Sanyo AHX1252, UHX2452, UHX0752, UHX1252, UHX3652 Blinking inspection display 1 Automatic backup

Page 84

Trouble Diagnosis

4. Blinking (Inspection) Display on the Remote Controller

CAUTION

Currently the blinking inspection display can be displayed only on the wired remote controller and system remote controller.

1

2

3

4

5

6

7

8

Blinking inspection display (1) (Automatic backup)

Alarm code

(Blinking

inspection display)

 

 

Alarm meaning

Automatic backup is in progress. A/C units can be operated.

 

Status: The compressor at one of the outdoor units where the outdoor unit fan is running

 

should be operating.

 

* Blinking inspection display also occurs when seizing of the compressor magnet SW is

 

 

detected. Because this may also be the case, refer to “Blinking inspection display (2)

 

(compressor magnet SW seizing detection).”

Alarm conditions

When alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device

 

(remote controller, etc.) input engages this mode.

 

 

Probable cause

Because alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history

 

then refer to the corresponding items.

 

 

Correction

Follow the instructions in the corresponding items to correct the trouble.

 

 

Recovery

After repairing the malfunctioning locations, reset the power for the system (all outdoor units).

 

Caution: Automatic backup mode will not be canceled until the power is reset.

Notes

Automatic backup mode is not engaged in cases of alarms other than those listed above.

 

Reasons: There is no need for automatic backup if recovery is possible by correcting the

 

 

remote controller input.

 

 

With alarms for which automatic recovery is possible (such as sensor alarms), the

 

 

presence of electrical noise may result in a new alarm. Howeve r, it is believed that

 

 

this occurs for a comparatively short time only. In these cases, a mode (automatic

 

 

backup mode) that limits operation may be engaged.

 

 

Control is not possible when a communications system alarm has occurred.

 

 

Automatic backup mode is not engaged in order to avoid causing secondary

 

 

damage.

 

 

 

