Error mode detected by remote controller or central controller
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Operation of diagnostic function |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Judgment and measures |
|
|
| Check code | Cause of operation | Status of | Condition |
| ||||||||||||
|
|
|
|
| |||||||||||||||
|
|
| air conditioner |
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Power supply error of remote controller, Indoor | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| EEPROM error | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1. | Check remote controller |
| Not displayed at all | No communication with master indoor unit |
|
| 2. | Check remote controller. | |||||||||||||
|
|
|
| ||||||||||||||||
| • Remote controller wiring is not correct. |
|
| 3. | Check indoor power wiring. | ||||||||||||||
| (Operation on | Stop | — | ||||||||||||||||
|
| ||||||||||||||||||
| remote controller | • Power of indoor unit is not turned on. | 4. | Check indoor P.C. board. | |||||||||||||||
|
|
| |||||||||||||||||
| is impossible.) |
|
|
| |||||||||||||||
| • Automatic address cannot be completed. |
|
| 5. | Check indoor EEPROM. | ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (including socket insertion) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| → Automatic address repeating phenom- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| enon generates. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| No communication with master indoor unit | Stop |
| Receiving error from remote controller | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1. | Check remote controller | ||
|
|
|
|
|
| E01 | • Disconnection of | (Automatic reset) | Displayed when | ||||||||||
|
|
|
|
|
| 2. | Check remote controller. | ||||||||||||
|
|
|
|
|
| ∗2 | remote controller and master indoor unit | ∗ If center exists, | error is detected | ||||||||||
|
|
|
|
|
| 3. | Check indoor power wiring. | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (Detected by remote controller side) | operation continues. |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4. | Check indoor P.C. board. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Stop |
| Sending error of remote controller | |
|
|
|
|
|
| E02 | Signal send error to indoor unit | (Automatic reset) | Displayed when | 1. Check sending circuit inside of remote | |||||||||
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
| (Detected by remote controller side) | ∗ If center exists, | error is detected |
| controller. | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| operation continues. |
|
| → Replace remote controller. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Stop |
| 1. | In |
|
|
|
|
|
| E09 | There are multiple main remote controllers. | Displayed when |
| there are multiple main units. | |||||||||
|
|
|
|
|
| (Sub unit |
| ||||||||||||
|
|
|
|
|
| (Detected by remote controller side) | error is detected |
| Check that there are 1 main remote | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| continues operation.) |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| controller and other sub remote controllers. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| L20 | Duplicated indoor central addresses on | Stop | Displayed when | 1. | Check setting of central control system | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| communication of central control system |
| network address. (Network adapter SW01) | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| Central controller | (Detected by indoor/central controller side) | (Automatic reset) | error is detected | 2. Check network adapter P.C. board. | ||||||||||||||
|
|
|
|
|
| L20 |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
| — |
|
|
| 1. | Check communication wire / miswiring | ||||||||
|
|
|
|
|
| ∗3 |
|
|
| 2. | Check communication (U3, U4 terminals) | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Communication circuit error of central | Continues | Displayed when | 3. | Check network adapter P.C. board. |
| Central controller | ||||||||||||||||||
| control system | 4. Check central controller (such as central | |||||||||||||||||
|
|
|
|
| (Send) | (By remote controller) | error is detected | ||||||||||||
|
|
|
|
| (Detected by central controller side) | ||||||||||||||
|
|
|
|
|
| C05 |
|
|
| control remote controller, etc.) | |||||||||
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
| 5. | Check terminal resistance. | |||||||||
|
|
|
| (Receive) |
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
| C06 |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
| — | Indoor Gr sub unit error | Continuation/Stop | Displayed when | Check the check code of the corresponding | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (According | ||||
| Central controller | (Detected by central controller side) | error is detected | unit from remote controller. | |||||||||||||||
| to each case) | ||||||||||||||||||
|
|
|
|
|
| P30 |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
∗2 The check code cannot be displayed by the wired remote controller. (Usual operation of air conditioner becomes unavailable.)
For the wireless models, an error is notified with indication lamp.
∗3 This trouble is related to communication of remote controller (A, B), central system
– 51 –