Sanyo THX1852, UHX2452 Using the Wireless Remote Control Unit, How to install batteries, Cover

Page 29

Remote Control Functions

2. Wireless Remote Controller

4. Using the Wireless Remote Control Unit

Slide switch This is used to set the operation mode of the indoor units and to set the flaps.

Depending on the indoor unit used, the operation display and airflow direction display settings will differ as shown below.

Use a pointed implement to change the switch position.

When the switch position has been changed, press the ACL button.

* For details on the flap functions, refer to the operating instructions of the indoor unit used.

With the battery cover removed

How to install batteries

How to use the wireless remote control unit

Model which supports

Swing-only model

No-flap model

different flap settings

 

 

Slide switch position

Flap display on wireless remote control unit

Heat pump (with auto

Heat pump (without

 

cooling/heating

auto cooling/heating

Cooling only

function)

function)

 

Operation mode display on wireless remote control unit

Slide switch position

Before use, check that the slide switch has been set to the position shown in the figure above. For details on how to set the slide switch, consult your dealer.

1.Slide the cover in the direction indicated by the arrow and remove it.

2.Install two AAA alkaline batteries. Make sure the batteries point in the direction marked in the battery compartment.

3.Use a pointed implement to press the ACL button.

• The batteries last about a year, depending on how much

 

you use the wireless remote control unit. Replace the

ACL

batteries when the wireless remote control unit's display

button

fails to light, or when the remote control cannot be used

Cover

to change the air conditioner's settings.

 

When the batteries are to be replaced, make sure that both batteries are new and that the same kind of battery is used.

Remove the batteries if the wireless remote control unit is not going to be used for a prolonged period.

Dispose of the used batteries at the designated location.

Point the wireless remote control unit's transmitter at the signal receiver. If the signal is received properly, a beep is heard. (Two beeps are heard only when operation starts up.)

Signals can be received over a distance of approximately 26 ft. This distance is approximate: it may be slightly more or less depending on how much charge remains in the batteries and on other factors.

Ensure that the signals will not be blocked by any objects positioned between the transmitter and signal receiver.

Avoid placing the wireless remote control unit where it will be exposed to direct sunlight or in the direct path of the air blown out from the air conditioner, near a heating appliance, etc.

Do not drop, throw or wash the wireless remote control unit.

Signal reception may not be accepted in rooms with fluorescent lights that use the electronic instantaneous lighting system (rapid start system) or inverter system.

For further details, contact your dealer.

