38AU
| TXV |
|
| EQUALIZER LINE |
|
INDOOR |
|
|
|
| |
SENSING |
| SIGHT GLASS |
| ||
COIL CKT | BULB |
|
|
| |
|
|
|
| A LOCATION |
|
|
|
|
| FILTER DRIER | |
|
|
|
| A LOCATION |
|
AIRFLOW | 15 DIAMS |
|
| TXV |
|
10 |
|
|
| ||
| MIN |
|
|
| |
|
| DIAMS |
|
|
|
|
| 8 DIAMS | FLOW | ||
|
| MIN |
| ||
|
|
|
| LIQUID LINE |
|
|
|
|
| SOLENOID |
|
|
|
|
| VALVE |
|
|
| Single Circuit Coil Piping Configuration |
| ||
| For single compressor condensing units |
| |||
| TXV |
|
| EQUALIZER LINE |
|
INDOOR |
|
|
|
| |
SENSING |
|
|
| ||
COIL CKT 2 | BULB |
|
|
|
|
|
|
|
| SIGHT GLASS |
|
|
|
|
| A LOCATION | FILTER DRIER |
AIRFLOW | 15 DIAMS |
|
| TXV | |
10 | CKT 2 | A LOCATION | |||
| MIN |
|
|
| |
|
| DIAMS |
|
|
|
|
| 8 DIAMS | SIGHT |
| |
|
| MIN |
|
| |
|
|
|
| GLASSES | FLOW |
| TXV |
|
| B LOCATION | |
|
|
| FILTER |
| |
INDOOR | SENSING |
| LIQUID LINE | ||
COIL CKT 1 | BULB |
| DRIERS | SOLENOID | |
|
|
|
| B LOCATION | VALVE |
|
|
|
|
| |
AIRFLOW | 15 DIAMS |
|
| TXV |
|
10 | CKT 1 |
| |||
| MIN |
|
|
| |
|
| DIAMS |
|
|
|
8DIAMS
MIN
Dual Circuit Coil Piping Configuration
For single compressor condensing units
C10202
Fig. 8 - Location of Sight Glass(es) and Filter Driers
Typical 38AUZ Systems
| TXV |
| EQUALIZER LINE |
|
| SENSING |
|
| |
| BULB |
|
|
|
AIRFLOW |
|
|
|
|
| 15 DIAMS |
| TXV |
|
| 10 | CKT 2 |
| |
| MIN |
|
| |
|
| DIAMS | 8 DIAMS |
|
|
|
|
| |
|
|
| MIN | FLOW |
|
|
| SIGHT | |
| TXV |
| GLASSES | LIQUID LINE |
|
|
| ||
| SENSING | FILTER | SOLENOID VALVE | |
| BULB |
| DRIERS | CIRCUIT 2 |
AIRFLOW | 15 DIAMS |
| TXV |
|
10 | CKT 1 |
| ||
| MIN |
|
| |
|
| DIAMS |
|
|
|
|
| 8 DIAMS | FLOW |
|
|
| MIN | |
|
|
|
| LIQUID LINE |
| SUCTION |
|
| SOLENOID VALVE |
| CIRCUIT 1 |
|
| CIRCUIT 1 |
SUCTION
CIRCUIT 2
Dual Circuit Coil Piping Configuration
For two circuit condensing units
C10072
Fig. 9 - Location of Sight Glasses and Filter Driers
Typical 38AUD Systems
In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses in a single circuit application. One filter drier and sight glass may be installed at A locations (see Fig. 8) or 2 filter driers and sight glasses may be installed at B locations (see Figs. 8 and 9).
Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping
from the indoor unit to the outdoor unit before opening the liquid and suction lines at the outdoor unit.
Install Liquid Line Solenoid Valve —
It is recommended that a solenoid valve be placed in the main liquid line (see Figs. 8 & 9) between the condensing unit and the evaporator coil. Locate the solenoid valve at the outlet end of the liquid line, near the evaporator coil connections, with flow direction arrow pointed at the evaporator coil. Refer to Table 9. (A liquid line solenoid valve is required when the liquid line length exceeds 75 ft [23 m].) This valve prevents refrigerant migration (which causes oil dilution) to the compressor during the off cycle, at low outdoor ambient temperatures. Wire the solenoid in parallel with the compressor contactor coil (see Figs. 8 & 9). This means of electrical control is referred to as solenoid drop control.
Solenoid drop control wiring: Control the power to the liquid line solenoid through a Solenoid Valve Relay (SVR) in all units. Use part number HN61PC005
38AUD unit also requires a separate control power transformer for the liquid solenoid valve loads. Select transformer part number according to unit power supply.
Unit Power | Transformer Part # |
|
|
208/230 | HT01BD202 |
460HT01BD702
575HT01BD902
Mount the SVR (and transformer TRAN3 when used) in unit control box. Connect per wiring schematic label on unit or per Fig. 29 (38AUZ) or Fig. 30 (38AUD).
Capacity Control Liquid Line Solenoid Valve:
Evaporator capacity staging control via direct thermostat control of a liquid solenoid valve on the evaporator’s second stage circuit is not possible with 38AU models. If this installation is a retrofit for a unit that included automatic
Selecting an Accumulator –
Because all 38AU models use scroll compressors, an accumulator is not required. If an accumulator is to be added, check the accumulator manufacturer’s literature carefully for indication of its suitability for use with
Make Piping Connections —
Piping connections at the 38AU unit are ball valves with stub tube extensions. Do not open the unit service valves until all interconnecting tube brazing has been completed.