(Indoor unit detected)
| Check code indication |
|
|
| Air conditioner operation | |
|
| Representative defective position |
| Explanation of error contents |
|
|
|
| Automatic | Operation | |||
|
|
|
| |||
| Remote controller |
|
|
| reset | continuation |
|
|
|
|
|
|
|
| E03 | Regular communication error between indoor and remote controller |
| No communication from remote controller and network adapter | ¡ | × |
|
| (Also no communication from central control system) | ||||
| E04 | Indoor/Outdoor serial error |
| There is error on serial communication between indoor and outdoor units | ¡ | × |
| E08 | Duplicated indoor addresses | ² | Same address as yours was detected. | ¡ | × |
| E10 | Communication error between indoor MCU |
| MCU communication error between main motor and micro computer | ¡ | × |
| E18 | Regular communication error between indoor master and follower units |
| Regular communication between indoor master and follower units is impossible. | ¡ | × |
| F01 | Indoor unit, Heat exchanger (TCJ) error |
| Open/short was detected on heat exchanger (TCJ). | ¡ | × |
| F02 | Indoor unit, Heat exchanger (TC) error |
| Open/short was detected on heat exchanger (TC). | ¡ | × |
| F10 | Indoor unit, Room temp. sensor (TA) error |
| Open/short was detected on room temp. sensor (TA). | ¡ | × |
| F29 | Indoor unit, other indoor P.C. board error |
| EEPROM error (Other error may be detected. If no error, automatic address is repeated. | × | × |
| L03 | Duplicated setting of indoor group master unit | ² | There are multiple master units in a group. | × | × |
| L07 | There is group cable in individual indoor unit. | ² | When even one group connection indoor unit exists in individual indoor unit. | × | × |
| L08 | Unset indoor group address | ² | Indoor group address is unset. | × | × |
| L09 | Unset indoor capacity |
| Capacity of indoor unit is unset. | × | × |
| L20 | Duplicated central control system address |
| Duplicated setting of central control system address | ¡ | × |
| L30 | Outside error input to indoor unit (Interlock) |
| Abnormal stop by outside error (CN80) input | × | × |
| P01 | Indoor unit, AC fan error |
| An error of indoor AC fan was detected. (Fan motor thermal relay worked.) | × | × |
– | P10 | Indoor unit, overflow detection |
| Float switch worked. | × | × |
|
| |||||
47 – | P12 | Indoor unit, DC fan error |
| Indoor DC fan error | × | × |
P19 |
| In heating operation, an error was detected by temp. down of indoor heat exchanger sensor. | ¡ | × | ||
| P31 | Other indoor unit error |
| Follower unit in group cannot operate by warning from [E03/L03/L07/L08] of master unit. | ¡ | × |
²When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
(Remote controller detected)
Check code indication |
|
| |
| Representative defective position | Explanation of error contents | |
Remote controller | |||
|
| ||
|
|
| |
E01 | No master remote controller, Remote controller communication (Receive) error | Signal cannot be received from indoor unit. Master remote controller was not set. (including 2 remote controllers) | |
|
|
| |
E02 | Remote controller communication (Send) error | Signal cannot be sent to indoor unit. | |
|
|
| |
E09 | Duplicated master remote controller | In | |
(Indoor master unit stops warning and follower unit continues operation.) | |||
|
| ||
|
|
|
Air conditioner operation
Automatic | Operation |
reset | continuation |
|
|
— | — |
|
|
— | — |
×
(Central control devices detected)
Check code indication |
|
| Air conditioner operation | ||
| Representative defective position | Explanation of error contents |
|
| |
Automatic | Operation | ||||
|
| ||||
|
| reset | continuation | ||
|
|
| |||
|
|
|
|
| |
C05 | Central control system communication (send) error | Signal sending operation of central control system is impossible. There are multiple same central devices. | — | — | |
|
|
|
|
| |
C06 | Central control system communication (receive) error | Signal receiving operation of central control system is impossible. | — | — | |
|
|
|
|
| |
C12 | An error on device connected to | — | — | ||
|
|
|
|
| |
P30 | Group follower unit is defective. | Group follower unit is defective. (For remote controller, | — | — | |
|
|
|
|
| |
|
|
|
|
|
NOTE: Even for the same contents of error such as communication error, the display of check code may differ according to detection device.
When remote controller or central controller detects an error, it is not necessarily related to operation of the air conditioner. In this list, the check codes that outdoor unit detects are not described.