Sanyo KHX0752, UHX2452, UHX0752 L06 Alarm Alarm code, L10 Alarm Alarm code, L17 Alarm Alarm code

Page 79

Trouble Diagnosis

3. W-2WAY ECO-i Alarm Codes

L06 Alarm

 

Alarm code

 

L06

 

 

 

 

 

 

 

Alarm meaning

 

Duplicated indoor unit priority (alarm at non-priority indoor units and outdoor unit)

 

 

 

 

 

 

 

Alarm conditions

 

Multiple indoor units set as the priority unit were detected in the system.

 

 

 

 

 

 

 

 

 

 

Probable cause

 

More than one indoor unit is set as the priority unit in the system.

 

 

 

 

 

 

 

Check

 

Find the indoor units in the system where alarm L05 has occurred.

 

 

 

 

 

Correction

 

Refer to the description of alarm L05.

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

Notes

 

Alarm L06 occurs as a result of alarm L05. Therefore, correcting the duplicated priority

 

 

 

 

 

 

 

settings will also correct alarm L06.

 

 

 

 

 

 

 

L10 Alarm

 

 

 

 

 

 

 

 

 

Alarm code

 

L10

 

 

 

 

 

 

 

Alarm meaning

 

Outdoor unit capacity not set

 

 

Alarm conditions

 

The outdoor unit capacity has not been set, or the setting is not allowed by the system.

 

 

Probable cause

 

This alarm occurs because the capacity has not been set.

 

 

Check

 

Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed

 

 

 

 

setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is

 

 

 

 

not set to “0” or to a capacity that is not allowed.

 

 

Correction

 

If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it

 

 

 

 

correctly.

 

 

 

 

* After changing the setting, be sure to reset both the indoor and outdoor power.

 

 

Example

 

 

 

Notes

 

The outdoor unit maintenance remote controller is required in order to set the capacity in the

 

 

 

 

outdoor unit EEPROM.

 

 

L17 Alarm

 

 

 

 

 

 

 

 

 

Alarm code

 

L17

 

 

 

 

 

 

 

Alarm meaning

 

Outdoor unit model mismatch

 

 

Alarm conditions

 

This alarm occurs when a unit other than a R410A refrigerant model is connected.

 

 

Probable cause

 

(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.

 

 

 

 

(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit

 

 

 

 

EEPROM (item code 80) is incorrect.

 

 

Check

 

(1) Check the refrigerant type at the connected unit.

 

 

 

 

(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant

 

 

 

 

type. If the setting is incorrect, change it to R410A.

 

 

Correction

 

 

 

Example

 

 

 

Notes

 

The outdoor unit maintenance remote controller is required in order to set the refrigerant type in

 

 

 

 

the outdoor unit EEPROM.

 

 

L18 alarm

 

 

 

 

Alarm code

 

L18

 

 

Alarm meaning

 

4-way valve operation failure

 

 

Alarm conditions

 

During heating operation (Comp. ON), the highest detected temperature at an outdoor unit heat

 

 

 

 

exchanger (EXG 1, EXG 2, EXL1, or EXL2) was 68°F (20°C) or more above the outdoor air

 

 

 

 

temperature (Air Temp.) continuously for 5 minutes or longer, or the detected suction temperature

 

 

 

 

(SCT) was 68°F (20°C) or more above the outdoor air temperature continuously for 5 minutes or longer.

 

 

 

 

 

 

 

Probable cause

 

(1) The 4-way valve connector (20S CN060) has become disconnected from the control PCB.

 

 

 

 

(2) The 4-way valve circuit is locked (mal functioning).

 

 

Check

 

(1) Check the 4-way valve connector (20S CN060).

 

 

 

 

(2) If the connector is normal, check the 4-way valve wiring and the PCB circuit.

 

 

Correction

 

If the connector is normal, correct or replace the problem locations.

 

 

Example

 

 

 

Notes

 

 

