UPS model | Utility voltage | Available settings utility | Branch circuit | Line cord |
| frequency (Hz) | voltage (VAC) | rating (A) |
|
|
|
|
|
|
T1000/1500 | 60/50 | 100, 110, 120* | 15 | Nondetachable power |
NA/JPN/TWN |
|
|
| cord with NEMA |
|
|
|
| plug |
|
|
|
|
|
T1000/1500 INTL | 50/60 | 220, 230*, 240 | 10 | Detachable power cord |
|
|
|
| with |
T1000 output specifications
UPS model | Output receptacles | Maximum current |
|
|
|
T1000 | 8 x NEMA | 8.3 A |
NA/JPN/TWN |
|
|
|
|
|
T1000 INTL | 8 x | 4.3 A |
|
|
|
T1500 output specifications
UPS model | Output receptacles | Maximum current |
|
|
|
T1500 | 8 x NEMA | 12.5 A |
NA/JPN/TWN |
|
|
|
|
|
T1500 INTL | 8 x | 6.5 A |
|
|
|
T1000 power protection specifications
UPS model | VA | Nominal power rating (W) | Nominal voltage setting |
|
|
|
|
T1000 | 1000 | 650 | 100, 110, 120 |
NA/JPN/TWN |
|
|
|
|
|
|
|
T1000 INTL | 1000 | 650 | 220, 230, 240 |
|
|
|
|
T1500 power protection specifications
UPS model | VA | Nominal power rating (W) | Nominal voltage setting |
|
|
|
|
T1500 | 1500 | 900 | 100, 110, 120 |
NA/JPN/TWN |
|
|
|
T1500 INTL | 1500 | 900 | 220, 230, 240 |
|
|
|
|
Voltage specifications
Configuration setting (VAC) | Available nominal output voltage (VAC) |
|
|
100 | 100 |
|
|
110 | 110 |
|
|
120 | 120 |
|
|
220 | 220 |
|
|
Specifications 32