Carrier appendix Installation, Matching 38AU Model To Evaporator Coil, Jobsite Survey

Page 11

Matching 38AU Model To Evaporator Coil

The Model 38AUZ is a single-circuit unit design, requiring one set of refrigeration piping. This model can be connected to an evaporator coil with one circuit or with two circuits (by manifolding the evaporator connections into a single piping system).

The Model 38AUD is a dual-circuit unit design that requires two sets of refrigeration piping between the outdoor unit and the evaporator coil (or coils). This model can only be connected to an evaporator coil that has two refrigeration circuits (or to two separate evaporator coils). The Model 38AUD CANNOT be connected to a

Evaluate the path and required line length for interconnecting refrigeration piping, including suction riser requirements (outdoor unit above indoor unit), liquid line lift (outdoor unit below indoor unit) and hot gas bypass line. Relocate sections to minimize the length of interconnecting tubing.

DO NOT BURY REFRIGERATION LINES.

Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.

single-circuit evaporator coil. The Model 38AUD CANNOT be field-converted to a single-circuit design.

Table 3 – Evaporator Coil Connections

Evaporator Coil has

Connect to Model

Notes

 

 

 

Single Circuit

38AUZ ONLY

 

 

 

 

 

38AUZ

Manifold evaporator

 

 

circuits into single

 

 

piping system

REAR:

Min 18” (457 mm) requried for service

LEFT:

Min 18” (457 mm) requried for service

RIGHT:

Min 18” (457 mm) requried for service

FRONT:

42” (1067 mm)

38AU

Two Circuits

Or

 

 

 

 

38AUD

Use two separate

 

 

piping systems

Before unpacking this new 38AU model, compare the evaporator coil design to the 38AU model.

.INSTALLATION

Jobsite Survey

Complete the following checks before installation.

1.Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa- tion requirements.

2.Determine unit location (from project plans) or select unit location.

3.Check for possible overhead obstructions which may interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (pad, rails or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 5.

NOTE: Consider also the effect of adjacent units on airflow performance and control box safety clearance.

Do not install the outdoor unit in an area where fresh air supply to the outdoor coil may be restricted or when recirculation from the condenser fan discharge is possible. Do not locate the unit in a well or next to high walls.

Note: Observe requirements for 39” (914 mm) operating clearance on either Left or Rear coil opening.

C10201

Fig. 5 - Service Clearance Dimensional Drawing

Step 2 — Complete Pre-Installation Checks

Check Unit Electrical Characteristics: Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.

Un-crate Unit: Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location.

Inspect Shipment: File a claim with shipping company if the shipment is damaged or incomplete.

Consider System Requirements:

S Consult local building codes and National Electrical Code (NEC, U.S.A.) for special installation requirements.

S Allow sufficient space for airflow clearance, wiring, refrigerant piping, and servicing unit. See Fig.1 and Fig. 2 for unit dimensions and weight distribution data.

S Locate the unit so that the outdoor coil (condenser) airflow is unrestricted on all sides and above.

S The unit may be mounted on a level pad directly on the base channels or mounted on raised pads at support points. See Tables 1A through 2B for unit operating weights. See Fig. 1 and Fig. 2 for weight distribution based on recommended support points.

NOTE: If vibration isolators are required for a particular installation, use the data in Fig. 1 and Fig. 2 to make the proper selection.

11

Image 11
Contents Contents Installation, Start---Up Service InstructionsReplacement/Retrofit R-22 to PuronR Safety ConsiderationsInstallation Guideline Unit Damage Hazard InstallationRtpf UnitMchx 38AUD*25 38AUZ*25Condenser Fans Unit Size 38AURefrigerant TYPE‡ CompressorScroll Pressurestat Settings kPa High CutoutNominal Capacity kW Rtpf Shipping Charge kgFace Area sq ft total Rows/Fins per inch FPI Rtpf Shipping Charge A/B lbOil Charge A/B oz Qty...r/s Motor Hp Nema Diameter mm Operating Weight kg Novation Coil Al TubeRtpf Shipping Charge A/B kg Oil Charge A/B LU Z a 2 5 a 0 G 6 a 0 a 0 a Do not Bury Refrigeration Lines InstallationMatching 38AU Model To Evaporator Coil Jobsite SurveyCheck 38AU Model with Evaporator Coil Connections Provide Safety ReliefSlab Mount Equivalent Lengths for Common Fittings ft38AUZ 16-25 Piping Recommendations Single-Circuit Unit Liquid LiftSuction Riser Hot Gas Bypass 38AUD 16-25 Piping Recommendations Two-Circuit UnitVertical Separation outdoor unit above indoor unit Insulate Suction LinesRefrigerant Specialties Part Numbers Install Filter Driers and Moisture IndicatorsMake Piping Connections Install Liquid Line Solenoid ValveCapacity Control Liquid Line Solenoid Valve Selecting an AccumulatorPreliminary Charge Evacuation/DehydrationAll Units Field Power SupplyUnits with Factory-Installed Disconnect Fire HazardElectrical Operation Hazard Convenience OutletsConvenience Outlet Utilization Notice Label Field Control WiringThermostat Control Transformer WiringUnbalanced 3-Phase Supply Voltage Unit Wire/Fuse or Hacr Breaker Sizing DataPreliminary Checks PRE-START-UPSTART-UP System CheckStart Unit Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Using plotted operating pointFinal Checks 38AUZ*25 Check Compressor Oil Level38AUD*16 Charging Chart Novation 38AUZ*16 Charging Chart Rtpf 38AUD*16 Charging Chart Rtpf 38AUD*25 Charging Chart Rtpf Typical 38AUZ Wiring Diagram 15 Ton 230V Tandem Unit Shown Typical 38AUD Wiring Diagram 15 Ton 230V Dual Unit Shown Base Unit Controls Operating SequenceEquipment Damage Hazard Routine System MaintenanceService Refrigeration SystemLiquid Line Filter Drier Field Refrigerant Access PortsFactory High-Flow Access Ports Input Terminal Voltage Comfort Alert Diagnostic ModuleLockout LED Status CodesCompressor Protection 38AUD Size 16 Cabinet LPS 38AUZ,D Size 25 Cabinet 38AUZ*25 Compressor Assembly Rear View NOVATIONt Type Novation Coil Cleaning and MaintenanceRepairing Novation Condenser Tube Leaks Coil Type IdentificationUnit Reliability Hazard Routine Cleaning of Round-Tube Plate Fin Rtpf CoilsReplacing NOVATIONt Condenser Coil Fastener Torque Values TroubleshootingProblem Solution Compressor does not RUN Compressor Stops on HIGH-PRESSURE SwitchSystem is Noisy Problem Solution Compressor Cycles on LOW-PRESSURE SwitchCompressor Running but Cooling Insufficient Unit Operates TOO Long or ContinuouslyAppendix B Wiring Diagram ListAppendix a Operation Low Ambient Option Factory InstalledTroubleshooting Appendix C38AUZ*16 & 38AUD*16 Novation 38AUZ*16/25 & 38AUD*16/25 Rtpf Motormaster Sensor LocationDimensions --- MM Unit Baffle Wind Baffle DimensionDimensions --- Inches Unit Baffle Wind Baffles Fabrication 15 Ton Wind Baffle Brackets Fabrication Front Front Back Left Right Catalog No 38AU---09SI II. PRE-START-UP Outdoor Unit START-UP ChecklistCheck Voltage Imbalance