3-17

1

2

3

4

5

6

7

8

Image 79
Contents Outdooe Units „ R410A Models Indoor UnitsPage Check of Density Limit Contents Test RUN ContentsPreparing for Test Run Test RunItems to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Setting of Unit Control PCBUnit No. setting Indoor unit setting S004 Rotary switch, redSystem address S003 System address No P DIP switch, blue 10 No. of outdoor units Outdoor unit setting S006Auto Address Setting Basic wiring diagram Example Auto Address SettingAutomatic Address Setting from the Outdoor Unit Refrigerant 22-9Circuit Units Case 2 Automatic Address Setting no compressor operationAutomatic Address Setting from Outdoor Unit On the NoCase 3A Automatic Address Setting in Heating Mode Case 3B Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerRemote controller display Display during automatic address settingOn outdoor main unit PCB Use the remote controller to check the indoor unit address Auto Address Setting Remote Controller Test Run SettingsIf 1 indoor unit is connected to 1 remote controller Remote Controller Test Run SettingsTest Run Alarm contents Meaning of Alarm MessagesPossible cause of malfunction P02 Alarm messages displayed on system controller Timer Remote Controller RCS-TM80BG Wireless Remote ControllerMain Operating Functions Deg Room Temperature ControlMain Operating Functions Thermostat is turned ON/OFF according to as shown belowAfter the compressor turns on Operating mode change Shifted set tempFAN Speed selector button Wireless Remote ControllerMode button TransmitterC Sensor button Cool mode and Dry mode, if the flaps are set in a downwardFilter button Address buttonOFF Cycle Timer Indicator when swing operation is stoppedTimer SET button OFF TimerReceiver Control Temperature sensors at the indoor unit side are usedOperation Multiple units GroupHow to install batteries Using the Wireless Remote Control UnitCover Address Settings D type TypeControl unit will not be accepted Emergency OperationOperation ShutdownPress the Emergency operation button once more Trouble Possible Cause Remedy TroubleshootingTrouble Possible Cause How to Use the Timer Remote Controller Operating buttons Timer Remote Controller RCS-TM80BGNames and Operations Timer OFF indication Display Section Refer to Setting indicationTimer No. indication Timer programHow to install the Remote Controller Installation Manual for Timer Remote ControllerTo Display the Sensor Temperature Group Control Using 2 Remote ControllersRemote Controller Setting Mode Indoor Unit Setting Mode13/32 Press To change the present hour in the range of 0 to 23 Setting the Present TimeOnce you enter in the setting mode Day and time fl ash Set to today’s day of the weekSelect a Timer number Weekly Program Function Checking Weekly TimerProgram image diagram Press To enter the program confirmation mode Start settingSet the minute. program step Set the hour. program stepIndoor unit starts operation at the programmed time Press / to change the temperature settingSet the program pattern. program step PatternDeleting the Program Timer How to invalidate the program timerHow to cancel the program timer invalidation If Power Failure OccurredBefore Asking Repair Work Duplicating the Program TimerYou can duplicate the preset program by day Select the copy sourceOuting Function Precautions„ For Example Setting at Outing Temperature 86F 30C Room temperatureOuting function indication Canceling the outing functionOuting function indication Status Sleeping Function Wired Remote Controller Test Run Settings Simple Settings Function ProcedureList of Simple Setting Items Detailed Settings Functions Setting data List of Detailed Setting ItemsDescription Item code Setting data Description Code Description Setting dataTimer Remote Controller RCS-TM80BG Table of DC Fan Motor Tap Settings ceiling-mounted type TP6 TP3 TP1 Display Sensor Servicing check Alarm history Press and hold Remote Controller Servicing FunctionsMaintained Test Run Function Normal remote controller display Trouble Diagnosis Contents of Remote Controller Switch Alarm Display Heat exchanger 1 gas temp. sensor F06 Display meaning Are occurring Automatic address setting is in progressNumber that was set Alarm display OFFAlarm code Alarm meaning 2WAY ECO-i Alarm CodesE15 Alarm Alarm code E06 Alaral rm Alarm codeAlarm E04 occurs E12 Alarm Alarm codeAt a number of indoor units E16 Alarm Alarm codeE20 Alarm Alarm code E24 Alarm Alarm codePower at the outdoor unit main is turned OFF E25 Alarm Alarm codeE26 Alarm Alarm code E29 Alarm Alarm codeOutdoor unit control PCB F04, F05, F22 Alarm Alarm codeCrossed wiring or installation error Check Check for crossed wiring and installation errorsAlarm meaning Identification of the problem in this caseF06, F23 Alarm Alarm code F07, F24 Alarm Alarm codeF08 Alarm code F12F16 Alarm Alarm code F17 Alarm Alarm codeH03 alarm Alarm code F31 Alarm Alarm codeValve must be replaced H06 Alarm Alarm codeOn the degree of the problem Which may damage the compressorH11, H12, H21, H22 Alarm Alarm code H05, H15, H25 Alarm Alarm code H13, H23 Alarm Alarm codeL04 Alarm Alarm code H31 Alarm Alarm codeL05 Alarm Alarm code L18 alarm Alarm code L06 Alarm Alarm codeL10 Alarm Alarm code L17 Alarm Alarm codeP03, P17, P18 Alarm Alarm code P04 Alarm Alarm code Noise in some cases P05 Alarm Alarm codeP16 Alarm Alarm code Primary or secondary currentP26 Alarm Alarm code P22 Alarm Alarm codeP29 Alarm Alarm code Alarm code Blinking Inspection display Blinking inspection display 1 Automatic backupCompressor magnet SW seizing detection Corresponding outdoor unit Alarm meaning Compressor magnet SW seizing detectedAlarm may be caused by the effects of noise. See notes Within that refrigerant tubing system are stoppedPage PCB and Functions Outdoor Unit Control PCB CR-CHDX14053 Outdoor Unit Control PCBFunctions for CR-CHDX14053 Progress will stop the automatic address setting operationOutdoor Unit Control PCB Mode. Static signalSetting the Outdoor Unit address S007 Setting Address Link wiringSystem only T10 Indoor Unit Control PCBJP1 For DC Fan Motor CR-SXRP56B-B For AC Fan Motor CR-UXRP71B-BCR1 for CR-KR74GXH56A/KHX0752~KHX1852 Wall-Mounted CR1 for CR-KR254GXH56A/KHX2452 Wall-Mounted CR2 for POW-KR74GXH56/KHX0752~KHX2452 Wall-Mounted Or less Signal. Jumper wire cut Static signal continuous signalCN017 CN014 OptionSELF-DIAGNOSIS Function Table Trouble Cause and correction Alarm displayAlarm descriptionSelf-Diagnosis Function Table Self-Diagnosis Function TableCause Check items E15 E16 E20DISCH2 Alarm code Alarm meaningService Checker System Diagram Outdoor Unit Maintenance Remote ControllerFunctions Functions on the ordinary display All units test run Fig Temperature monitorAll units start/stop Fig Cooling/heating change FigItem codes can be changed with Buttons Display functionsItem code Remarks Sample display -4, Fig XX-YY R.CSample Display A, B Outdoor unit Monitoring OperationsDisplay of unit No main unit Indoor unitOutdoor Unit Alarm History Monitor Code Parameter Description SET Data „ Setting modeParameter Description SET Data „ Setting modePage 200706MDC