8-3. Optional Generator Power Receptacles

European Receptacle

5

6

Australian Receptacle

5

6

South African Receptacle

5

6

1

2

1

3

1

4

 

 

 

 

 

 

1120 V 20 A AC GFCI Receptacle GFCI1

2240 V 16 A AC European Receptacle RC1

3240 V 15 A AC Australian Receptacle RC1

4240 V 15 A AC South African Receptacle RC1

Receptacles supply 60 Hz single- phase power at weld/power speed.

If a ground fault is detected, the GFCI Reset button pops out and the receptacle does not work. Check for faulty tools plugged in receptacle. Press button to reset GFCI1.

.At least once a month, run en-

gine at weld/power speed and press test button to verify GFCI is working properly.

5Supplementary Protector CB2

6Supplementary Protector CB3

CB2 protects GFCI1 from overload. If CB2 opens, GFCI1 does not work. Press button to reset.

CB3 protects RC1 from overload. If CB3 opens, RC1 does not work. Press button to reset.

.If a supplementary protector

continues to open, contact Factory Authorized Service Agent.

.Generator power is not af- fected by weld output.

Maximum output is 2.4 kVA/kW from GFCI1 and 4 kVA/kW from RC1. Maximum output from all re- ceptacles is 4 kVA/kW.

EXAMPLE: If 13 A is drawn from RC1, only 7 A is available at GFCI1:

