Check Code List
Error mode detected by indoor unit
|
| Operation of diagnostic function |
|
|
|
| ||
|
|
|
|
|
|
|
| Judgment and measures |
Check |
| Cause of operation |
| Status of |
| Condition |
| |
|
|
|
| |||||
|
|
|
|
| ||||
code |
|
| air conditioner |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| No communication from remote |
| Stop |
| Displayed when | 1. | Check cables of remote controller and communication adapters. |
E03 |
|
|
|
| • Remote controller LCD display OFF (Disconnection) | |||
| controller (including wireless) and |
|
|
| ||||
|
| (Automatic reset) |
| error is detected |
| |||
|
| communication adapter |
|
|
| • Central remote controller [97] check code | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| The serial signal is not output from |
|
|
|
| 1. | Outdoor unit does not completely operate. |
|
| outdoor unit to indoor unit. |
|
|
|
|
| • |
|
| • Miswiring of |
|
|
|
|
| |
|
|
| Stop |
| Displayed when |
| • Check outdoor P.C. board. Correct wiring of P.C. board. | |
E04 |
| • Defective serial sending circuit on |
|
|
| |||
|
| (Automatic reset) |
| error is detected | 2. When outdoor unit normally operates | |||
|
|
|
| |||||
|
| outdoor P.C. board |
|
|
|
|
| Check P.C. board (Indoor receiving / Outdoor sending). |
|
| • Defective serial receiving circuit on |
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
| indoor P.C. board |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E08 |
| Duplicated indoor unit address |
|
|
|
| 1. | Check whether remote controller connection (Group/Individual) |
|
|
|
|
|
|
|
| was changed or not after power supply turned on |
|
|
|
|
|
|
|
| |
L03 |
| Duplicated indoor header unit |
|
|
| Displayed when |
| (Finish of group construction/Address check). |
|
|
|
| Stop |
|
| * If group construction and address are not normal when the | |
|
|
|
|
|
| |||
|
| There is group wire in individual indoor |
|
| error is detected |
| ||
L07 |
|
|
|
| power has been turned on, the mode automatically shifts to | |||
|
|
|
|
| ||||
|
|
|
|
|
| |||
|
| unit. |
|
|
|
|
| address setup mode. (Resetting of address) |
|
|
|
|
|
|
|
|
|
L08 |
| Unset indoor group address |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
L09 |
| Unset indoor capacity |
| Stop |
| Displayed when | 1. Set indoor capacity (DN=11) | |
|
|
| error is detected |
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
L30 |
| Abnormal input of outside interlock |
| Stop |
| Displayed when | 1. Check outside devices. | |
|
|
| error is detected | 2. | Check indoor P.C. board. | |||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| Float switch operation |
|
|
|
| 1. | Trouble of drain pump |
P10 |
|
| Stop |
| Displayed when | 2. Clogging of drain pump | ||
| • Float circuit, Disconnection, |
|
| |||||
|
|
| error is detected | 3. | Check float switch. | |||
|
|
|
|
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
| 4. | Check indoor P.C. board. | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1. | Position detection error |
P12 |
| Indoor DC fan error |
| Stop |
| Displayed when | 2. Indoor fan driving part | |
|
|
| error is detected | 3. | Indoor fan lock | |||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 4. | Indoor P.C. board check |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1. | Check | |
|
|
| Stop |
| Displayed when | 2. Check | ||
P19 |
| • After heating operation has started, |
|
| ||||
|
| (Automatic reset) |
| error is detected | 3. | Check indoor heat exchanger (TC/TCJ). | ||
|
| indoor heat exchangers temp. is |
|
| ||||
|
|
|
|
|
| |||
|
| down. |
|
|
|
| 4. | Check indoor P.C. board. |
|
|
|
|
|
|
|
|
|
|
| Own unit stops while warning is output |
| Stop |
| Displayed when | 1. | Judge follower unit while master unit is [E03], [L03], [L07] or [L08]. |
P31 |
|
| (Follower unit) |
| 2. | Check indoor P.C. board. | ||
| to other indoor units. |
|
| error is detected | ||||
|
|
| (Automatic reset) |
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
F01 |
|
| Stop |
| Displayed when | 1. | Check indoor heat exchanger temp. sensor (TCJ). | |
| indoor heat exchanger temp. sensor |
|
| 2. Check indoor P.C. board. | ||||
|
| (Automatic reset) |
| error is detected | ||||
|
| (TCJ) |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| Stop |
| Displayed when | 1. | Check indoor heat exchanger temp. sensor (TC). | |
F02 |
| indoor heat exchanger temp. sensor |
|
| 2. Check indoor P.C. board. | |||
|
| (Automatic reset) |
| error is detected | ||||
|
| (TC) |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
F10 |
|
| Stop |
| Displayed when | 1. | Check indoor heat exchanger temp. sensor (TA). | |
| indoor heat exchanger temp. sensor |
|
| 2. Check indoor P.C. board. | ||||
|
| (Automatic reset) |
| error is detected | ||||
|
| (TA) |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
F29 |
| Indoor EEPROM error |
| Stop |
| Displayed when | 1. Check indoor EEPROM. (including socket insertion) | |
| • EEPROM access error |
| (Automatic reset) |
| error is detected | 2. | Check indoor P.C. board. | |
|
|
|
| |||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| Communication error between indoor |
| Stop |
|
| 1. | Check indoor P.C. board. |
E10 |
| MCU |
|
| Displayed when |
|
| |
| • Communication error between fan |
| (Automatic reset) |
| error is detected |
|
| |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
| driving MCU and main MCU |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Regular communication error between |
| Stop |
| Displayed when | 1. | Check remote controller wiring. |
E18 |
|
|
| 2. | Check indoor power supply wiring. | |||
| indoor header and follower units |
| (Automatic reset) |
| error is detected | |||
|
|
|
| 3. | Check indoor P.C. board. | |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
– 48 –