Carrier 38AU appendix Convenience Outlets, Electrical Operation Hazard

Page 19

Units Without Disconnect Option

C TB1

11 13

and mounted on a bracket behind the convenience outlet; access is through the unit’s control box access panel. See Fig. 13.

Disconnect

per

NEC

L1 L2 L3

208/230-3-60

460-3-60

575-3-60

Units With Disconnect Option

L1

2

1

 

 

Optional

 

 

Factory

Convenience

Outlet

GFCI

Pwd-CO

Fuse

Switch

Control Box

Access Panel

Pwd-CO

Transformer

L2

4

Disconnect

3

Wiring

 

 

Switch

 

 

 

 

 

L3

6

 

5

 

Disconnect factory test leads; discard.

C10204

Fig. 12 - Power Wiring Connections

Affix the crankcase heater warning sticker to the unit disconnect switch.

Convenience Outlets —

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary.

Two types of convenience outlets are offered on 38AU models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 13.

Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.

Unit-powered type: A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box

C10205

Fig. 13 - Convenience Outlet Location

The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non-fused disconnect switch; this will provide service power to the unit when the unit disconnect switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect is open. See Fig. 14.

 

 

 

C10206

UNIT

CONNECT

PRIMARY

TRANSFORMER

VOLTAGE

AS

CONNECTIONS

TERMINALS

208,

 

L1: RED + YEL

H1 + H3

230

240

L2: BLU + GRA

H2 + H4

 

 

L1: RED

 

460

480

Splice BLU +

H1

YEL

H2 + H3

 

 

 

 

L2: GRA

H4

 

 

 

 

575

600

L1: RED

H1

L2: GRA

H2

 

 

Fig. 14 - Powered Convenience Outlet Wiring

The unit-powered convenience outlet has a 1000 VA rated transformer. Maximum continuous current must not exceed 8 Amps.

38AU

19

Image 19
Contents Contents Installation, Start---Up Service InstructionsInstallation Guideline Safety ConsiderationsReplacement/Retrofit R-22 to PuronR Unit Damage Hazard InstallationMchx UnitRtpf 38AUD*25 38AUZ*25Condenser Fans Unit Size 38AURefrigerant TYPE‡ CompressorScroll Pressurestat Settings kPa High CutoutNominal Capacity kW Rtpf Shipping Charge kgOil Charge A/B oz Rtpf Shipping Charge A/B lbFace Area sq ft total Rows/Fins per inch FPI Qty...r/s Motor Hp Nema Diameter mm Operating Weight kg Novation Coil Al TubeRtpf Shipping Charge A/B kg Oil Charge A/B LU Z a 2 5 a 0 G 6 a 0 a 0 a Do not Bury Refrigeration Lines InstallationMatching 38AU Model To Evaporator Coil Jobsite SurveyCheck 38AU Model with Evaporator Coil Connections Provide Safety ReliefSlab Mount Equivalent Lengths for Common Fittings ftSuction Riser Liquid Lift38AUZ 16-25 Piping Recommendations Single-Circuit Unit Hot Gas Bypass 38AUD 16-25 Piping Recommendations Two-Circuit UnitVertical Separation outdoor unit above indoor unit Insulate Suction LinesRefrigerant Specialties Part Numbers Install Filter Driers and Moisture IndicatorsMake Piping Connections Install Liquid Line Solenoid ValveCapacity Control Liquid Line Solenoid Valve Selecting an AccumulatorPreliminary Charge Evacuation/DehydrationAll Units Field Power SupplyUnits with Factory-Installed Disconnect Fire HazardElectrical Operation Hazard Convenience OutletsConvenience Outlet Utilization Notice Label Field Control WiringThermostat Control Transformer WiringUnbalanced 3-Phase Supply Voltage Unit Wire/Fuse or Hacr Breaker Sizing DataPreliminary Checks PRE-START-UPSTART-UP System CheckStart Unit Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Using plotted operating pointFinal Checks 38AUZ*25 Check Compressor Oil Level38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Base Unit Controls Operating SequenceEquipment Damage Hazard Routine System MaintenanceService Refrigeration SystemFactory High-Flow Access Ports Field Refrigerant Access PortsLiquid Line Filter Drier Input Terminal Voltage Comfort Alert Diagnostic ModuleLockout LED Status CodesCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View NOVATIONt Type Novation Coil Cleaning and MaintenanceRepairing Novation Condenser Tube Leaks Coil Type IdentificationReplacing NOVATIONt Condenser Coil Routine Cleaning of Round-Tube Plate Fin Rtpf CoilsUnit Reliability Hazard Fastener Torque Values TroubleshootingProblem Solution Compressor does not RUN Compressor Stops on HIGH-PRESSURE SwitchSystem is Noisy Problem Solution Compressor Cycles on LOW-PRESSURE SwitchCompressor Running but Cooling Insufficient Unit Operates TOO Long or ContinuouslyAppendix a Wiring Diagram ListAppendix B Operation Low Ambient Option Factory InstalledTroubleshooting Appendix C38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 Rtpf Motormaster Sensor LocationDimensions --- Inches Unit Baffle Wind Baffle DimensionDimensions --- MM Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI II. PRE-START-UP Outdoor Unit START-UP ChecklistCheck Voltage Imbalance