Carrier 38AU Unit Wire/Fuse or Hacr Breaker Sizing Data, Unbalanced 3-Phase Supply Voltage

Page 22

38AU

Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

 

 

NO C.O. or UNPWRD C.O.

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

UNIT

RANGE

No. 1

No. 2

 

OFM

POWER SUPPLY

DISCONNECT SIZE

SUPPLY

 

 

 

 

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38AU

 

 

 

 

 

 

 

 

 

FLA

 

FUSE or

 

 

 

V---Ph---Hz

Min

Max

RLA

LRA

RLA

LRA

Qty

 

MCA

HACR

FLA

LRA

 

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

25.0

164

25.0

164

3

 

1.5

60.8/60.8

80/80

63/63

337/337

D*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

12.2

100

12.2

100

3

 

0.8

29.9

40

31

206

Z*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

9.0

78

9.0

78

3

 

0.7

22.4

30

23

162

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

30.1

225

30.1

225

4

 

1.5

73.7/73.7

100/100

76/76

462/462

D*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

16.7

114

16.7

114

4

 

0.8

40.8

50

42

236

Z*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

12.2

80

12.2

80

4

 

0.7

30.3

40

31

168

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

 

 

 

w/ PWRD C.O.

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

UNIT

RANGE

No. 1

No. 2

 

OFM

POWER SUPPLY

DISCONNECT SIZE

SUPPLY

 

 

 

 

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38AU

 

 

 

 

 

 

 

 

 

FLA

 

FUSE or

 

 

 

V---Ph---Hz

Min

Max

RLA

LRA

RLA

LRA

Qty

 

MCA

HACR

FLA

LRA

 

 

(ea)

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

25.0

164

25.0

164

3

 

1.5

65.6/65.6

90/90

68/68

342/342

D*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

12.2

100

12.2

100

3

 

0.8

32.1

40

33

208

Z*16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

9.0

78

9.0

78

3

 

0.7

24.1

30

25

164

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230---3---60

187

253

30.1

225

30.1

225

4

 

1.5

78.5/78.5

100/100

82/82

467/467

D*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460---3---60

414

506

16.7

114

16.7

114

4

 

0.8

43

50

45

238

Z*25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575---3---60

518

633

12.2

80

12.2

80

4

 

0.7

32

40

33

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend and Notes for Table 10

LEGEND:

 

 

BRKR

---

Circuit breaker

CO

---

Convenient outlet

FLA

---

Full Load Amps

LRA

---

Locked Rotor Amps

MCA

---

Minimum Circuit Amps

 

 

Protection

NEC

---

National Electrical Code

PWRD CO

---

Powered convenient outlet

RLA

---

Rated Load Amps

UNPWR CO

---

Unpowered convenient outlet

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.The MCA values are calculated in accordance with The NEC. Article 440.

3.Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL). Standard 1995.

4.The 575--- v units are UL, Canada--- listed only.

5.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to de- termine the percentage of voltage imbalance.

Example: Supply voltage is 230-3-60

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

 

average voltage

 

AB = 224 v

BC = 231 v

AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

 

 

3

3

 

 

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

 

227

 

 

 

= 1.76%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

22

Image 22
Contents Installation, Start---Up Service Instructions ContentsInstallation Guideline Safety ConsiderationsReplacement/Retrofit R-22 to PuronR Installation Unit Damage HazardMchx UnitRtpf 38AUZ*25 38AUD*25Compressor Unit Size 38AURefrigerant TYPE‡ Condenser FansRtpf Shipping Charge kg Pressurestat Settings kPa High CutoutNominal Capacity kW ScrollOil Charge A/B oz Rtpf Shipping Charge A/B lbFace Area sq ft total Rows/Fins per inch FPI Oil Charge A/B L Operating Weight kg Novation Coil Al TubeRtpf Shipping Charge A/B kg Qty...r/s Motor Hp Nema Diameter mmU Z a 2 5 a 0 G 6 a 0 a 0 a Jobsite Survey InstallationMatching 38AU Model To Evaporator Coil Do not Bury Refrigeration LinesEquivalent Lengths for Common Fittings ft Provide Safety ReliefSlab Mount Check 38AU Model with Evaporator Coil ConnectionsSuction Riser Liquid Lift38AUZ 16-25 Piping Recommendations Single-Circuit Unit Insulate Suction Lines 38AUD 16-25 Piping Recommendations Two-Circuit UnitVertical Separation outdoor unit above indoor unit Hot Gas BypassInstall Filter Driers and Moisture Indicators Refrigerant Specialties Part NumbersSelecting an Accumulator Install Liquid Line Solenoid ValveCapacity Control Liquid Line Solenoid Valve Make Piping ConnectionsEvacuation/Dehydration Preliminary ChargeFire Hazard Field Power SupplyUnits with Factory-Installed Disconnect All UnitsConvenience Outlets Electrical Operation HazardField Control Wiring Convenience Outlet Utilization Notice LabelControl Transformer Wiring ThermostatUnit Wire/Fuse or Hacr Breaker Sizing Data Unbalanced 3-Phase Supply VoltageSystem Check PRE-START-UPSTART-UP Preliminary ChecksUsing plotted operating point Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Start Unit38AUZ*25 Check Compressor Oil Level Final Checks38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Operating Sequence Base Unit ControlsRefrigeration System Routine System MaintenanceService Equipment Damage HazardFactory High-Flow Access Ports Field Refrigerant Access PortsLiquid Line Filter Drier Comfort Alert Diagnostic Module Input Terminal VoltageLED Status Codes LockoutCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View Coil Type Identification Novation Coil Cleaning and MaintenanceRepairing Novation Condenser Tube Leaks NOVATIONt TypeReplacing NOVATIONt Condenser Coil Routine Cleaning of Round-Tube Plate Fin Rtpf CoilsUnit Reliability Hazard Compressor Stops on HIGH-PRESSURE Switch TroubleshootingProblem Solution Compressor does not RUN Fastener Torque ValuesUnit Operates TOO Long or Continuously Problem Solution Compressor Cycles on LOW-PRESSURE SwitchCompressor Running but Cooling Insufficient System is NoisyAppendix a Wiring Diagram ListAppendix B Appendix C Low Ambient Option Factory InstalledTroubleshooting OperationMotormaster Sensor Location 38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 RtpfDimensions --- Inches Unit Baffle Wind Baffle DimensionDimensions --- MM Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI START-UP Checklist II. PRE-START-UP Outdoor UnitCheck Voltage Imbalance