1

1

2

2

3

3

4

4

5

5

6

6

7

7

2-9

8

8

Image 29
Contents Outdooe Units „ R410A Models Indoor UnitsPage Check of Density Limit Contents Test RUN ContentsPreparing for Test Run Test RunItems to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Setting of Unit Control PCBSystem address S003 System address No P DIP switch, blue 10 Indoor unit setting S004 Rotary switch, redNo. of outdoor units Outdoor unit setting S006 Unit No. settingAutomatic Address Setting from the Outdoor Unit Auto Address SettingAuto Address Setting Basic wiring diagram Example Circuit 22-9Refrigerant Automatic Address Setting from Outdoor Unit Case 2 Automatic Address Setting no compressor operationOn the No UnitsCase 3A Automatic Address Setting in Heating Mode Case 3B Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerOn outdoor main unit PCB Display during automatic address settingRemote controller display If 1 indoor unit is connected to 1 remote controller Auto Address Setting Remote Controller Test Run SettingsRemote Controller Test Run Settings Use the remote controller to check the indoor unit addressTest Run Possible cause of malfunction Meaning of Alarm MessagesAlarm contents P02 Alarm messages displayed on system controller Main Operating Functions Wireless Remote ControllerTimer Remote Controller RCS-TM80BG Main Operating Functions Room Temperature ControlThermostat is turned ON/OFF according to as shown below DegAfter the compressor turns on Operating mode change Shifted set tempMode button Wireless Remote ControllerTransmitter FAN Speed selector buttonFilter button Cool mode and Dry mode, if the flaps are set in a downwardAddress button C Sensor buttonTimer SET button Indicator when swing operation is stoppedOFF Timer OFF Cycle TimerReceiver Operation Temperature sensors at the indoor unit side are usedMultiple units Group ControlCover Using the Wireless Remote Control UnitHow to install batteries Address Settings D type TypeOperation Emergency OperationShutdown Control unit will not be acceptedPress the Emergency operation button once more Trouble Possible Cause TroubleshootingTrouble Possible Cause Remedy How to Use the Timer Remote Controller Operating buttons Timer Remote Controller RCS-TM80BGNames and Operations Timer No. indication Display Section Refer to Setting indicationTimer program Timer OFF indicationHow to install the Remote Controller Installation Manual for Timer Remote ControllerRemote Controller Setting Mode Group Control Using 2 Remote ControllersIndoor Unit Setting Mode To Display the Sensor Temperature13/32 Once you enter in the setting mode Day and time fl ash Setting the Present TimeSet to today’s day of the week Press To change the present hour in the range of 0 to 23Program image diagram Weekly Program Function Checking Weekly TimerPress To enter the program confirmation mode Start setting Select a Timer numberSet the minute. program step Set the hour. program stepSet the program pattern. program step Press / to change the temperature settingPattern Indoor unit starts operation at the programmed timeHow to cancel the program timer invalidation How to invalidate the program timerIf Power Failure Occurred Deleting the Program TimerYou can duplicate the preset program by day Duplicating the Program TimerSelect the copy source Before Asking Repair Work„ For Example Setting at Outing Temperature 86F 30C PrecautionsRoom temperature Outing FunctionOuting function indication Status Canceling the outing functionOuting function indication Sleeping Function Wired Remote Controller Test Run Settings Simple Settings Function ProcedureList of Simple Setting Items Detailed Settings Functions Description List of Detailed Setting ItemsSetting data Item code Setting data Description Code Description Setting dataTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Maintained Remote Controller Servicing FunctionsDisplay Sensor Servicing check Alarm history Press and hold Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 Number that was set Alarm display Are occurring Automatic address setting is in progressOFF Display meaningAlarm code Alarm meaning 2WAY ECO-i Alarm CodesAlarm E04 occurs E06 Alaral rm Alarm codeE12 Alarm Alarm code E15 Alarm Alarm codeE20 Alarm Alarm code E16 Alarm Alarm codeE24 Alarm Alarm code At a number of indoor unitsE26 Alarm Alarm code E25 Alarm Alarm codeE29 Alarm Alarm code Power at the outdoor unit main is turned OFFCrossed wiring or installation error F04, F05, F22 Alarm Alarm codeCheck Check for crossed wiring and installation errors Outdoor unit control PCBF06, F23 Alarm Alarm code Identification of the problem in this caseF07, F24 Alarm Alarm code Alarm meaningF16 Alarm Alarm code Alarm code F12F17 Alarm Alarm code F08H03 alarm Alarm code F31 Alarm Alarm codeOn the degree of the problem H06 Alarm Alarm codeWhich may damage the compressor Valve must be replacedH11, H12, H21, H22 Alarm Alarm code H05, H15, H25 Alarm Alarm code H13, H23 Alarm Alarm codeL05 Alarm Alarm code H31 Alarm Alarm codeL04 Alarm Alarm code L10 Alarm Alarm code L06 Alarm Alarm codeL17 Alarm Alarm code L18 alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code P16 Alarm Alarm code P05 Alarm Alarm codePrimary or secondary current Noise in some casesP29 Alarm Alarm code P22 Alarm Alarm codeP26 Alarm Alarm code Compressor magnet SW seizing detection Blinking inspection display 1 Automatic backupAlarm code Blinking Inspection display Alarm may be caused by the effects of noise. See notes Alarm meaning Compressor magnet SW seizing detectedWithin that refrigerant tubing system are stopped Corresponding outdoor unitPage PCB and Functions Outdoor Unit Control PCB CR-CHDX14053 Outdoor Unit Control PCBFunctions for CR-CHDX14053 Progress will stop the automatic address setting operationOutdoor Unit Control PCB Mode. Static signalSystem only Link wiringSetting the Outdoor Unit address S007 Setting Address JP1 Indoor Unit Control PCBT10 For DC Fan Motor CR-SXRP56B-B For AC Fan Motor CR-UXRP71B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted CN017 Signal. Jumper wire cut Static signal continuous signalOr less CN014 OptionSELF-DIAGNOSIS Function Table Self-Diagnosis Function Table Alarm displayAlarm descriptionSelf-Diagnosis Function Table Trouble Cause and correctionCause Check items E15 E16 E20DISCH2 Alarm code Alarm meaningService Checker Functions Functions on the ordinary display Outdoor Unit Maintenance Remote ControllerSystem Diagram All units start/stop Fig Temperature monitorCooling/heating change Fig All units test run FigItem code Remarks Display functionsItem codes can be changed with Buttons Sample display -4, Fig XX-YY R.CSample Display A, B Display of unit No main unit Monitoring OperationsIndoor unit Outdoor unitOutdoor Unit Alarm History Monitor Code Parameter Description SET Data „ Setting modeParameter Description SET Data „ Setting modePage 200706MDC