Sanyo UHX3652, UHX2452, UHX0752, UHX1252, UHX1852, THX2452, THX1252, THX1852 Check of Density Limit

Page 3

Check of Density Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrig- erant gas leaking out, its density will not exceed a set limit.

The refrigerant (R410A), which is used in the air con- ditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the num- ber of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc.

Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro- cedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

In a room where the density may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density is as given below.

Total amount of refrigerant (lbs)

Min. volume of the indoor unit installed room (ft.3)

<Density limit (oz/ft.3)

The density limit of refrigerant which is used in multi air conditioners is 0.3 oz/ft.3 (ISO 5149).

NOTE

1.If there are 2 or more refrigerating systems in a single refrigerating device, the amount of refrigerant should be as charged in each independent device.

For the amount of charge in this example:

Outdoor unit

e.g., charged

 

 

 

 

 

 

e.g., charged

 

amount (353 oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

amount (529 oz)

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room A Room B Room C Room D Room E Room F

The possible amount of leaked refrigerant gas in rooms A, B and C is 353 oz.

The possible amount of leaked refrigerant gas in rooms D, E and F is 529 oz.

2.The standards for minimum room volume are as fol- lows.

(1) No partition (shaded portion)

(2)When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (open- ing without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).

Outdoor unit

Refrigerant tubing

Indoor unit

(3)If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.

 

 

Refrigerant tubing

 

 

Outdoor unit

Very

 

 

small

 

Indoor unit

room

 

 

 

Small

Medium

Large room

room

room

 

Mechanical ventilation device – Gas leak detector

3.The minimum indoor floor space compared with the amount of refrigerant is roughly as follows: (When the ceiling is 8.8 ft. high)

 

ft.3

 

 

 

 

 

 

 

 

 

 

ft.2

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

454

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

Range below

 

 

 

 

 

 

398

indoorMin. floor area ceilingthe(when is 8.8 ft. high)

 

 

 

 

 

 

 

 

 

3000

 

the density limit of

 

 

 

 

341

indoorMin. volume

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

(countermeasures

 

 

500

 

(countermeasures

 

 

57

 

2500

 

not needed)

 

 

 

 

 

 

284

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

227

 

 

1500

 

 

 

 

 

Range above

 

170

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

the density limit of

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

0

 

 

 

 

 

needed)

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

200

400

600

800

1000

1200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oz

 

