unit START-UP ChecklistCheck Voltage Imbalance