7 EVACUATING

Valve unit

Handle

Pull out the handle and using cutting pliers, etc. turn it counterclockwise by 90˚. (Open fully)

Charge port

Flare nut

Valve unit

Push in handle.

Charge port

Flare nut

Handle position

Handle

Opened fully

Closed completely

*1. Use the vacuum pump, vacuum pump adapters,

and gauge manifold referring to the manuals attached to each tool before using them. For the vacuum pump, check oil is filled up to the specified line of the oil gauge.

*2. While the air is purged, check again that the connecting port of charge hose, which has a projection to push the valve core, is firmly con- nected to the charge port.

Valve handling precautions

Open the valve stem or the handle until it strikes the stopper. It is unnecessary to apply further force.

Securely tighten the cap with a torque wrench.

Cap tightening torque

 

Ø6.4

14 to 18N•m (1.4 to 1.8kgf•m)

 

 

 

Valve

Ø9.5

33 to 42N•m (3.3 to 4.2kgf•m)

 

 

size

Ø12.7

33 to 42N•m (3.3 to 4.2kgf•m)

 

 

 

 

 

Ø15.9

20 to 25N•m (2.0 to 2.5kgf•m)

 

 

 

Charge port

14 to 18N•m (1.4 to 1.8kgf•m)

 

 

 

Additional refrigerant

1.The amount of refrigerant put into the outdoor unit at the factory is sufficient to fill up to 20m of refrigerant piping work.

2.If the length of the refrigerant piping work is 20m or less, addition of refrigerant at the installation site is unnecessary.

3.If the length of the piping work exceeds 20m, extra refrigerant must be added. Refer to the outdoor installation manual for details of the extra amounts.

4.Overcharge or undercharge of refrigerant in the outdoor unit may cause malfunction of the compressor.

Add Only R410A Refrigerant to These Units

Heat insulation

1.Provide heat insulation on the refrigerant piping on both the liquid side and gas side separately, and ensure that all joints in the insulation are compleatly sealed (without gap).

2.Since the temperature of the piping on the gas side increases during heating operations, the heat insulating material used must be able to withstand temperatures of more than 120°C.

3.Use the pipe insulation supplied in the accessory pack to insulate the piping connecting section on the indoor unit side.

101

Image 104
Contents Split Type Way Air Discharge Cassette Type Installation Manual Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-EPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Refrigerant Selection of InstallationAccessory and Installation Parts Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeSelection of Installation Installation of Outdoor UnitPiping connection Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe Cover Knockout procedureHow to remove the front panel Refrigerant Piping Pipe Forming/End PositioningFlaring size a Unit mm FlaringRequirement Tightening of Connecting PartRefrigerant Piping Vacuum pump EvacuatingAir Purge Evacuating Open CloseSM560AT-E How to remove the valve cover How to wireStripping length power cord and connecting cable Electrical WorkSelf-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation Changes in the product and components New tools for R410AAccessories Precautions for SafetyRemote controller Screws two pcs Standard 4-way cassette panel optional partsRAV-SM560UT-E RAV-SM800UT-E Outdoor unit Parts NameIndoor unit Parts Name of Remote Controller Display sectionOperation section Preparation Turn on the main power switch and/or the leakage breakerCorrect Usage Push button StopStart How to set up the wind direction How to start swingingHow to stop swinging Heat operationCancel of timer operation Timer OperationTimer operation Maintenance Hints for Economical OperationCleaning of panel and air filter Clean the panel and air filter with waterCleaning of Air Filters If you do not plan to use the unit for more than 1 monthCleaning of discharge flap Be careful to the direction of the flap when mountingAIR Conditioner Operations and Performance RE-INSTALLATION Do not install the air conditioner in the following placesTroubles and Causes Be careful with noise or vibrationsInoperative Page Accessory parts and Parts to be procured locally Separate sold partsPrecautions for Safety Precautions for Safety Avoid installing in the following places Selection of Installation PlaceInstallation space Selection of Installation Place Selection of installation place Discharge directionAdvice Height list of ceiling possible to be installedExternal view Installation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Drain Piping Work Piping/Heat insulating materialFlexible hose Adhesive inhibitedConnection procedure Drain upCheck the draining Perform heat insulatingPermissible Piping Length and Heat Flaring dia meter size a Unit mmTightening connection Tightening torque of flare pipe connectionsUse a vacuum pump Open the valve fullyGas leak check Thermal insulation processSM800 type valve at gas side Packed valve handling precautionsFor RAV-SM800AT-E model Be sure to connect earth wire. Grounding work Remote controller wiringThermal insulation to cabling connecting port Electrical WorkCable connection Cabling on the ceiling panelCabling Remote Controller CablingCabling diagram How to execute a test run Case of wired remote controllerTest RUN Before test runConfirmation and check TroubleshootingConfirmation of error history Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Test run display Operation mode displayFan mode display Filter UP/DOWN button Fan mode button ButtonUnit and Auto flap button No function Operation lamp Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Cleaning of Return grille Clean the Return grilles with waterAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation of Indoor Unit Installation procedureDimension Hanging down of indoor unitInstallation of Indoor Unit Restriction to installationConcealed duct type Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting WorkConnecting method of the duct AIR Ducting WorkPoints at installation work General cautionsMounting of remote controller Hanging of indoor unitMounting of filter and canvas for suction port For referenceConnection of the drain hose Piping materialPiping and cautions 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work INSTALLATION/SERVICING Tools ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Temporary button Name and Functions of Indicators and ControlsDisplay panel Name and Operations of Indicators and Controls Set up temp. button Central indicationLouver operation button ON/OFF buttonTurn on the power switch When restarting the operation after stopPush ON/OFF button CoolingSTART/STOP button DRY OperationSTART/STOP button Automatic operation Adjusting AIR Flow DirectionHOW the AIR Conditioner Works Air filter reset Cleaning of indoor unit and remote controllerTemporary Operation Temporary operationCleaning the air filter Clean the air filters as often as possibleCheck before operation Open the air inlet grilleHeating operation characteristics Preheating operation Cleaning the air inlet grilleMinute protection function Warm air controlProblems and Causes RecheckInoperative Does not cool well or heat wellWired remote Precautions for Safety Precautions for Safety Installation Procedure Installation Diagram of Indoor UnitMounting the Installation Plate When the installation plate is directly mounted on the wallGood location Bad location Piping and Drain Hose Installation Case of right-side exitCase of downward pipe exit Piping via left-hand connectionDrain Piping Work DrainagePermissible Piping Length and Head Evacuating 100 For RAV-SM560AT-E modelAdd Only R410A Refrigerant to These Units Heat insulation 101Additional refrigerant 102 Wiring between unitsWiring connections Installation of Remote Controllers Precautions103 Flush wall mounting104 Improving System EfficiencyOptions Final Installation Checks 105Environmental Issues Product maintenanceEnvironment 106

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.