Toshiba RAV-SM564MUT-E, RAV-SM454MUT-E, RAV-SM404MUT-TR, RAV-SM1404BT-E service manual Setup AT Local

Page 38

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

18

DC motor

1)

When the fan operation has started, positioning of

 

 

 

 

the stator and the rotor are performed.

 

 

 

 

(Moves slightly with tap sound)

 

 

 

2)

The motor operates according to the command from

 

 

 

 

the indoor controller.

 

Notes)

When the fan rotates while the air conditioner stops due to entering of outside air, etc, the air conditioner may operate while the fan motor stops.

 

 

• When a fan lock is found, the air conditioner stops, and

 

Check code [P12]

 

 

an error is displayed.

 

 

 

 

 

 

 

 

 

 

 

 

19

Self-clean

1)

When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following

 

operation

 

three self-clean operations are performed.

 

 

 

 

 

 

 

(Dry operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

Self-clean

 

FAN

 

Drain pump

Louver

 

 

 

 

 

 

 

 

 

 

 

ON period

 

operation period

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 10 min.

 

None

 

 

 

 

 

 

Horizontal discharge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 to 60 min.

 

1 hour

 

Fan (UL)

 

STOP

 

 

 

 

 

 

 

 

 

 

 

position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 min. to

 

2 hours

 

 

 

 

 

 

Concealed duct is none.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2)

During operation of self-clean,

lights on the wired

 

And it is not also on the

 

 

 

 

 

 

remote controller screen. However the operation

 

wireless remote controller.

 

 

 

lamp (Green LED) goes off.

 

 

 

 

 

It is recognized as [STOP]

 

 

3)

To stop the self-clean operation, push twice the

 

from the remote monitor

 

 

 

[ON/OFF] button on the remote controller

 

 

 

side.

 

 

 

continuously. (Stop the operation as compressor ON

 

 

 

 

 

 

 

time in the table above: 10 minutes or below.)

 

 

 

 

 

 

4)

When the follower unit executes self-clean operation

 

 

 

 

 

 

 

in the group connection, the segment of

is

 

 

 

 

 

 

 

displayed on the wired remote controller screen via

 

 

 

 

 

 

 

master unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

If self-clean operation is not used, set invalidity

 

 

 

 

 

 

 

(does not use) of the self-clean operation by

 

 

 

 

 

 

 

changing [0001 (At shipment) of CODE No. (DN)

 

 

 

 

 

 

 

[D3] to [0000].

 

 

 

 

 

 

 

 

 

 

 

To erase the

 

display during operation of

 

 

 

 

 

 

 

self-clean, change CODE No. [D4] from [0000:

 

 

 

 

 

 

 

Display (At shipment)] to [0001: Non-display].

 

 

 

 

 

 

 

 

 

 

 

20

Save operation

1)

Turn on SAVE

button on the remote controller.

 

Carry out setting

 

 

2)

During operation of save operation,

lights on the

 

operation during stop of

 

 

 

wired remote controller.

 

 

 

 

 

the unit; otherwise the

 

 

3)

During save operation, the current release control is

 

unit stops operation.

 

 

 

For the setup operation,

 

 

 

performed with the restriction ratio set in EEPROM

 

 

 

 

 

refer to

 

 

 

on the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

“How to set contents of

 

 

4)

The restriction ratio can be set by keeping

SAVE

 

 

 

 

 

 

save operation” in Sction

 

 

 

button pushed for 4 seconds or more on the remote

 

 

 

 

 

8. SETUP AT LOCAL

 

 

 

controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SITE AND OTHERS”.

 

 

5)

When validating the save operation, the next opera-

 

 

 

 

 

 

 

 

 

 

tion starts with save operation valid because contents

 

 

 

 

 

 

 

are held even when operation stops, operation mode

 

 

 

 

 

 

 

changes or power supply is reset.

