Sanyo XHX1852, UHX2452, UHX0752, UHX1252, UHX3652, UHX1852 F31 Alarm Alarm code, H03 alarm Alarm code

Page 74

1

2

3

4

5

6

7

8

Trouble Diagnosis

3. W-2WAY ECO-i Alarm Codes

F31 Alarm

Alarm code

F31

 

 

Alarm meaning

Outdoor unit non-volatile memory (EEPROM) trouble

Alarm conditions

(1)

Non-volatile memory is not present when power initialization occurs.

 

(2)

Read values do not match after writing to non-volatile memory is complete.

Probable cause

(1)

Memory was not inserted after the PCB was replaced.

 

(2) The lifetime of the non-volatile memory has been reached.

 

(3)

Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).

Check

(1)

Check the non-volatile memory on the PCB.

Correction

 

Example

 

Notes

 

 

 

 

H03 alarm

 

 

 

 

Alarm code

H03

 

 

Alarm meaning

Compressor CT sensor disconnected or short-circuit

 

 

Alarm conditions

Alarm occurs if the current value is 1.5 A or less when 2 seconds or longer have elapsed after

 

output from that compressor started.

 

* No current is detected even though the compressor is operating.

Probable cause

(1)

CT circuit failure (including cut wiring, etc.)

 

(2)

Disconnected CT circuit connector

 

(3) This CT circuit is connected to the connector of the other CT circuit.

 

(4)

PCB failure

 

(5)

Noise

Check

(1)

CT circuit failure, PCB failure

 

 

Trouble: • Current value during compressor operation is below the threshold value.

 

 

Check: • Check that the connector is not disconnected.

 

 

• Check the continuity of the CT circuit.

 

 

Install a normal CT in place of this CT and check. If current is detected, then the

 

 

PCB can be judged OK.

 

 

CT circuit failure

 

 

• Check that current is flowing in the phase where the CT circuit is connected.

 

 

Check voltage and current.

 

(2)

Crossed wiring or installation error

 

 

Trouble: When the compressor is stopped, the current value at the other compressor is high.

 

(3)

If the cause is still unknown after checking the above, then it is possible that noise is the

 

 

cause of the trouble. It is necessary to connect a PC or other instrument.

 

 

 

Correction

(1)

Replace the CT circuit.

 

(2)

Replace the outdoor unit PCB.

 

(3)

Correct the problem.

Example

(1) The connector was not inserted after the PCB was replaced.

Notes

Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.