(240 V x 13 A) + (120 V x 7 A) = 4.0 kVA/kW

191 624

OM-4421 Page 40

Image 46
Contents Description OM-4421215 075QProcesses File Engine DriveFrom Miller to You Table of Contents − Maintenance & Troubleshooting Standards DirectivesDecrot1/07 Manufacturer European Contact Notified Body Decrotsound6/05Electric Shock can kill Symbol UsageArc Welding Hazards HOT Parts can cause severe burnsARC Rays can burn eyes and skin Fumes and Gases can be hazardousBuildup of GAS can injure or kill Welding can cause fire or explosionEngine Hazards Compressed Air HazardsFire or Explosion hazard Welding Wire can cause injuryHOT Parts can cause burns and injury Falling Unit can cause injuryEMF Information Principal Safety StandardsCalifornia Proposition 65 Warnings Radiation can cause interferenceUN Choc Électrique peut tuer Signification des symboles− Consignes DE Sécurité − Lire Avant Utilisation Indique des instructions spécifiquesLE Soudage peut provoquer un in cendie ou une explosion DES Pièces Chaudes peuvent provoquer des brûlures gravesLES Fumées ET LES GAZ peuvent être dangereux LE Bruit peut affecter l’ouïe’EXPLOSION DE LA Batterie peu DES Organes Mobiles peuvent pro voquer des blessures’AIR Comprimé peut provoquer des blessures LA Chaleur DU Moteur peut pro- voquer un incendieRisque D’INCENDIE OU D’EXPLO- Sion LES Fils DE Soudage peuvent provoquer des blessures LE Surchauffement peut endom- mager le moteur électriqueDES Organes Mobiles peuvent provoquer des blessures ’EMPLOI Excessif peutInformation EMF Proposition californienne 65 AvertissementsPrincipales normes de sécurité En ce qui concerne les implants médicaux− 50 h Std − DefinitionsStd Manufacturer’s Rating Labels Symbols And Definitions Some symbols are found only on export productsWeld, Power, And Engine Specifications − SpecificationsDimensions, Weights, And Operating Angles Volt-Ampere Curves For CC Models TIG Mode Stick ModeMIG Mode Volt-Ampere Curves For CC/CV ModelsDuty Cycle And Overheating Fuel Consumption100% Duty Cycle At 400 Amperes 12 kVA/kW Single-Phase AC Output No Weld Load AC Generator Power CurveOptional Three-Phase Generator Curves 15 kVA/kW Three-Phase AC Output No Weld LoadLocation/Airflow Clearance − InstallationInstalling Welding Generator Grounding1Using Lifting Eye Mounting Welding Generator Installing Exhaust Pipe Stop engine and let coolActivating The Dry Charge Battery If Applicable Connecting The BatteryCoolant Recovery Tank Engine Prestart ChecksMIG and Fcaw Welding Connecting To Weld Output TerminalsStick and TIG Welding Stop engine150 ft 200 ft 250 ft Connecting to WeldSelecting Weld Cable Sizes 350 ft 400 ft 45 m 60 m 70 m 90 m 105 m 120 mConnecting To Remote 14 Receptacle RC14 On CC/CV Models SocketOM-4421 − Operating Welding Generator − CC Models Front Panel Controls For CC Models See SectionEngine Gauges And Meters Engine Starting ControlsTo Start Weld ControlsWeld Control/Arc Condition Information Label Remote Amperage Control On CC Models OptionalExample Combination Remote Amperage Control Stick OM-4421 − Operating Welding Generator − CC/CV Models Front Panel Controls For CC/CV Models See SectionElectric shock can kill Voltage/Amperage Adjust Switch And Remote 14 Receptacle14 AC/DC Voltmeter Optional Process/Contactor Switch On CC/CV Models Process/Contactor Switch SettingsRemote Voltage/Amperage Control On CC/CV Models Optional Example Combination Remote Amperage Control TIGAt least once a month, run en − Operating Auxiliary EquipmentVolt And 240 Volt Receptacles If a SupplementaryRear Of Panel Three-Phase Power ConnectionClose panel opening if no connections are made to generator 240 V 15 a AC South African Receptacle RC1 Optional Generator Power ReceptaclesSupplementary Protector CB2 Supplementary Protector CB3 − Maintenance & Troubleshooting Maintenance LabelRoutine Maintenance Checking Generator Brushes Servicing Air Cleaner To clean air filterInspecting And Cleaning Optional Spark Arrestor Muffler Engine Speed No Load Adjusting Engine SpeedWeld/Power Speed Adjustment Standard Model Idle Speed Ad- justmentTo replace primary fuel filter Servicing Fuel And Lubrication SystemsTo change oil and filter While draining fuel tankOverload Protection Troubleshooting Welding − CC ModelsWelding − CC/CV Models Standard Generator Power Optional Three-Phase Generator Power CC/CV Models OnlyEngine Welding Symbols − Electrical Diagrams Circuit Diagram For CC Welding Generator223 522-B Circuit Diagram For CC/CV Welding Generator 223 523-B Wetstacking − RUN-IN ProcedureWelding Generator Keep exhaust and pipe away Run-In Procedure Using Load BankFrom flammables Just generator A/V control so Run-In Procedure Using Resistance GridSpecifications section in this ManualGrounding Generator To Truck Or Trailer Frame − Generator Power GuidelinesSelecting Equipment Electrically Bond GeneratorUse ground device as stated in electrical codes Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Amperes x Volts = WattsIndustrial Motors Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Farm/Home Equipment Rating Starting Watts Running WattsApproximate Power Requirements For Contractor Equipment Contractor Rating Starting Watts Running WattsSingle-Phase Induction Motor Starting Requirements Power Required To Start MotorHow Much Power Can Generator Supply? KVA/HP x HP x 1000 / Volts = Starting AmperageTypical Connections To Supply Standby Power Selecting Extension Cord Use Shortest Cord Possible − Parts List 128 93 −6 105 104 100 101 102 103 Main Assembly 010 Figures 13-2 Figures 13-4 Control Box Assembly − CC Models 087 Control Box Assembly − CC/CV Models Control Box Assembly − CC/CV Models -1ItemTD1 214 Panel, Front w/Components − CC Models 3634Panel, Front w/Components − CC Models -1Item Panel, Front w/Components − CC/CV Models 40 39Panel, Front w/Components − CC/CV Models -1Item 170 Hardware is common Not available unless listed 34 36 27 26602 SCREW, .312−18x .75 hexwhd.66d stl pld slffmg tap−rw 601 Main Rectifier Assembly Wiring Harnesses Harness, receptacle auxiliary power export models includes PLG4Page Your distributor also gives ServiceSupport For assistance in filing or settling claims, contact To locate a Distributor or Service Agency visitMiller Electric Mfg. Co Your distributor and/or equipment manufacturer’s