6. Meaning of Alarm Messages
6. Meaning of Alarm Messages
Table of
Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on the wired remote controller.
zViewing the LED 1 and 2 (D72 and D75) alarm displays
LED1 | LED2 | Alarm contents |
|
|
|
|
| Alarm Display |
Alternating | LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats. | |
|
| M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm |
|
| N = Alarm No. |
|
| Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats. |
|
| Alarm is "P17". |
(
: Blinling) Connect the outdoor maintenance remote controller to the RC socket on the outdoor main unit control PCB (3P, blue),and check the Alarm Messages on the remote controller display.
Possible cause of malfunction |
|
|
| Alarm | ||
|
|
| Message | |||
|
|
|
|
| ||
Serial | Remote controller is detecting | Error in receiving serial communication signal. |
| |||
communication | error signal from indoor unit. | (Signal from main indoor unit in case of group control) | <E01> | |||
errors |
| Ex: Auto address is not completed. |
|
| ||
|
|
|
|
| ||
| Error in transmitting serial communication signal. | <E02> | ||||
|
| |||||
|
|
|
|
| ||
| Indoor unit is detecting error signal from remote controller (and system controller). | <<E03>> | ||||
|
|
|
|
| ||
| Indoor unit is detecting error | Error in receiving serial communication signal. |
| |||
| signal from main outdoor unit. | When turning on the power supply, the number of connected indoor units | E04 | |||
|
| does not correspond to the number set. (Except R.C. address is "0.") |
| |||
|
| Error of the main outddor unit in receiving serial communication signal | <E06> | |||
|
| from the indoor unit. |
| |||
|
|
|
| |||
| Improper setting of indoor unit | Indoor unit address setting is duplicated. | E08 | |||
| or remote controller. |
|
|
|
| |
| Remote controller adress connector (RCU. ADR) is duplicated. | <<E09>> | ||||
|
| |||||
|
| (Duplication of main remote controller) |
| |||
|
|
|
| |||
|
|
|
|
| ||
| During auto address setting, | Starting auto address setting is prohibited. |
| |||
| number of connected units does | This alarm message shows that the auto address connector CN100 is | E12 | |||
| not correspond to number set. | shorted while other RC line is executing auto address operation. |
| |||
|
| Error in auto address setting. (Number of connected indoor units is less | E15 | |||
| When turning on the power | than the number set.) |
| |||
|
|
| ||||
| supply, number of connected | Error in auto address setting. (Number of connected indoor units is more | E16 | |||
| units does not correspond to | than the number set.) |
| |||
|
|
| ||||
| number set. |
|
|
|
| |
| No indoor unit is connected during auto address setting. | E20 | ||||
| (Except R.C. address is "0.") | |||||
|
|
|
|
| ||
|
| Main outdoor unit is detecting error signal from sub outdoor unit. | E24 | |||
|
|
|
|
|
| |
|
| Error of outdoor unit address setting. |
| E25 | ||
|
|
|
|
| ||
|
| The number of connected main and sub outdoor units do not correspond | E26 | |||
|
| to the number set at main outdoor unit PCB. | ||||
|
|
| ||||
|
| Error of sub outdoor unit in receiving serial communication signal from | E29 | |||
|
| main outdoor unit. |
| |||
|
|
|
| |||
| Indoor unit communication error | Error of main indoor unit in receiving serial communication signal from | E18 | |||
| of group control wiring. | sub indoor units. |
| |||
|
|
| ||||
| Improper setting. | This alarm message shows when an indoor unit for | L02 | |||
|
| connected to the outdoor unit. |
| |||
|
|
|
| |||
|
| Duplication of main indoor unit address setting in group control. | <L03> | |||
|
|
|
|
| ||
|
| Duplication of outdoor R.C. address setting. | L04 | |||
|
|
|
|
|
| |
|
| There are 2 or more indoor unit |
| Priority set remote controller | L05 | |
|
| controllers that have oparation |
|
|
| |
|
|
| L06 | |||
|
| mode priority in refrigerant circuit. |
| |||
|
|
|
|
| ||
|
| Group control wiring is connected to individual control indoor unit. | L07 | |||
|
| Indoor unit address is not set. |
| L08 | ||
|
|
|
|
| ||
|
| Capacity code of indoor unit is not set. |
| <<L09>> | ||
|
|
|
| |||
|
| Capacity code of outdoor unit is not set. | L10 | |||
|
|
|
| |||
|
| L17 | ||||
|
| refrigerant. |
| |||
|
|
|
| |||
|
|
| L18 | |||
|
|
|
| |||
Activation of | Protective device in indoor unit | Thermal protector in indoor unit fan motor is activated. | <<P01>> | |||
protective | is activated. |
|
|
|
| |
Improper wiring connections of ceiling panel. | <<P09>> | |||||
device |
| |||||
|
|
|
|
| ||
|
| Float switch is activated. |
| <<P10>> | ||
|
|
|
| |||
|
| Operation of protective function of fan inverter. | P12 | |||
|
| O2 sensor (detects low oxygen level) activated. | P14 | |||
|
|
|
| Continued | ||