Toshiba RAV-SM1104BT-E, RAV-SM454MUT-E, RAV-SM1404BT-E RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗

Page 17

2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

2-1. Compact 4-way Cassette Type

RAV-SM404MUT, RAV-SM454MUT, RAV-SM564MUT

595 to 660 Ceiling open dimension

595 to 660 Ceiling open dimension

1000 or more

1000 or more

15 or more

 

Obustacle

1000 or more

15 or more

Space required for

installation and servicing

207

175

149

 

 

 

 

 

 

64

29

142

64

368.5

 

 

 

 

Bottom face

Knockout for flesh

 

of ceiling

air intake Ø100

 

145.5

 

700 Panel external dimension

93

 

595 to 660 Ceiling open dimension

 

 

525 Hanging bolt pitch

105

70

 

 

 

235

dimension

 

 

105

external

 

 

235

575 Unit

 

 

Ø162

Electric parts box

320.5

 

 

For branch duct knockout

 

square hole Ø150

575 Unit external dimension

Bottom face of ceiling

Drain discharge port

Hanging bolt M10 or W3/8 local arrange

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling660to595open dimension

 

externalPanel700 dimension

 

 

105214 256

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14842

 

 

 

 

 

 

 

 

 

 

 

 

 

177 Hanging510bolt pitch

 

 

 

 

 

 

 

 

 

 

 

 

 

Ø162

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

97.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe

 

 

 

 

 

 

 

 

 

 

(Liquid) Ø6.4

 

 

 

 

For branch ductt knockout square hole Ø150

Refrigerant pipe (Gas) Ø12.7

268

27

220.5

 

145.5

 

134

Bottom face

63

of ceiling

Ceiling panel

 

 

120

 

142

21

158

Wiring connection port

55

70

105

93

139.5

190.5

– 17 –

Image 17
Contents Split Type Contents Indoort Unit TroubleshootingOriginal instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Declaration of Conformity Explanations given to userRelocation Specifications Copper pipe Piping Safety Caution Concerned to New RefrigerantFlare nut JointGeneral tools Conventional tools can be used ToolsSM56 type Round duct Concealed Duct typeSM110 type Round duct RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗ Space required for Installation and servicingRAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗ DimensionRAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗ Ceiling TypeParts name Type Specifications Specifications of Electrical PartsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramWireless remote controller Case of Connection of Wireless Remote ControllerMax units Control outline Command Outline of specifications RemarksTemperature in heating Heat Ceiling type Outline of specificationsTcn TcjTc n ConditionsSetup at shipment All operations Cooling/dry operation Heating/fan operationAll modes AlarmCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks TCJ Exct Disp CHK MCC-1402Indoor P.C. Board Optional Connector Specifications MCC-1402 Before troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Power supply error of remote controller, Indoor E09 error Check code E01 errorE10 error E04 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error F10 error P10 errorP12 error Check by tester P19 errorExchange to cooling cycle Exchange to heating cycleF01 error F02 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TA, TC, TCJ, TE, TS, to sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE,TS, to sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresCode No. required at least Contents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures MCC-1402 Writing the setting data to EepromSetting data Type Type name abb Setting data Factory-set valueSetting data Type Type Code NoCompact 4-way Cassette Type and Concealed Duct Type Test Run Setup on Remote Controller Wired remote controllerTest cooling operation Test heating operation Procedure DescriptionD203 Red Practical operationLED Display on Indoor P.C. Board D002 Red Using the set temperature Function Selection SetupTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment When connected 2 remote controllers operate an idoor unit Wireless remote controllerWhen connected 2 remote controllers operate the twin Setup methodContents Pushing Test button returns the display to usual display Calling of error history ContentsGroup control operation System exampleUsual regular communication Indoor unit power-ON sequenceInitial communication Model connection interface wiring connection Microprocessor block diagramModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLEC. Board Switch SW01 Setup Wiring SpecificationsExternal view of P.C. board assembly How to set up from indoor unit side by remote controllerAddress setup Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationExample Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringPush SET + CL + Test buttons Using timer time Buttons, set the line addressSimultaneously for 4 seconds or more ButtonButton if the unit stops ProcedureTo know the position of indoor unit body by address Ceiling panel RBC-UM11PGWE Preparing work Part name ProcedureDetachment AttachmentPart name Procedure Remarks Panel has directionality Part name Procedure Remarks Ceiling panelNo. Part name Procedure RemarksElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pump 1. Detachment Drain pan 1. DetachmentDetails of sensor lead wire drawing Part name Procedure Remarks HeatExchanger Recover refrigerant gas RAV-SM∗∗∗BT ∗ Part name Procedure RemarksFan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch 100 No. Part name Procedure Remarks101 102 103 237 209222 104404MUT-E 454MUT-E 564MUT-E 105Location Description Model name 404MUT-TR 454MUT-TR 564MUT-TR 106401 Electric parts107 Location Model name108 RAV-SM564BT-E RAV-SM564BT-TR 109110 RAV-SM804BT-E RAV-SM804BT-TR 111112 1104BT-TR 113564BT-E 804BT-E 1104BT-E 1404BT-E 114Location Model name RAV-SM Description 115 264220 Location 116Description Model name RAV-SM 117 Description 564CT-E 804CT-E 1104CT-E 1404CT-E 118Check of Concentration Limit Toshiba Carrier Corporation