Carrier 38AU Field Power Supply, Fire Hazard, Units with Factory-Installed Disconnect, All Units

Page 18

38AU

Step 7 — Complete Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise.

Field Power Supply —

If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet’s transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads..

Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and TB1 (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size is #4 AWG (copper only).

NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only.

!WARNING

FIRE HAZARD

Failure to follow this warning could cause in personal injury, death and/or equipment damage.

Do not connect aluminum wire between disconnect switch and condensing unit. Use only copper wire. (See Fig. 11.)

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 11 - Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.

Units with Factory-Installed Disconnect —

The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel.

All Units —

All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 12 for power wiring connections to the unit contactor and terminal block and equipment ground.

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.

All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire with the 1/4 -in. female spade connector from the 230-v connection and moving it to the 208-v1/4 -in. male terminal on the primary side of the transformer. Refer to unit label diagram for line-side information.

18

Image 18
Contents Installation, Start---Up Service Instructions ContentsSafety Considerations Installation GuidelineReplacement/Retrofit R-22 to PuronR Installation Unit Damage HazardUnit MchxRtpf 38AUZ*25 38AUD*25Compressor Unit Size 38AURefrigerant TYPE‡ Condenser FansRtpf Shipping Charge kg Pressurestat Settings kPa High CutoutNominal Capacity kW ScrollRtpf Shipping Charge A/B lb Oil Charge A/B ozFace Area sq ft total Rows/Fins per inch FPI Oil Charge A/B L Operating Weight kg Novation Coil Al TubeRtpf Shipping Charge A/B kg Qty...r/s Motor Hp Nema Diameter mmU Z a 2 5 a 0 G 6 a 0 a 0 a Jobsite Survey InstallationMatching 38AU Model To Evaporator Coil Do not Bury Refrigeration LinesEquivalent Lengths for Common Fittings ft Provide Safety ReliefSlab Mount Check 38AU Model with Evaporator Coil ConnectionsLiquid Lift Suction Riser38AUZ 16-25 Piping Recommendations Single-Circuit Unit Insulate Suction Lines 38AUD 16-25 Piping Recommendations Two-Circuit UnitVertical Separation outdoor unit above indoor unit Hot Gas BypassInstall Filter Driers and Moisture Indicators Refrigerant Specialties Part NumbersSelecting an Accumulator Install Liquid Line Solenoid ValveCapacity Control Liquid Line Solenoid Valve Make Piping ConnectionsEvacuation/Dehydration Preliminary ChargeFire Hazard Field Power SupplyUnits with Factory-Installed Disconnect All UnitsConvenience Outlets Electrical Operation HazardField Control Wiring Convenience Outlet Utilization Notice LabelControl Transformer Wiring ThermostatUnit Wire/Fuse or Hacr Breaker Sizing Data Unbalanced 3-Phase Supply VoltageSystem Check PRE-START-UPSTART-UP Preliminary ChecksUsing plotted operating point Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Start Unit38AUZ*25 Check Compressor Oil Level Final Checks38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Operating Sequence Base Unit ControlsRefrigeration System Routine System MaintenanceService Equipment Damage HazardField Refrigerant Access Ports Factory High-Flow Access PortsLiquid Line Filter Drier Comfort Alert Diagnostic Module Input Terminal VoltageLED Status Codes LockoutCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View Coil Type Identification Novation Coil Cleaning and MaintenanceRepairing Novation Condenser Tube Leaks NOVATIONt TypeRoutine Cleaning of Round-Tube Plate Fin Rtpf Coils Replacing NOVATIONt Condenser CoilUnit Reliability Hazard Compressor Stops on HIGH-PRESSURE Switch TroubleshootingProblem Solution Compressor does not RUN Fastener Torque ValuesUnit Operates TOO Long or Continuously Problem Solution Compressor Cycles on LOW-PRESSURE SwitchCompressor Running but Cooling Insufficient System is NoisyWiring Diagram List Appendix aAppendix B Appendix C Low Ambient Option Factory InstalledTroubleshooting OperationMotormaster Sensor Location 38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 RtpfWind Baffle Dimension Dimensions --- Inches Unit BaffleDimensions --- MM Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI START-UP Checklist II. PRE-START-UP Outdoor UnitCheck Voltage Imbalance