Toshiba RAV-SM564BT-TR, RAV-SM454MUT-E Power supply error of remote controller, Indoor

Page 51

Error mode detected by remote controller or central controller (TCC-LINK)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judgment and measures

 

 

 

Check code

Cause of operation

Status of

Condition

 

 

 

 

 

 

 

 

 

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply error of remote controller, Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

Not displayed at all

No communication with master indoor unit

 

 

2.

Check remote controller.

 

 

 

 

 

• Remote controller wiring is not correct.

 

 

3.

Check indoor power wiring.

 

(Operation on

Stop

 

 

 

remote controller

• Power of indoor unit is not turned on.

4.

Check indoor P.C. board.

 

 

 

 

is impossible.)

 

 

 

 

• Automatic address cannot be completed.

 

 

5.

Check indoor EEPROM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(including socket insertion)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address repeating phenom-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enon generates.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No communication with master indoor unit

Stop

 

Receiving error from remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

 

 

 

 

 

E01

• Disconnection of inter-unit wire between

(Automatic reset)

Displayed when

 

 

 

 

 

 

2.

Check remote controller.

 

 

 

 

 

 

2

remote controller and master indoor unit

If center exists,

error is detected

 

 

 

 

 

 

3.

Check indoor power wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

operation continues.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

Sending error of remote controller

 

 

 

 

 

 

E02

Signal send error to indoor unit

(Automatic reset)

Displayed when

1. Check sending circuit inside of remote

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

If center exists,

error is detected

 

controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation continues.

 

 

Replace remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

1.

In 2-remote controllers (including wireless),

 

 

 

 

 

 

E09

There are multiple main remote controllers.

Displayed when

 

there are multiple main units.

 

 

 

 

 

 

(Sub unit

 

 

 

 

 

 

 

(Detected by remote controller side)

error is detected

 

Check that there are 1 main remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continues operation.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller and other sub remote controllers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L20

Duplicated indoor central addresses on

Stop

Displayed when

1.

Check setting of central control system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication of central control system

 

network address. (Network adapter SW01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central controller

(Detected by indoor/central controller side)

(Automatic reset)

error is detected

2. Check network adapter P.C. board.

 

 

 

 

 

 

L20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check communication wire / miswiring

 

 

 

 

 

 

3

 

 

 

2.

Check communication (U3, U4 terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication circuit error of central

Continues

Displayed when

3.

Check network adapter P.C. board.

 

Central controller

 

control system

4. Check central controller (such as central

 

 

 

 

 

(Send)

(By remote controller)

error is detected

 

 

 

 

 

(Detected by central controller side)

 

 

 

 

 

 

C05

 

 

 

control remote controller, etc.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

Check terminal resistance. (TCC-LINK)

 

 

 

 

(Receive)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Gr sub unit error

Continuation/Stop

Displayed when

Check the check code of the corresponding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(According

 

Central controller

(Detected by central controller side)

error is detected

unit from remote controller.

 

to each case)

 

 

 

 

 

 

P30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 The check code cannot be displayed by the wired remote controller. (Usual operation of air conditioner becomes unavailable.)

For the wireless models, an error is notified with indication lamp.

3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4), and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according to the contents.

