Sanyo AHX0952 Alarm meaning Compressor magnet SW seizing detected, Corresponding outdoor unit

Page 85

Trouble Diagnosis

4. Blinking (Inspection) Display on the Remote Controller

Blinking inspection display (2) (compressor magnet SW seizing detection)

Alarm code

(Blinking

inspection display)

 

 

Alarm meaning

Compressor magnet SW seizing detected

 

Status: The compressor and outdoor unit fan motor continue to run even though all indoor units

 

within that refrigerant tubing system are stopped.

 

 

Because the fan is running only at the outdoor unit where seizing was detected, check

 

 

the corresponding outdoor unit.

 

 

* The fan may also run on its own when fan cracking prevention control is in effect or

 

 

when snowfall sensor input is present. Therefore monitor for approximately 10

 

 

minutes if the outdoor unit fans are operating at multiple units.

Alarm conditions

Current is detected in the CT circuit when the compressor is stopped.

 

(1) This control is not engaged for the first 30 seconds after the compressor turns ON OFF.

 

(2) For 1 minute following the first 30 seconds after the compressor turned ON OFF, the

 

threshold for the detected current is 10 A or more continuing for 2 seconds.

 

(3) All times other than the above:

 

If the low-pressure SW has not activated, the threshold for the detected current is 7 A or

 

more continuing for 5 seconds.

 

If the low-pressure switch has activated, the threshold for the detected current is 7 A or

 

more continuing for 2 seconds.

Probable cause

(1) Magnet SW malfunction

 

The magnet SW has seized, and the compressor is continuing to run.

 

Even when the power is turned OFF, the primary side and secondary side contacts

 

remain together.

 

The conditions of magnet SW operation are poor (difficult to open).

 

When a magnet SW is used in a DC circuit, it may be difficult for the SW to open at

 

times. In an AC circuit the magnet SW should open instantaneously as long as the

 

current is within the allowable range. However, this kind of trouble can occur if

 

excessive current flows, and may prevent the SW from opening.

 

(2) CT circuit failure or PCB failure (A/D failure)

 

CT circuit contact failure

 

Check that the connector is not partially disconnected.

 

Wiggle the connector to check the connection.*

 

* These symptoms will not occur if the connector is completely disconnected or the

 

 

wire is cut. In these cases alarm Hx3 occurs.

 

Current of 7A or higher was detected although the compressor was stopped, or a

 

higher current was detected at occasional intervals.

 

The compressor continues to operate at a time when the outdoor unit should be

 

stopped (such as when all indoor units are stopped).

 

Check whether or not 200 V is output from the PCB to the magnet SW. If the voltage

 

is output, there is a PCB failure.

 

(3) Installation error

 

CT1 connector is connected to the compressor 2 side

 

CT1 circuit is connected to the compressor 2 side

 

CT2 connector is connected to the compressor 1 side

 

CT2 circuit is connected to the compressor 1 side

 

 

Correction

(1) Replace the CT circuit.

 

(2) Replace the magnet SW.

 

(3) Replace the PCB.

 

If the above probable causes are not the cause of the alarm, it is possible that in rare cases

 

the alarm may be caused by the effects of noise. See notes.

 

 

 

Notes

 

 

 

 

