Toshiba RAV-SM804BT-TR, RAV-SM454MUT-E Error mode detected by outdoor unit, Air conditioner

Page 49

Error mode detected by outdoor unit

The check code has been ramified from 4 series and after

The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after. (Ex. Combination of RAV-SM1404BT-E with RAV-SP1404AT-E)

When the outdoor unit is 3 series and before, the conventional check code is displayed.

(Ex. Combination of RAV-SM1404BT-E and RAV-SM1403AT-E: Indoor unit only is 4 series.)

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

Check

 

 

 

 

 

code

Cause of operation

Status of

Condition

 

Judgment and measures

 

 

Indoor

air conditioner

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

F04

Disconnection, short of discharge temp. sensor

Stop

Displayed when

1.

Check discharge temp. sensor (TD).

(TD)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

F06

Disconnection, short of outdoor temp. sensor

Stop

Displayed when

1.

Check temp. sensor (TE).

(TE)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

F07

Disconnection, short of outdoor temp. sensor

Stop

Displayed when

1.

Check temp. sensor (TL).

(TL)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

F12

Disconnection, short of suction temp. sensor

Stop

Displayed when

1.

Check suction temp. sensor (TS).

(TS)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

F15

Miss-mounting of outdoor temp. sensor (TE, TS)

Stop

Displayed when

1.

Check temp. sensor (TE, TS).

 

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

F08

Disconnection, short of outside temp. sensor

Continue

Displayed when

1.

Check outside temp. sensor (TO).

(TO)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

F13

Disconnection, short of heat sink temp. sensor

Stop

Displayed when

1.

Check outdoor P.C. board.

(TH)

error is detected

 

(Q201 is incorporated in TH sensor.)

 

 

 

 

 

 

 

 

 

F31

Outdoor P.C. EEPROM error

Stop

Displayed when

1.

Check outdoor P.C. board.

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

L10

Unset jumper of service P.C. board

Stop

Displayed when

1.

Outdoor service P.C. board

error is detected

 

Check model type setting jumper wire.

 

 

 

 

 

 

 

 

 

 

L29

Communication error between outdoor P.C.

Stop

Displayed when

1.

Check outdoor P.C. board

board MCU

error is detected

2.

Connection check for each P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat sink overheat error

 

Displayed when

1.

Check screw tightening between PC. Board and heat

P07

Heat sink temp. sensor detected over specified

Stop

 

sink and check radiator grease.

error is detected

 

 

temperature.

 

2.

Check heat sink blast path.

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check gas leak, recharge

 

Detection of gas leak

 

 

2.

Check full open of service valve.

P15

Discharge temp. sensor (TD), Suction temp.

Stop

Displayed when

3.

Check PMV (Pulse Motor Valve).

 

sensor (TS) detected temperature over

 

error is detected

4.

Check broken pipe.

 

specified temp.

 

 

 

 

 

5.

Check discharge temp. sensor (TD), suction temp.

 

 

 

 

 

 

 

 

 

sensor (TS).

 

 

 

 

 

 

 

4-way valve inverse error

 

 

1.

Check operation of 4-way valve.

 

After heating operation has started, indoor

 

 

2.

Check outdoor heat exchanger (TE), suction temp.

 

heat exchanger temp. lowers under the

 

Displayed when

 

sensor (TS).

P19

specified temp.

Stop

 

 

error is detected

3.

Check indoor heat exchanger sensor (TC).

 

After heating operation has started, outdoor

 

 

 

 

4.

Check 4-way valve coil.

 

heat exchanger / suction temp. rises over the

 

 

 

 

 

5.

Check PMV (Pulse Motor Valve).

 

specified temp.

 

 

 

 

 

 

 

 

 

Compressor break down

 

Displayed when

1.

Check power supply voltage.

H01

Although operation has started, operation

Stop

2.

Overload operation of refrigerating cycle

error is detected

 

frequency decreases and operation stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lock

 

Displayed when

1.

Trouble of compressor (Lock, etc.): Replace compressor.

