No. | Item | Outline of specifications | Remarks |
|
|
|
|
6 | Fan speed control | 1) Operation with (HH), (H), (L) or [AUTO] mode is carried | HH > H+ > H > L+ > |
|
| out by the command from the remote controller. | L > UL |
2)When the fan speed mode [AUTO] is selected, the fan speed varies by the difference between Ta and Ts.
<COOL> |
|
| |
Ta ˚C |
| A | |
+3.0 |
| ||
HH | B | ||
+2.5 | |||
(HH) | C | ||
| |||
+2.0 |
| ||
H+ (HH) | D | ||
+1.5 | |||
H (HH) |
| ||
+1.0 |
| ||
L+ (H+) | E | ||
+0.5 | |||
L (H) |
| ||
Tsc |
| ||
L (H) | F | ||
L (L+) | G | ||
|
•Controlling operation in case when thermostat of remote controller works is same as a case when thermostat of the body works.
•If the fan speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the fan speed changes.
•When cooling operation has started, select a downward slope for the fan speed, that is, the high position.
•If the temperature is just on the difference boundary, the fan speed does not change.
•Mode in the parentheses indicates one in automatic cooling operation.
<HEAT>
Ta ˚C | L (L+) |
| |
| |||
L+ (H) | E | ||
| |||
(0) Tsh |
| ||
H (H+) |
| ||
(+0.5) +1.0 |
| ||
| D | ||
| H+ | ||
|
| ||
(+1.0) +2.0 | (HH) |
| |
| C | ||
(+1.5) +3.0 | HH | ||
| |||
(HH) | B | ||
(+2.0) +4.0 | |||
| A | ||
|
|
Value in the parentheses indicates one when thermostat of the remote controller works.
Value without parentheses indicates one when thermostat of the body works.
•If the fan speed has been changed once, it is not changed for 1 minute. However when the fan speed exchanged, the fan speed changes.
•When heating operation has started, select an upward slope for the fan speed, that is, the high position.
•If the temperature is just on the difference boundary, the fan speed does not change.
• Mode in the parentheses indicates one in automatic | Tc: Indoor heat |
heating operation. | exchanger sensor |
• In Tc ≥ 60°C, the fan speed increases by 1 step. | temperature |
– 29 –