3-22

Image 84
Contents „ R410A Models Indoor Units Outdooe UnitsPage Check of Density Limit Contents Contents Test RUNTest Run Preparing for Test RunTest Run Procedure Items to Check Before the Test RunSetting of Unit Control PCB Main Outdoor Unit PCB SettingIndoor unit setting S004 Rotary switch, red System address S003 System address No P DIP switch, blue 10No. of outdoor units Outdoor unit setting S006 Unit No. settingAuto Address Setting Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit 22-9 RefrigerantCircuit Case 2 Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor UnitOn the No UnitsCase 3A Automatic Address Setting in Heating Mode Automatic Address Setting* from the Remote Controller Case 3B Automatic Address Setting in Cooling ModeDisplay during automatic address setting Remote controller displayOn outdoor main unit PCB Auto Address Setting Remote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerRemote Controller Test Run Settings Use the remote controller to check the indoor unit addressTest Run Meaning of Alarm Messages Alarm contentsPossible cause of malfunction P02 Alarm messages displayed on system controller Wireless Remote Controller Timer Remote Controller RCS-TM80BGMain Operating Functions Room Temperature Control Main Operating FunctionsThermostat is turned ON/OFF according to as shown below DegOperating mode change Shifted set temp After the compressor turns onWireless Remote Controller Mode buttonTransmitter FAN Speed selector buttonCool mode and Dry mode, if the flaps are set in a downward Filter buttonAddress button C Sensor buttonIndicator when swing operation is stopped Timer SET buttonOFF Timer OFF Cycle TimerReceiver Temperature sensors at the indoor unit side are used OperationMultiple units Group ControlUsing the Wireless Remote Control Unit How to install batteriesCover Address Settings Type D typeEmergency Operation OperationShutdown Control unit will not be acceptedPress the Emergency operation button once more Troubleshooting Trouble Possible Cause RemedyTrouble Possible Cause Timer Remote Controller RCS-TM80BG How to Use the Timer Remote Controller Operating buttonsNames and Operations Display Section Refer to Setting indication Timer No. indicationTimer program Timer OFF indicationInstallation Manual for Timer Remote Controller How to install the Remote ControllerGroup Control Using 2 Remote Controllers Remote Controller Setting ModeIndoor Unit Setting Mode To Display the Sensor Temperature13/32 Setting the Present Time Once you enter in the setting mode Day and time fl ashSet to today’s day of the week Press To change the present hour in the range of 0 to 23Weekly Program Function Checking Weekly Timer Program image diagramPress To enter the program confirmation mode Start setting Select a Timer numberSet the hour. program step Set the minute. program stepPress / to change the temperature setting Set the program pattern. program stepPattern Indoor unit starts operation at the programmed timeHow to invalidate the program timer How to cancel the program timer invalidationIf Power Failure Occurred Deleting the Program TimerDuplicating the Program Timer You can duplicate the preset program by daySelect the copy source Before Asking Repair WorkPrecautions „ For Example Setting at Outing Temperature 86F 30CRoom temperature Outing FunctionCanceling the outing function Outing function indicationOuting function indication Status Sleeping Function Wired Remote Controller Test Run Settings Procedure Simple Settings FunctionList of Simple Setting Items Detailed Settings Functions List of Detailed Setting Items Setting dataDescription Item code Setting data Description Setting data Code DescriptionTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Remote Controller Servicing Functions Display Sensor Servicing check Alarm history Press and holdMaintained Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 Are occurring Automatic address setting is in progress Number that was set Alarm displayOFF Display meaning2WAY ECO-i Alarm Codes Alarm code Alarm meaningE06 Alaral rm Alarm code Alarm E04 occursE12 Alarm Alarm code E15 Alarm Alarm codeE16 Alarm Alarm code E20 Alarm Alarm codeE24 Alarm Alarm code At a number of indoor unitsE25 Alarm Alarm code E26 Alarm Alarm codeE29 Alarm Alarm code Power at the outdoor unit main is turned OFFF04, F05, F22 Alarm Alarm code Crossed wiring or installation errorCheck Check for crossed wiring and installation errors Outdoor unit control PCBIdentification of the problem in this case F06, F23 Alarm Alarm codeF07, F24 Alarm Alarm code Alarm meaningAlarm code F12 F16 Alarm Alarm codeF17 Alarm Alarm code F08F31 Alarm Alarm code H03 alarm Alarm codeH06 Alarm Alarm code On the degree of the problemWhich may damage the compressor Valve must be replacedH11, H12, H21, H22 Alarm Alarm code H13, H23 Alarm Alarm code H05, H15, H25 Alarm Alarm codeH31 Alarm Alarm code L04 Alarm Alarm codeL05 Alarm Alarm code L06 Alarm Alarm code L10 Alarm Alarm codeL17 Alarm Alarm code L18 alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code P05 Alarm Alarm code P16 Alarm Alarm codePrimary or secondary current Noise in some casesP22 Alarm Alarm code P26 Alarm Alarm codeP29 Alarm Alarm code Blinking inspection display 1 Automatic backup Alarm code Blinking Inspection displayCompressor magnet SW seizing detection Alarm meaning Compressor magnet SW seizing detected Alarm may be caused by the effects of noise. See notesWithin that refrigerant tubing system are stopped Corresponding outdoor unitPage PCB and Functions Outdoor Unit Control PCB Outdoor Unit Control PCB CR-CHDX14053Progress will stop the automatic address setting operation Functions for CR-CHDX14053Mode. Static signal Outdoor Unit Control PCBLink wiring Setting the Outdoor Unit address S007 Setting AddressSystem only Indoor Unit Control PCB T10JP1 For AC Fan Motor CR-UXRP71B-B For DC Fan Motor CR-SXRP56B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted Signal. Jumper wire cut Static signal continuous signal Or lessCN017 Option CN014SELF-DIAGNOSIS Function Table Alarm displayAlarm description Self-Diagnosis Function TableSelf-Diagnosis Function Table Trouble Cause and correctionCheck items E15 E16 E20 CauseAlarm code Alarm meaning DISCH2Service Checker Outdoor Unit Maintenance Remote Controller System DiagramFunctions Functions on the ordinary display Temperature monitor All units start/stop FigCooling/heating change Fig All units test run FigDisplay functions Item codes can be changed with ButtonsItem code Remarks XX-YY R.C Sample display -4, FigSample Display A, B Monitoring Operations Display of unit No main unitIndoor unit Outdoor unitOutdoor Unit Alarm History Monitor „ Setting mode Code Parameter Description SET Data„ Setting mode Parameter Description SET DataPage 200706MDC