3-23

1

2

3

4

5

6

7

8

Image 85
Contents Outdooe Units „ R410A Models Indoor UnitsPage Check of Density Limit Contents Test RUN ContentsPreparing for Test Run Test RunItems to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Setting of Unit Control PCBSystem address S003 System address No P DIP switch, blue 10 Indoor unit setting S004 Rotary switch, redNo. of outdoor units Outdoor unit setting S006 Unit No. settingAuto Address Setting Basic wiring diagram Example Auto Address SettingAutomatic Address Setting from the Outdoor Unit Refrigerant 22-9Circuit Automatic Address Setting from Outdoor Unit Case 2 Automatic Address Setting no compressor operationOn the No UnitsCase 3A Automatic Address Setting in Heating Mode Case 3B Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerRemote controller display Display during automatic address settingOn outdoor main unit PCB If 1 indoor unit is connected to 1 remote controller Auto Address Setting Remote Controller Test Run SettingsRemote Controller Test Run Settings Use the remote controller to check the indoor unit addressTest Run Alarm contents Meaning of Alarm MessagesPossible cause of malfunction P02 Alarm messages displayed on system controller Timer Remote Controller RCS-TM80BG Wireless Remote ControllerMain Operating Functions Main Operating Functions Room Temperature ControlThermostat is turned ON/OFF according to as shown below DegAfter the compressor turns on Operating mode change Shifted set tempMode button Wireless Remote ControllerTransmitter FAN Speed selector buttonFilter button Cool mode and Dry mode, if the flaps are set in a downwardAddress button C Sensor buttonTimer SET button Indicator when swing operation is stoppedOFF Timer OFF Cycle TimerReceiver Operation Temperature sensors at the indoor unit side are usedMultiple units Group ControlHow to install batteries Using the Wireless Remote Control UnitCover Address Settings D type TypeOperation Emergency OperationShutdown Control unit will not be acceptedPress the Emergency operation button once more Trouble Possible Cause Remedy TroubleshootingTrouble Possible Cause How to Use the Timer Remote Controller Operating buttons Timer Remote Controller RCS-TM80BGNames and Operations Timer No. indication Display Section Refer to Setting indicationTimer program Timer OFF indicationHow to install the Remote Controller Installation Manual for Timer Remote ControllerRemote Controller Setting Mode Group Control Using 2 Remote ControllersIndoor Unit Setting Mode To Display the Sensor Temperature13/32 Once you enter in the setting mode Day and time fl ash Setting the Present TimeSet to today’s day of the week Press To change the present hour in the range of 0 to 23Program image diagram Weekly Program Function Checking Weekly TimerPress To enter the program confirmation mode Start setting Select a Timer numberSet the minute. program step Set the hour. program stepSet the program pattern. program step Press / to change the temperature settingPattern Indoor unit starts operation at the programmed timeHow to cancel the program timer invalidation How to invalidate the program timerIf Power Failure Occurred Deleting the Program TimerYou can duplicate the preset program by day Duplicating the Program TimerSelect the copy source Before Asking Repair Work„ For Example Setting at Outing Temperature 86F 30C PrecautionsRoom temperature Outing FunctionOuting function indication Canceling the outing functionOuting function indication Status Sleeping Function Wired Remote Controller Test Run Settings Simple Settings Function ProcedureList of Simple Setting Items Detailed Settings Functions Setting data List of Detailed Setting ItemsDescription Item code Setting data Description Code Description Setting dataTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Display Sensor Servicing check Alarm history Press and hold Remote Controller Servicing FunctionsMaintained Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 Number that was set Alarm display Are occurring Automatic address setting is in progressOFF Display meaningAlarm code Alarm meaning 2WAY ECO-i Alarm CodesAlarm E04 occurs E06 Alaral rm Alarm codeE12 Alarm Alarm code E15 Alarm Alarm codeE20 Alarm Alarm code E16 Alarm Alarm codeE24 Alarm Alarm code At a number of indoor unitsE26 Alarm Alarm code E25 Alarm Alarm codeE29 Alarm Alarm code Power at the outdoor unit main is turned OFFCrossed wiring or installation error F04, F05, F22 Alarm Alarm codeCheck Check for crossed wiring and installation errors Outdoor unit control PCBF06, F23 Alarm Alarm code Identification of the problem in this caseF07, F24 Alarm Alarm code Alarm meaningF16 Alarm Alarm code Alarm code F12F17 Alarm Alarm code F08H03 alarm Alarm code F31 Alarm Alarm codeOn the degree of the problem H06 Alarm Alarm codeWhich may damage the compressor Valve must be replacedH11, H12, H21, H22 Alarm Alarm code H05, H15, H25 Alarm Alarm code H13, H23 Alarm Alarm codeL04 Alarm Alarm code H31 Alarm Alarm codeL05 Alarm Alarm code L10 Alarm Alarm code L06 Alarm Alarm codeL17 Alarm Alarm code L18 alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code P16 Alarm Alarm code P05 Alarm Alarm codePrimary or secondary current Noise in some casesP26 Alarm Alarm code P22 Alarm Alarm codeP29 Alarm Alarm code Alarm code Blinking Inspection display Blinking inspection display 1 Automatic backupCompressor magnet SW seizing detection Alarm may be caused by the effects of noise. See notes Alarm meaning Compressor magnet SW seizing detectedWithin that refrigerant tubing system are stopped Corresponding outdoor unitPage PCB and Functions Outdoor Unit Control PCB CR-CHDX14053 Outdoor Unit Control PCBFunctions for CR-CHDX14053 Progress will stop the automatic address setting operationOutdoor Unit Control PCB Mode. Static signalSetting the Outdoor Unit address S007 Setting Address Link wiringSystem only T10 Indoor Unit Control PCBJP1 For DC Fan Motor CR-SXRP56B-B For AC Fan Motor CR-UXRP71B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted Or less Signal. Jumper wire cut Static signal continuous signalCN017 CN014 OptionSELF-DIAGNOSIS Function Table Self-Diagnosis Function Table Alarm displayAlarm descriptionSelf-Diagnosis Function Table Trouble Cause and correctionCause Check items E15 E16 E20DISCH2 Alarm code Alarm meaningService Checker System Diagram Outdoor Unit Maintenance Remote ControllerFunctions Functions on the ordinary display All units start/stop Fig Temperature monitorCooling/heating change Fig All units test run FigItem codes can be changed with Buttons Display functionsItem code Remarks Sample display -4, Fig XX-YY R.CSample Display A, B Display of unit No main unit Monitoring OperationsIndoor unit Outdoor unitOutdoor Unit Alarm History Monitor Code Parameter Description SET Data „ Setting modeParameter Description SET Data „ Setting modePage 200706MDC