Carrier 38AU appendix Convenience Outlet Utilization Notice Label, Field Control Wiring

Page 20

38AU

NOTICE

Convenience Outlet Utilization

Maximum Continuous use : 8 Amps 24/7

 

50HJ542739

B

C10207

Fig. 15 - Convenience Outlet Utilization Notice Label

Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the RESET button to clear the tripped condition.

Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Using unit-mounted convenience outlets: Units with unit-mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

Installing Weatherproof Cover: A weatherproof while in use cover for the factory installed convenience outlets is now required by UL standards. This cover cannot be factory mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet; discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not overtighten).

Mount the weatherproof cover to the backing plate as shown in Fig. 16. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.

C09022

Fig. 16 - Weatherproof Cover Installation

All Units —

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Tables 10 and 11. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Tables 10 and 11, Note 5 (see page 22) to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

Field Control Wiring —

38AU unit control voltage is 24 v. See Fig. 29 (38AUZ) and Fig. 30 (38AUD) for typical field control connections and the unit’s label diagram for field-supplied wiring details. Route control wires to the 38AU unit through the opening in unit’s end panel to the connections terminal board in the unit’s control box.

Remainder of the system controls connection will vary according to the specific construction details of the indoor section (air handler or packaged fan coil). Fig. 17 (38AUZ) and Fig. 18 (38AUD) depict typical connections to a Carrier 40RU fan coil unit. Plan for field connections carefully and install control wiring correctly per the project plan. Additional components and supplemental transformer accessory may be required.

The 38AU unit requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as a field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control).

20

Image 20
Contents Installation, Start---Up Service Instructions ContentsReplacement/Retrofit R-22 to PuronR Safety ConsiderationsInstallation Guideline Installation Unit Damage HazardRtpf UnitMchx 38AUZ*25 38AUD*25Unit Size 38AU Refrigerant TYPE‡Compressor Condenser FansPressurestat Settings kPa High Cutout Nominal Capacity kWRtpf Shipping Charge kg ScrollFace Area sq ft total Rows/Fins per inch FPI Rtpf Shipping Charge A/B lbOil Charge A/B oz Operating Weight kg Novation Coil Al Tube Rtpf Shipping Charge A/B kgOil Charge A/B L Qty...r/s Motor Hp Nema Diameter mmU Z a 2 5 a 0 G 6 a 0 a 0 a Installation Matching 38AU Model To Evaporator CoilJobsite Survey Do not Bury Refrigeration LinesProvide Safety Relief Slab MountEquivalent Lengths for Common Fittings ft Check 38AU Model with Evaporator Coil Connections38AUZ 16-25 Piping Recommendations Single-Circuit Unit Liquid LiftSuction Riser 38AUD 16-25 Piping Recommendations Two-Circuit Unit Vertical Separation outdoor unit above indoor unitInsulate Suction Lines Hot Gas BypassInstall Filter Driers and Moisture Indicators Refrigerant Specialties Part NumbersInstall Liquid Line Solenoid Valve Capacity Control Liquid Line Solenoid ValveSelecting an Accumulator Make Piping ConnectionsEvacuation/Dehydration Preliminary ChargeField Power Supply Units with Factory-Installed DisconnectFire Hazard All UnitsConvenience Outlets Electrical Operation HazardField Control Wiring Convenience Outlet Utilization Notice LabelControl Transformer Wiring ThermostatUnit Wire/Fuse or Hacr Breaker Sizing Data Unbalanced 3-Phase Supply VoltagePRE-START-UP START-UPSystem Check Preliminary ChecksAdvanced Scroll Temperature Protection Astp Adjust Refrigerant ChargeUsing plotted operating point Start Unit38AUZ*25 Check Compressor Oil Level Final Checks38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Operating Sequence Base Unit ControlsRoutine System Maintenance ServiceRefrigeration System Equipment Damage HazardLiquid Line Filter Drier Field Refrigerant Access PortsFactory High-Flow Access Ports Comfort Alert Diagnostic Module Input Terminal VoltageLED Status Codes LockoutCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View Novation Coil Cleaning and Maintenance Repairing Novation Condenser Tube LeaksCoil Type Identification NOVATIONt TypeUnit Reliability Hazard Routine Cleaning of Round-Tube Plate Fin Rtpf CoilsReplacing NOVATIONt Condenser Coil Troubleshooting Problem Solution Compressor does not RUNCompressor Stops on HIGH-PRESSURE Switch Fastener Torque ValuesProblem Solution Compressor Cycles on LOW-PRESSURE Switch Compressor Running but Cooling InsufficientUnit Operates TOO Long or Continuously System is NoisyAppendix B Wiring Diagram ListAppendix a Low Ambient Option Factory Installed TroubleshootingAppendix C OperationMotormaster Sensor Location 38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 RtpfDimensions --- MM Unit Baffle Wind Baffle DimensionDimensions --- Inches Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI START-UP Checklist II. PRE-START-UP Outdoor UnitCheck Voltage Imbalance