 

 

 

 

 

 

 

 

 

 

6)

The restriction ratio can be set by changing the setup

 

 

 

 

 

 

 

data of CODE No. (DN) [C2] in the range of 50 to

 

 

 

 

 

 

 

100% (every 1%, Setting at shipment: 75%).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 38 –

Image 38
Contents Split Type Contents Troubleshooting Indoort UnitOriginal instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit DescriptionPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Declaration of Conformity Explanations given to userRelocation Specifications Flare nut Safety Caution Concerned to New RefrigerantCopper pipe Piping JointTools General tools Conventional tools can be usedConcealed Duct type SM56 type Round ductSM110 type Round duct Space required for Installation and servicing RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗Dimension RAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗RAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ Ceiling Type RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗Specifications of Electrical Parts Parts name Type SpecificationsIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Wireless remote controllerMax units Outline of specifications Remarks Control outline CommandTemperature in heating Heat Outline of specifications Ceiling typeTc n TcjTcn ConditionsSetup at shipment Cooling/dry operation Heating/fan operation All operationsAlarm All modesCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks MCC-1402 TCJ Exct Disp CHKIndoor P.C. Board Optional Connector Specifications MCC-1402 Troubleshooting procedure Summary of TroubleshootingBefore troubleshooting Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Power supply error of remote controller, Indoor Check code E01 error E09 errorE04 error E10 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error P10 error F10 errorP12 error Exchange to cooling cycle P19 errorCheck by tester Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TA, TC, TCJ, TE,TS, to sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseCode No. required at least Contents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures Writing the setting data to Eeprom MCC-1402Setting data Type Setting data Factory-set valueSetting data Type Type name abb Type Code NoTest Run Setup on Remote Controller Wired remote controller Compact 4-way Cassette Type and Concealed Duct TypeProcedure Description Test cooling operation Test heating operationD203 Red Practical operationLED Display on Indoor P.C. Board D002 Red To change the selected indoor unit, proceed to Procedure Function Selection SetupUsing the set temperature To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment When connected 2 remote controllers operate the twin Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit Setup methodContents Group control operation Calling of error history ContentsPushing Test button returns the display to usual display System exampleUsual regular communication Indoor unit power-ON sequenceInitial communication Model Connection Interface TCC-LINK adapter Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLEWiring Specifications C. Board Switch SW01 SetupAddress setup How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Push Test + Vent buttons for 4 seconds or moreDuring unset time, At shipment from factory is displayed Address Setup Address setup procedureSystem configuration Address Setup & Group Control TerminologyExample Automatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionSimultaneously for 4 seconds or more Using timer time Buttons, set the line addressPush SET + CL + Test buttons ButtonButton if the unit stops ProcedureTo know the position of indoor unit body by address Detachment Part name ProcedureCeiling panel RBC-UM11PGWE Preparing work AttachmentPart name Procedure Remarks Part name Procedure Remarks Ceiling panel Panel has directionalityProcedure Remarks No. Part nameElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pan 1. Detachment Drain pump 1. DetachmentDetails of sensor lead wire drawing Part name Procedure Remarks HeatExchanger Recover refrigerant gas Part name Procedure Remarks RAV-SM∗∗∗BT ∗Fan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch No. Part name Procedure Remarks 100101 102 103 222 209237 104404MUT-E 454MUT-E 564MUT-E 105Location Description Model name 106 404MUT-TR 454MUT-TR 564MUT-TR107 Electric parts401 Location Model name108 109 RAV-SM564BT-E RAV-SM564BT-TR110 111 RAV-SM804BT-E RAV-SM804BT-TR112 113 1104BT-TR564BT-E 804BT-E 1104BT-E 1404BT-E 114Location Model name RAV-SM Description 115 264220 Location 116Description Model name RAV-SM 117 118 Description 564CT-E 804CT-E 1104CT-E 1404CT-ECheck of Concentration Limit Toshiba Carrier Corporation