PRE-START-UP
IMPORTANT: Before beginning
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Do not attempt to start the condensing unit, even momentarily, until the following steps have been completed. Compressor damage may result.
System Check
1.The electrical power source must agree with the unit’s nameplate rating.
2.Check all air handler(s) and other equipment auxiliary components. Consult the manufacturer’s instructions re- garding any other equipment connected to the condens- ing unit. If the unit has
3.Check tightness of all electrical connections.
4.Be sure liquid line and low side of the system are properly leak checked and dehydrated.
5.Be sure the unit is properly charged. See “Preliminary Charge”, below.
6.Open the liquid line and suction line service valves.
7.The crankcase heater must be firmly attached to the compressor crankcase. Be sure the crankcase is warm (heater must be on for 24 hours before starting com- pressor).
Turn On Crankcase Heater —
Turn on the crankcase heater for 24 hours before starting the unit to be sure all the refrigerant is out of the oil. To energize the crankcase heater, proceed as follows:
1.Set the space thermostat set point above the space temperature so there is no demand for cooling.
2.Close the field disconnect.
Preliminary Charge —
Before starting the unit, charge liquid refrigerant into the high side of the system through the liquid service valve. The amount of refrigerant added must be at least 80% of the operating charge listed in the Physical Data table (Tables 1A through 2B, pages 6 through 9). Allow high and low side pressures to equalize before starting compressor. If pressures do not equalize readily, charge vapor on low side of system to assure charge in the evaporator. Refer to GTAC II, Module 5, Charging, Recover, Recycling, and Reclamation for liquid charging procedures.
!CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Prior to starting compressor, a preliminary charge of refrigerant must be added to avoid possible compressor damage.
START-UP
38AU Units: The compressor crankcase heater must be on for 24 hours before
Preliminary Checks
1.Check that electric power supply agrees with unit nameplate data.
2.Verify that the compressor crankcase heater is se- curely in place.
3.Check that the compressor crankcase heater has been on at least 24 hours.
4.Recheck for leaks using the procedure outlined in the
5.Ensure that the preliminary charge has been added as described in the
6.All internal wiring connections must be tight, and all barriers and covers must be in place.
NOTE: The 38AU units are factory charged with the required amount of oil. If recharging in required, use Emkarate RL
Compressor Rotation —
On
To correct phase order:
1.Turn off power to the unit, tag disconnect.
2.Reverse any two of the unit power leads.
3.Reapply power to the compressor, verify correct pres- sures.
To verify the compressor is rotating in the proper direction:
1.Connect service gages to the suction and liquid pres- sure fittings.
2.Energize the compressor.
3.The suction pressure should drop and the liquid pres- sure should rise, as is normal on any
38AU
23