Error mode detected by outdoor unit
The check code has been ramified from 4 series and after
The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after. (Ex. Combination of
When the outdoor unit is 3 series and before, the conventional check code is displayed.
(Ex. Combination of
| Operation of diagnostic function |
|
|
| ||
|
|
|
|
|
| |
Check |
|
|
|
|
| |
code | Cause of operation | Status of | Condition |
| Judgment and measures | |
|
| |||||
Indoor | air conditioner |
|
| |||
|
|
|
| |||
|
|
|
|
| ||
unit |
|
|
|
|
| |
|
|
|
|
|
| |
F04 | Disconnection, short of discharge temp. sensor | Stop | Displayed when | 1. | Check discharge temp. sensor (TD). | |
(TD) | error is detected | 2. | Check outdoor P.C. board. | |||
|
| |||||
|
|
|
|
|
| |
F06 | Disconnection, short of outdoor temp. sensor | Stop | Displayed when | 1. | Check temp. sensor (TE). | |
(TE) | error is detected | 2. | Check outdoor P.C. board. | |||
|
| |||||
|
|
|
|
|
| |
F07 | Disconnection, short of outdoor temp. sensor | Stop | Displayed when | 1. | Check temp. sensor (TL). | |
(TL) | error is detected | 2. | Check outdoor P.C. board. | |||
|
| |||||
|
|
|
|
|
| |
F12 | Disconnection, short of suction temp. sensor | Stop | Displayed when | 1. | Check suction temp. sensor (TS). | |
(TS) | error is detected | 2. | Check outdoor P.C. board. | |||
|
| |||||
|
|
|
|
|
| |
F15 | Stop | Displayed when | 1. | Check temp. sensor (TE, TS). | ||
| error is detected | 2. | Check outdoor P.C. board. | |||
|
|
| ||||
|
|
|
| |||
|
|
|
|
|
| |
F08 | Disconnection, short of outside temp. sensor | Continue | Displayed when | 1. | Check outside temp. sensor (TO). | |
(TO) | error is detected | 2. | Check outdoor P.C. board. | |||
|
| |||||
|
|
|
|
|
| |
F13 | Disconnection, short of heat sink temp. sensor | Stop | Displayed when | 1. | Check outdoor P.C. board. | |
(TH) | error is detected |
| (Q201 is incorporated in TH sensor.) | |||
|
|
| ||||
|
|
|
|
|
| |
F31 | Outdoor P.C. EEPROM error | Stop | Displayed when | 1. | Check outdoor P.C. board. | |
error is detected |
|
| ||||
|
|
|
|
| ||
|
|
|
|
|
| |
L10 | Unset jumper of service P.C. board | Stop | Displayed when | 1. | Outdoor service P.C. board | |
error is detected |
| Check model type setting jumper wire. | ||||
|
|
|
| |||
|
|
|
|
|
| |
L29 | Communication error between outdoor P.C. | Stop | Displayed when | 1. | Check outdoor P.C. board | |
board MCU | error is detected | 2. | Connection check for each P.C. board. | |||
|
| |||||
|
|
|
| |||
|
|
|
|
|
| |
| Heat sink overheat error |
| Displayed when | 1. | Check screw tightening between PC. Board and heat | |
P07 | ∗ Heat sink temp. sensor detected over specified | Stop |
| sink and check radiator grease. | ||
error is detected |
| |||||
| temperature. |
| 2. | Check heat sink blast path. | ||
|
|
| ||||
|
|
|
|
|
| |
|
|
|
| 1. | Check gas leak, recharge | |
| Detection of gas leak |
|
| 2. | Check full open of service valve. | |
P15 | ∗ Discharge temp. sensor (TD), Suction temp. | Stop | Displayed when | 3. | Check PMV (Pulse Motor Valve). | |
| sensor (TS) detected temperature over |
| error is detected | 4. | Check broken pipe. | |
| specified temp. |
|
| |||
|
|
| 5. | Check discharge temp. sensor (TD), suction temp. | ||
|
|
|
| |||
|
|
|
|
| sensor (TS). | |
|
|
|
|
|
| |
|
|
| 1. | Check operation of | ||
| ∗ After heating operation has started, indoor |
|
| 2. | Check outdoor heat exchanger (TE), suction temp. | |
| heat exchanger temp. lowers under the |
| Displayed when |
| sensor (TS). | |
P19 | specified temp. | Stop |
|
| ||
error is detected | 3. | Check indoor heat exchanger sensor (TC). | ||||
| ∗ After heating operation has started, outdoor |
| ||||
|
|
| 4. | Check | ||
| heat exchanger / suction temp. rises over the |
|
| |||
|
|
| 5. | Check PMV (Pulse Motor Valve). | ||
| specified temp. |
|
| |||
|
|
|
|
|
| |
| Compressor break down |
| Displayed when | 1. | Check power supply voltage. | |
H01 | ∗ Although operation has started, operation | Stop | 2. | Overload operation of refrigerating cycle | ||
error is detected | ||||||
| frequency decreases and operation stops. |
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
| Compressor lock |
| Displayed when | 1. | Trouble of compressor (Lock, etc.): Replace compressor. | |
H02 | * | Stop | 2. | Wiring error of compressor (Open phase) | ||
error is detected | ||||||
|
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
|