– 51 –

Image 51
Contents Split Type Contents Indoort Unit TroubleshootingOriginal instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornDescription Confirmation of warning label on the main unitPrecaution for Safety Proceeding with the repair work Refrigerant used by this air conditioner is the R410A Resistance and water drainage Explanations given to user RelocationDeclaration of Conformity Specifications Joint Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsSM56 type Round duct Concealed Duct typeSM110 type Round duct RAV-SM404MUT∗, RAV-SM454MUT∗, RAV-SM564MUT∗ Space required for Installation and servicingRAV-SM564BT∗, RAV-SM804BT∗, RAV-SM1104BT∗, RAV-SM1404BT∗ DimensionRAV-SM564CT∗, RAV-SM804CT∗, RAV-SM1104CT∗, RAV-SM1404CT∗ Compact 4-way Cassette Type RAV-SM564BT ∗, RAV-SM804BT ∗, RAV-SM1104BT ∗, RAV-SM1404BT ∗ RAV-SM564CT ∗, RAV-SM804CT ∗, RAV-SM1104CT ∗, RAV-SM1404CT ∗ Ceiling TypeParts name Type Specifications Specifications of Electrical PartsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramWireless remote controller Case of Connection of Wireless Remote ControllerMax units Control outline Command Outline of specifications RemarksTemperature in heating Heat Ceiling type Outline of specificationsConditions TcjTcn Tc nSetup at shipment All operations Cooling/dry operation Heating/fan operationAll modes AlarmCase of wired remote controller LCD Figure if To 28C Setup AT Local Outline of specifications Remarks TCJ Exct Disp CHK MCC-1402Indoor P.C. Board Optional Connector Specifications MCC-1402 Wired remote controller type Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Remote controller detected Indoor unit detectedCentral control devices detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Power supply error of remote controller, Indoor E09 error Check code E01 errorE10 error E04 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller F10 error P10 errorP12 error Exchange to heating cycle P19 errorCheck by tester Exchange to cooling cycleF01 error F02 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TA, TC, TCJ, TE,TS, to sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresCode No. required at least Contents MCC-1402 Writing the setting data to EepromType Code No Setting data Factory-set valueSetting data Type Type name abb Setting data TypeCompact 4-way Cassette Type and Concealed Duct Type Test Run Setup on Remote Controller Wired remote controllerTest cooling operation Test heating operation Procedure DescriptionPractical operation LED Display on Indoor P.C. Board D002 RedD203 Red To change item to be set up, proceed to Procedure Function Selection SetupUsing the set temperature To change the selected indoor unit, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment Setup method Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit When connected 2 remote controllers operate the twinContents System example Calling of error history ContentsPushing Test button returns the display to usual display Group control operationIndoor unit power-ON sequence Initial communicationUsual regular communication Model name TCB-PCNT30TLE Microprocessor block diagramModel connection interface wiring connection Model Connection Interface TCC-LINK adapterC. Board Switch SW01 Setup Wiring SpecificationsPush Test + Vent buttons for 4 seconds or more How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Address setupDuring unset time, At shipment from factory is displayed Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationExample Only turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringButton Using timer time Buttons, set the line addressPush SET + CL + Test buttons Simultaneously for 4 seconds or moreProcedure To know the position of indoor unit body by addressButton if the unit stops Attachment Part name ProcedureCeiling panel RBC-UM11PGWE Preparing work DetachmentPart name Procedure Remarks Panel has directionality Part name Procedure Remarks Ceiling panelNo. Part name Procedure RemarksElectric parts box No. Part name Procedure Fan motor 1. Detachment Drain pump 1. Detachment Drain pan 1. DetachmentPart name Procedure Remarks Heat Exchanger Recover refrigerant gasDetails of sensor lead wire drawing RAV-SM∗∗∗BT ∗ Part name Procedure RemarksFan motor Remove the Multi blade fan † Drain pump Remove the drain pan and float switch 100 No. Part name Procedure Remarks101 102 103 104 209237 222105 Location Description Model name404MUT-E 454MUT-E 564MUT-E 404MUT-TR 454MUT-TR 564MUT-TR 106Location Model name Electric parts401 107108 RAV-SM564BT-E RAV-SM564BT-TR 109110 RAV-SM804BT-E RAV-SM804BT-TR 111112 1104BT-TR 113114 Location Model name RAV-SM Description564BT-E 804BT-E 1104BT-E 1404BT-E 264 220115 116 Description Model name RAV-SMLocation 117 Description 564CT-E 804CT-E 1104CT-E 1404CT-E 118Check of Concentration Limit Toshiba Carrier Corporation