Toshiba RAV-SM564BT-E Type Code No, Indoor unit capacity Code No, Setting data Factory-set value

Page 67

Table 1

DN

Item

Setting data

Factory-set value

 

 

 

 

01

Filter sign lighting time

 

Depending on Type

 

 

 

 

02

Filter pollution level

 

0000: standard

 

 

 

 

03

Central control address

 

0099: Not determined

 

 

 

 

06

Heating suction temperature shift

 

0002: +2°C

 

 

 

 

0F

Cooling only

 

0000: Heat pump

 

 

 

 

10

Type

 

Depending on model type

 

 

 

 

11

Indoor unit capacity

 

Depending on capacity type

 

 

 

 

12

System address

 

0099: Not determined

 

 

 

 

13

Indoor unit address

 

0099: Not determined

 

 

 

 

14

Group address

 

0099: Not determined

 

 

 

 

1E

Temperature range of cooling/heating

 

0003: 3 deg (Ts ± 1.5)

automatic SW control point

 

 

 

 

 

 

 

 

28

Auto restart after power failure

 

0000: None

 

 

 

 

2b

Thermo output SW (T10 ƒ )

 

0000: Thermo ON

 

 

 

 

31

Ventilation fan (standalone)

 

0000: Not available

 

 

 

 

32

Sensor select (Selection of static pressure)

 

0000: Body sensor

 

 

 

 

40

Drain pump control

 

0003: Drain pump OFF

 

 

 

 

60

Timer setting (wired remote controller)

 

0000: Available

 

 

 

 

C2

DEMAND setup

 

0075: 75%

 

 

 

 

d0

Remote controller save function

 

0001: Valid

 

 

 

 

d1

Frost protection function

 

0000: Not available

 

 

 

 

d3

Revolutions per minute of dry operation

 

0001: 210rpm

 

 

 

 

Table 2. Type: CODE No. 10

Setting data

Type

Type name abb.

 

 

 

0004

Concealed Duct Type

RAV-SM∗∗∗BT-E (TR)

 

 

 

0007

Ceiling Type

RAV-SM∗∗∗CT-E (TR)

 

 

 

0014

Compact 4-way Cassette Type

RAV-SM∗∗∗MUT-E (TR)

 

 

 

Table 3. Indoor unit capacity: CODE No. 11

Setting data

Type

 

 

0000

Disable

 

 

0006

40

 

 

0007

45

 

 

0009

56

 

 

0012

80

 

 

0015

110

 

 

0017

140

 

 

EEPROM initial value on the P.C. board for indoor unit servicing.

– 67 –

Image 67
Contents Split Type Contents Indoort Unit TroubleshootingOriginal instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Relocation Explanations given to userDeclaration of Conformity Specifications Joint Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsSM56 type Round duct Concealed Duct typeSM110 type Round duct RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗ Space required for Installation and servicingRAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗ DimensionRAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗ Ceiling TypeParts name Type Specifications Specifications of Electrical PartsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramWireless remote controller Case of Connection of Wireless Remote ControllerMax units Control outline Command Outline of specifications RemarksTemperature in heating Heat Ceiling type Outline of specificationsConditions TcjTcn Tc nSetup at shipment All operations Cooling/dry operation Heating/fan operationAll modes AlarmCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks TCJ Exct Disp CHK MCC-1402Indoor P.C. Board Optional Connector Specifications MCC-1402 Wired remote controller type Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Power supply error of remote controller, Indoor E09 error Check code E01 errorE10 error E04 errorE08, L03, L07, L08 error E18 errorL09 error L30 error L20 errorP30 error Central controller F10 error P10 errorP12 error Exchange to heating cycle P19 errorCheck by tester Exchange to cooling cycleF01 error F02 errorC06 error 11 model connection interface F29 error E03 error Master indoor unitP31 error Follower indoor unit TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TA, TC, TCJ, TE,TS, to sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresC. Board for indoor unit servicing replacement procedures Setting data read out from EepromCode No. required at least Contents MCC-1402 Writing the setting data to EepromType Code No Setting data Factory-set valueSetting data Type Type name abb Setting data TypeCompact 4-way Cassette Type and Concealed Duct Type Test Run Setup on Remote Controller Wired remote controllerTest cooling operation Test heating operation Procedure DescriptionLED Display on Indoor P.C. Board D002 Red Practical operationD203 Red To change item to be set up, proceed to Procedure Function Selection SetupUsing the set temperature To change the selected indoor unit, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment Setup method Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit When connected 2 remote controllers operate the twinContents System example Calling of error history ContentsPushing Test button returns the display to usual display Group control operationInitial communication Indoor unit power-ON sequenceUsual regular communication Model name TCB-PCNT30TLE Microprocessor block diagramModel connection interface wiring connection Model Connection Interface TCC-LINK adapterC. Board Switch SW01 Setup Wiring SpecificationsPush Test + Vent buttons for 4 seconds or more How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Address setupDuring unset time, At shipment from factory is displayed Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationExample Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringButton Using timer time Buttons, set the line addressPush SET + CL + Test buttons Simultaneously for 4 seconds or moreTo know the position of indoor unit body by address ProcedureButton if the unit stops Attachment Part name ProcedureCeiling panel RBC-UM11PGWE Preparing work DetachmentPart name Procedure Remarks Panel has directionality Part name Procedure Remarks Ceiling panelNo. Part name Procedure RemarksElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pump 1. Detachment Drain pan 1. DetachmentExchanger Recover refrigerant gas Part name Procedure Remarks HeatDetails of sensor lead wire drawing RAV-SM∗∗∗BT ∗ Part name Procedure RemarksFan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch 100 No. Part name Procedure Remarks101 102 103 104 209237 222Location Description Model name 105404MUT-E 454MUT-E 564MUT-E 404MUT-TR 454MUT-TR 564MUT-TR 106Location Model name Electric parts401 107108 RAV-SM564BT-E RAV-SM564BT-TR 109110 RAV-SM804BT-E RAV-SM804BT-TR 111112 1104BT-TR 113Location Model name RAV-SM Description 114564BT-E 804BT-E 1104BT-E 1404BT-E 220 264115 Description Model name RAV-SM 116Location 117 Description 564CT-E 804CT-E 1104CT-E 1404CT-E 118Check of Concentration Limit Toshiba Carrier Corporation