H02

* Over-current detection after compressor

Stop

2.

Wiring error of compressor (Open phase)

error is detected

 

start-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 49 –

Image 49
Contents Split Type Contents Indoort Unit TroubleshootingOriginal instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Relocation Explanations given to userDeclaration of Conformity Specifications Copper pipe Piping Safety Caution Concerned to New RefrigerantFlare nut JointGeneral tools Conventional tools can be used ToolsSM56 type Round duct Concealed Duct typeSM110 type Round duct RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗ Space required for Installation and servicingRAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗ DimensionRAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗ Ceiling TypeParts name Type Specifications Specifications of Electrical PartsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramWireless remote controller Case of Connection of Wireless Remote ControllerMax units Control outline Command Outline of specifications RemarksTemperature in heating Heat Ceiling type Outline of specificationsTcn TcjTc n ConditionsSetup at shipment All operations Cooling/dry operation Heating/fan operationAll modes AlarmCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks TCJ Exct Disp CHK MCC-1402Indoor P.C. Board Optional Connector Specifications MCC-1402 Before troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Power supply error of remote controller, Indoor E09 error Check code E01 errorE10 error E04 errorE08, L03, L07, L08 error E18 errorL09 error L30 error L20 errorP30 error Central controller F10 error P10 errorP12 error Check by tester P19 errorExchange to cooling cycle Exchange to heating cycleF01 error F02 errorC06 error 11 model connection interface F29 error E03 error Master indoor unitP31 error Follower indoor unit TA, TC, TCJ, TE, TS, to sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE,TS, to sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresC. Board for indoor unit servicing replacement procedures Setting data read out from EepromCode No. required at least Contents MCC-1402 Writing the setting data to EepromSetting data Type Type name abb Setting data Factory-set valueSetting data Type Type Code NoCompact 4-way Cassette Type and Concealed Duct Type Test Run Setup on Remote Controller Wired remote controllerTest cooling operation Test heating operation Procedure DescriptionLED Display on Indoor P.C. Board D002 Red Practical operationD203 Red Using the set temperature Function Selection SetupTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment When connected 2 remote controllers operate an idoor unit Wireless remote controllerWhen connected 2 remote controllers operate the twin Setup methodContents Pushing Test button returns the display to usual display Calling of error history ContentsGroup control operation System exampleInitial communication Indoor unit power-ON sequenceUsual regular communication Model connection interface wiring connection Microprocessor block diagramModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLEC. Board Switch SW01 Setup Wiring SpecificationsExternal view of P.C. board assembly How to set up from indoor unit side by remote controllerAddress setup Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationExample Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringPush SET + CL + Test buttons Using timer time Buttons, set the line addressSimultaneously for 4 seconds or more ButtonTo know the position of indoor unit body by address ProcedureButton if the unit stops Ceiling panel RBC-UM11PGWE Preparing work Part name ProcedureDetachment AttachmentPart name Procedure Remarks Panel has directionality Part name Procedure Remarks Ceiling panelNo. Part name Procedure RemarksElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pump 1. Detachment Drain pan 1. DetachmentExchanger Recover refrigerant gas Part name Procedure Remarks HeatDetails of sensor lead wire drawing RAV-SM∗∗∗BT ∗ Part name Procedure RemarksFan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch 100 No. Part name Procedure Remarks101 102 103 237 209222 104Location Description Model name 105404MUT-E 454MUT-E 564MUT-E 404MUT-TR 454MUT-TR 564MUT-TR 106401 Electric parts107 Location Model name108 RAV-SM564BT-E RAV-SM564BT-TR 109110 RAV-SM804BT-E RAV-SM804BT-TR 111112 1104BT-TR 113Location Model name RAV-SM Description 114564BT-E 804BT-E 1104BT-E 1404BT-E 220 264115 Description Model name RAV-SM 116Location 117 Description 564CT-E 804CT-E 1104CT-E 1404CT-E 118Check of Concentration Limit Toshiba Carrier Corporation