
Trouble Diagnosis
3. W-2WAY ECO-i Alarm Codes
P04 Alarm
Alarm code | P04 |
|
|
| |
Alarm meaning | ||
|
|
|
Alarm conditions | When the electrical circuit of the | |
| pressure, the terminals may be | |
| will be | |
| pressure decreases to 360 psi. | |
|
|
|
Probable cause | (1) | The check valve installed on the compressor |
| (2) | The service valve is closed. |
| (3) | The outdoor unit heat exchanger became clogged during cooling operation. |
| (4) | An air short circuit occurred in the outdoor unit during cooling operation. |
| (5) | The outdoor unit fan malfunctioned during cooling operation. |
| (6) | The indoor unit air filter became clogged during heating operation. |
| (7) | An air short circuit occurred in the indoor unit during heating operation. |
| (8) | The indoor fan failed during heating operation. |
| (9) | The refrigerant circuit has become clogged. |
| (10) | The mechanical valve failed. |
| (11) | The solenoid valve kit failed. |
| (12) | Refrigerant overcharge has occurred. |
| (13) | The |
|
|
|
Check | (1) | Check that the |
| (2) | If it is connected securely, then connect a pressure gauge to the |
|
| monitor the high pressure while operating the system. Check the pressure at the time when |
|
| the |
|
| that the check valve has failed. |
| The following concern cases in which the pressure is actually too high. | |
| (3) | If the operation is cooling operation, check that the outdoor heat exchanger has not become |
|
| clogged or blocked. Remove any objects that impede the flow of air. |
| (4) | If the operation is cooling operation, check that an air short circuit has not occurred at the |
|
| outdoor unit. The status is OK as long as the temperature in the area around the outdoor |
|
| unit does not become abnormally high during operation. |
| (5) | If the operation is cooling operation, check that the outdoor unit fan has not failed. Check that |
|
| the screws which fasten the fan have not become loose. Check that the fan connector has |
|
| been securely inserted into the outdoor unit PCB. |
| (6) | If the operation is heating operation, check that the indoor unit air filter has not become |
|
| clogged. If it is clogged, clean it. |
| (7) | If the operation is heating operation, check that an air short circuit has not occurred at the |
|
| indoor unit. The status is OK as long as the temperature in the area around the indoor unit |
|
| air intake does not become abnormally high during operation. |
| (8) | If the operation is heating operation, check that the indoor unit fan has not failed. |
| (9) | Check that the refrigerant circuit has not become clogged. Check that all the service valves |
|
| are fully opened. Check that the welded connections are not clogged. |
| (10) | Check that the mechanical valves have not failed. Check whether or not mechanical valve 3 |
|
| makes a grinding sound when the power is reset. At the indoor unit, the mechanical valve is |
|
| located at a position where it is difficult to hear, so this check should be made electronically. |
|
| Check that 4 V is being output to the mechanical valve connector pin on the PCB. Also check |
|
| that the mechanical valve coil winding resistance is several tens of Ohms. |
| (11) | Check that the solenoid valve kit has not failed. Removing the coil when the valve is ON should |
|
| produce a click sound. Removing the coil when the valve is OFF should produce no sound. |
| (12) | Check that refrigerant overcharge has not occurred. If the |
|
| condenser discharge is 59°F (15°C) or higher, overcharge has occurred. |
|
| |
Correction | Replace the failed part and correct the amount of refrigerant charge. | |
|
|
|
Example | — |
|
|
|
|
Notes | — |
|
|
|
|
1
2
3
4
5
6
7
8