Test Run
3. Auto Address Setting
1
2
3
4
5
6
7
8
Case 3B Automatic Address Setting in Cooling Mode
zIndoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.
Automatic Address Setting from Outdoor Unit
1. Perform steps 1 - 4 in the same way as for Case 2 .
5.Turn the indoor and outdoor unit power ON at all systems.
6.To perform automatic address setting in Cooling mode , on the outdoor main unit control PCB in the refrigerant system where you wish to set the addresses,
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling mode begins.)
(All indoor units operate.)
*To cancel, again
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the outdoor main unit control PCB turn OFF.)
7.At the outdoor main unit in the next (different) system,
(Repeat the same steps to complete automatic address setting for all units.)
8.Operation from the remote controllers is now possible.
*Automatic address setting in Cooling mode cannot be done from the remote controller.
Automatic Address Setting* from the Remote Controller
Selecting each refrigerant system individually for automatic address setting
1. Press the remote controller timer time button and button at the same time.
(Press and hold for 4 seconds or longer.)
2. Next, press either the temperature setting or button. (Check that the item code is “A1.”)
3. Use either the or button to set the system No. to perform auto- matic address setting.
4. Then press the button.
(Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the system returns to normal stopped status.) <Approximately 4 - 5 minutes is required.>
(During automatic address setting, “NOW SETTING” is displayed on the remote controller. This message disappears when automatic address setting is completed.)
5.Repeat the same steps to perform automatic address setting for each successive system.