Total amount of refrigerant

ii

Image 3
Contents Outdooe Units „ R410A Models Indoor UnitsPage Check of Density Limit Contents Test RUN ContentsPreparing for Test Run Test RunItems to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Setting of Unit Control PCBUnit No. setting Indoor unit setting S004 Rotary switch, redSystem address S003 System address No P DIP switch, blue 10 No. of outdoor units Outdoor unit setting S006Auto Address Setting Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit 22-9 RefrigerantCircuit Units Case 2 Automatic Address Setting no compressor operationAutomatic Address Setting from Outdoor Unit On the NoCase 3A Automatic Address Setting in Heating Mode Case 3B Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerDisplay during automatic address setting Remote controller displayOn outdoor main unit PCB Use the remote controller to check the indoor unit address Auto Address Setting Remote Controller Test Run SettingsIf 1 indoor unit is connected to 1 remote controller Remote Controller Test Run SettingsTest Run Meaning of Alarm Messages Alarm contentsPossible cause of malfunction P02 Alarm messages displayed on system controller Wireless Remote Controller Timer Remote Controller RCS-TM80BGMain Operating Functions Deg Room Temperature ControlMain Operating Functions Thermostat is turned ON/OFF according to as shown belowAfter the compressor turns on Operating mode change Shifted set tempFAN Speed selector button Wireless Remote ControllerMode button TransmitterC Sensor button Cool mode and Dry mode, if the flaps are set in a downwardFilter button Address buttonOFF Cycle Timer Indicator when swing operation is stoppedTimer SET button OFF TimerReceiver Control Temperature sensors at the indoor unit side are usedOperation Multiple units GroupUsing the Wireless Remote Control Unit How to install batteriesCover Address Settings D type TypeControl unit will not be accepted Emergency OperationOperation ShutdownPress the Emergency operation button once more Troubleshooting Trouble Possible Cause RemedyTrouble Possible Cause How to Use the Timer Remote Controller Operating buttons Timer Remote Controller RCS-TM80BGNames and Operations Timer OFF indication Display Section Refer to Setting indicationTimer No. indication Timer programHow to install the Remote Controller Installation Manual for Timer Remote ControllerTo Display the Sensor Temperature Group Control Using 2 Remote ControllersRemote Controller Setting Mode Indoor Unit Setting Mode13/32 Press To change the present hour in the range of 0 to 23 Setting the Present TimeOnce you enter in the setting mode Day and time fl ash Set to today’s day of the weekSelect a Timer number Weekly Program Function Checking Weekly TimerProgram image diagram Press To enter the program confirmation mode Start settingSet the minute. program step Set the hour. program stepIndoor unit starts operation at the programmed time Press / to change the temperature settingSet the program pattern. program step PatternDeleting the Program Timer How to invalidate the program timerHow to cancel the program timer invalidation If Power Failure OccurredBefore Asking Repair Work Duplicating the Program TimerYou can duplicate the preset program by day Select the copy sourceOuting Function Precautions„ For Example Setting at Outing Temperature 86F 30C Room temperatureCanceling the outing function Outing function indicationOuting function indication Status Sleeping Function Wired Remote Controller Test Run Settings Simple Settings Function ProcedureList of Simple Setting Items Detailed Settings Functions List of Detailed Setting Items Setting dataDescription Item code Setting data Description Code Description Setting dataTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Remote Controller Servicing Functions Display Sensor Servicing check Alarm history Press and holdMaintained Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 Display meaning Are occurring Automatic address setting is in progressNumber that was set Alarm display OFFAlarm code Alarm meaning 2WAY ECO-i Alarm CodesE15 Alarm Alarm code E06 Alaral rm Alarm codeAlarm E04 occurs E12 Alarm Alarm codeAt a number of indoor units E16 Alarm Alarm codeE20 Alarm Alarm code E24 Alarm Alarm codePower at the outdoor unit main is turned OFF E25 Alarm Alarm codeE26 Alarm Alarm code E29 Alarm Alarm codeOutdoor unit control PCB F04, F05, F22 Alarm Alarm codeCrossed wiring or installation error Check Check for crossed wiring and installation errorsAlarm meaning Identification of the problem in this caseF06, F23 Alarm Alarm code F07, F24 Alarm Alarm codeF08 Alarm code F12F16 Alarm Alarm code F17 Alarm Alarm codeH03 alarm Alarm code F31 Alarm Alarm codeValve must be replaced H06 Alarm Alarm codeOn the degree of the problem Which may damage the compressorH11, H12, H21, H22 Alarm Alarm code H05, H15, H25 Alarm Alarm code H13, H23 Alarm Alarm codeH31 Alarm Alarm code L04 Alarm Alarm codeL05 Alarm Alarm code L18 alarm Alarm code L06 Alarm Alarm codeL10 Alarm Alarm code L17 Alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code Noise in some cases P05 Alarm Alarm codeP16 Alarm Alarm code Primary or secondary currentP22 Alarm Alarm code P26 Alarm Alarm codeP29 Alarm Alarm code Blinking inspection display 1 Automatic backup Alarm code Blinking Inspection displayCompressor magnet SW seizing detection Corresponding outdoor unit Alarm meaning Compressor magnet SW seizing detectedAlarm may be caused by the effects of noise. See notes Within that refrigerant tubing system are stoppedPage PCB and Functions Outdoor Unit Control PCB CR-CHDX14053 Outdoor Unit Control PCBFunctions for CR-CHDX14053 Progress will stop the automatic address setting operationOutdoor Unit Control PCB Mode. Static signalLink wiring Setting the Outdoor Unit address S007 Setting AddressSystem only Indoor Unit Control PCB T10JP1 For DC Fan Motor CR-SXRP56B-B For AC Fan Motor CR-UXRP71B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted Signal. Jumper wire cut Static signal continuous signal Or lessCN017 CN014 OptionSELF-DIAGNOSIS Function Table Trouble Cause and correction Alarm displayAlarm descriptionSelf-Diagnosis Function Table Self-Diagnosis Function TableCause Check items E15 E16 E20DISCH2 Alarm code Alarm meaningService Checker Outdoor Unit Maintenance Remote Controller System DiagramFunctions Functions on the ordinary display All units test run Fig Temperature monitorAll units start/stop Fig Cooling/heating change FigDisplay functions Item codes can be changed with ButtonsItem code Remarks Sample display -4, Fig XX-YY R.CSample Display A, B Outdoor unit Monitoring OperationsDisplay of unit No main unit Indoor unitOutdoor Unit Alarm History Monitor Code Parameter Description SET Data „ Setting modeParameter Description SET Data „ Setting modePage 200706MDC