3-12

Image 74
Contents „ R410A Models Indoor Units Outdooe UnitsPage Check of Density Limit Contents Contents Test RUNTest Run Preparing for Test RunTest Run Procedure Items to Check Before the Test RunSetting of Unit Control PCB Main Outdoor Unit PCB SettingNo. of outdoor units Outdoor unit setting S006 Indoor unit setting S004 Rotary switch, redSystem address S003 System address No P DIP switch, blue 10 Unit No. settingAutomatic Address Setting from the Outdoor Unit Auto Address SettingAuto Address Setting Basic wiring diagram Example Circuit 22-9Refrigerant On the No Case 2 Automatic Address Setting no compressor operationAutomatic Address Setting from Outdoor Unit UnitsCase 3A Automatic Address Setting in Heating Mode Automatic Address Setting* from the Remote Controller Case 3B Automatic Address Setting in Cooling ModeOn outdoor main unit PCB Display during automatic address settingRemote controller display Remote Controller Test Run Settings Auto Address Setting Remote Controller Test Run SettingsIf 1 indoor unit is connected to 1 remote controller Use the remote controller to check the indoor unit addressTest Run Possible cause of malfunction Meaning of Alarm MessagesAlarm contents P02 Alarm messages displayed on system controller Main Operating Functions Wireless Remote ControllerTimer Remote Controller RCS-TM80BG Thermostat is turned ON/OFF according to as shown below Room Temperature ControlMain Operating Functions DegOperating mode change Shifted set temp After the compressor turns onTransmitter Wireless Remote ControllerMode button FAN Speed selector buttonAddress button Cool mode and Dry mode, if the flaps are set in a downwardFilter button C Sensor buttonOFF Timer Indicator when swing operation is stoppedTimer SET button OFF Cycle TimerReceiver Multiple units Group Temperature sensors at the indoor unit side are usedOperation ControlCover Using the Wireless Remote Control UnitHow to install batteries Address Settings Type D typeShutdown Emergency OperationOperation Control unit will not be acceptedPress the Emergency operation button once more Trouble Possible Cause TroubleshootingTrouble Possible Cause Remedy Timer Remote Controller RCS-TM80BG How to Use the Timer Remote Controller Operating buttonsNames and Operations Timer program Display Section Refer to Setting indicationTimer No. indication Timer OFF indicationInstallation Manual for Timer Remote Controller How to install the Remote ControllerIndoor Unit Setting Mode Group Control Using 2 Remote ControllersRemote Controller Setting Mode To Display the Sensor Temperature13/32 Set to today’s day of the week Setting the Present TimeOnce you enter in the setting mode Day and time fl ash Press To change the present hour in the range of 0 to 23Press To enter the program confirmation mode Start setting Weekly Program Function Checking Weekly TimerProgram image diagram Select a Timer numberSet the hour. program step Set the minute. program stepPattern Press / to change the temperature settingSet the program pattern. program step Indoor unit starts operation at the programmed timeIf Power Failure Occurred How to invalidate the program timerHow to cancel the program timer invalidation Deleting the Program TimerSelect the copy source Duplicating the Program TimerYou can duplicate the preset program by day Before Asking Repair WorkRoom temperature Precautions„ For Example Setting at Outing Temperature 86F 30C Outing FunctionOuting function indication Status Canceling the outing functionOuting function indication Sleeping Function Wired Remote Controller Test Run Settings Procedure Simple Settings FunctionList of Simple Setting Items Detailed Settings Functions Description List of Detailed Setting ItemsSetting data Item code Setting data Description Setting data Code DescriptionTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Maintained Remote Controller Servicing FunctionsDisplay Sensor Servicing check Alarm history Press and hold Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 OFF Are occurring Automatic address setting is in progressNumber that was set Alarm display Display meaning2WAY ECO-i Alarm Codes Alarm code Alarm meaningE12 Alarm Alarm code E06 Alaral rm Alarm codeAlarm E04 occurs E15 Alarm Alarm codeE24 Alarm Alarm code E16 Alarm Alarm codeE20 Alarm Alarm code At a number of indoor unitsE29 Alarm Alarm code E25 Alarm Alarm codeE26 Alarm Alarm code Power at the outdoor unit main is turned OFFCheck Check for crossed wiring and installation errors F04, F05, F22 Alarm Alarm codeCrossed wiring or installation error Outdoor unit control PCBF07, F24 Alarm Alarm code Identification of the problem in this caseF06, F23 Alarm Alarm code Alarm meaningF17 Alarm Alarm code Alarm code F12F16 Alarm Alarm code F08F31 Alarm Alarm code H03 alarm Alarm codeWhich may damage the compressor H06 Alarm Alarm codeOn the degree of the problem Valve must be replacedH11, H12, H21, H22 Alarm Alarm code H13, H23 Alarm Alarm code H05, H15, H25 Alarm Alarm codeL05 Alarm Alarm code H31 Alarm Alarm codeL04 Alarm Alarm code L17 Alarm Alarm code L06 Alarm Alarm codeL10 Alarm Alarm code L18 alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code Primary or secondary current P05 Alarm Alarm codeP16 Alarm Alarm code Noise in some casesP29 Alarm Alarm code P22 Alarm Alarm codeP26 Alarm Alarm code Compressor magnet SW seizing detection Blinking inspection display 1 Automatic backupAlarm code Blinking Inspection display Within that refrigerant tubing system are stopped Alarm meaning Compressor magnet SW seizing detectedAlarm may be caused by the effects of noise. See notes Corresponding outdoor unitPage PCB and Functions Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CHDX14053Progress will stop the automatic address setting operation Functions for CR-CHDX14053Mode. Static signal Outdoor Unit Control PCBSystem only Link wiringSetting the Outdoor Unit address S007 Setting Address JP1 Indoor Unit Control PCBT10 For AC Fan Motor CR-UXRP71B-B For DC Fan Motor CR-SXRP56B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted CN017 Signal. Jumper wire cut Static signal continuous signalOr less Option CN014SELF-DIAGNOSIS Function Table Self-Diagnosis Function Table Alarm displayAlarm descriptionSelf-Diagnosis Function Table Trouble Cause and correctionCheck items E15 E16 E20 CauseAlarm code Alarm meaning DISCH2Service Checker Functions Functions on the ordinary display Outdoor Unit Maintenance Remote ControllerSystem Diagram Cooling/heating change Fig Temperature monitorAll units start/stop Fig All units test run FigItem code Remarks Display functionsItem codes can be changed with Buttons XX-YY R.C Sample display -4, FigSample Display A, B Indoor unit Monitoring OperationsDisplay of unit No main unit Outdoor unitOutdoor Unit Alarm History Monitor „ Setting mode Code Parameter Description SET Data„ Setting mode Parameter Description SET DataPage 200706MDC