Toshiba RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM560AT-E Points at installation work, General cautions

Page 75

Connecting method of the duct

1. Supply air side

<Round duct>

1.Make the round duct according to inner dimension of the flange

Use a glass wool board with inside/outside finishing 25mm-thickness and 24kg/m³-density.

2.Connect the flange and each type of duct. (Fig. 1)

Thermal insulator (50mm (w), 6mm (t))

Aluminum tape

 

Seal

(50mm-width)

 

Thermal insulator :

 

 

 

( 25mm (w), 6mm (t) )

 

 

 

 

25mm

 

 

 

 

 

 

 

 

<Square duct>

1.Using 6 screws, mount the flange to the supply air port of the indoor unit. (Fig. 2)

2.Make the square duct according to inner dimension

of the flange A x B .

Use a glass wool board with inside/outside finishing 25mm-thickness and 24kg/m³-density.

3. Connect the flange and each type of duct. (Fig. 3)

B

A

Fig. 2

Thermal insulator (50mm (w), 6mm (t))

Indoor unit

End

Round duct board Thermal insulator

(25mm thickness, 24kg/m³ or equivalent)

Fig. 1

Aluminum tape (50mm-width)

25mm

Square duct board (25mm)

Seal

( Thermal insulator : ) 25mm (w), 6mm (t)

End

Indoor unit

Points at installation work

nGeneral cautions

Fig. 3

1.Considering installation places of indoor unit supply chamber, structure of the building and determine the duct path.

2.In order to utilize the static pressure characteristics of the air supply in the indoor unit, design the duct branching having the large size of the air supply chamber or setting distance to the first branch as long as possible

(Min. : 200mm or longer) so that an even air volume can be obtained.

Especially, when branching just after air supply of the indoor unit, air concentrates at the center part and is difficult to flow to the ducts at both sides.

3.Connect each connecting section surely, and apply sufficient thermal insulation.

In this model of which the duct is branched in the ceiling, compared with the model for ordinary houses, the high temperature generates on the periphery in the cooling time (Especially, at attic and etc.), temperature difference increases between the supply air and outside of the duct, and dewing may occur.

Dewing on the surface of the thermal insulator covering the metal connecting section or leaking portion of the cooled air may cause a trouble such as water drops.

4.Thermal insulation of screwing sections is necessary.

Prevent dewing by applying thermal insulation to 6 screws those fix the duct flange of the air supply chamber.

For duct parts, the flexible branch duct (thermal insulation, 25mm or more thickness) is recommended.

Adjust the duct length to 6m or less even for straight pipe, and avoid sharp bending (Air flow resistance is large.) if bending.

72

Image 75
Contents Split Type Way Air Discharge Cassette Type Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-E Installation ManualConnect the connecting cable correctly Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInappropriate grounding may cause electric shock Before installation Accessory and RefrigerantSelection of Installation Accessory and Installation PartsObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeInstallation of Outdoor Unit Selection of InstallationOptional Installation Parts Local Procure Refrigerant Piping ConnectionPiping connection Knockout procedure How to remove the front panelKnockout of Pipe Cover Flaring Refrigerant PipingPipe Forming/End Positioning Flaring size a Unit mmTightening of Connecting Part Refrigerant PipingRequirement Evacuating Air PurgeVacuum pump Open Close EvacuatingElectrical Work SM560AT-E How to remove the valve coverHow to wire Stripping length power cord and connecting cableFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsStandard 4-way cassette panel optional parts AccessoriesPrecautions for Safety Remote controller Screws two pcsRAV-SM560UT-E RAV-SM800UT-E Parts Name Indoor unitOutdoor unit Display section Parts Name of Remote ControllerOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation Stop StartPush button Heat operation How to set up the wind directionHow to start swinging How to stop swingingTimer Operation Timer operationCancel of timer operation Hints for Economical Operation MaintenanceIf you do not plan to use the unit for more than 1 month Cleaning of panel and air filterClean the panel and air filter with water Cleaning of Air FiltersBe careful to the direction of the flap when mounting Cleaning of discharge flapAIR Conditioner Operations and Performance Be careful with noise or vibrations RE-INSTALLATIONDo not install the air conditioner in the following places Troubles and CausesInoperative Page Separate sold parts Accessory parts and Parts to be procured locallyPrecautions for Safety Precautions for Safety Selection of Installation Place Installation spaceAvoid installing in the following places Height list of ceiling possible to be installed Selection of Installation PlaceSelection of installation place Discharge direction AdviceExternal view Installation of ceiling opening and hanging bolt Installation of hanging boltInstallation of ceiling panel Sold separately Adhesive inhibited Drain Piping WorkPiping/Heat insulating material Flexible hosePerform heat insulating Connection procedureDrain up Check the drainingTightening torque of flare pipe connections Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening connectionThermal insulation process Use a vacuum pumpOpen the valve fully Gas leak checkPacked valve handling precautions For RAV-SM800AT-E modelSM800 type valve at gas side Remote controller wiring Be sure to connect earth wire. Grounding workCabling on the ceiling panel Thermal insulation to cabling connecting portElectrical Work Cable connectionRemote Controller Cabling Cabling diagramCabling Before test run How to execute a test runCase of wired remote controller Test RUNTroubleshooting Confirmation of error historyConfirmation and check Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Operation mode display Fan mode displayTest run display Fan mode button Button Unit and Auto flap button No function Operation lampFilter UP/DOWN button Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Clean the Return grilles with water Cleaning of Return grilleAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation procedure Installation of Indoor UnitHanging down of indoor unit DimensionLedge ceiling concealed duct type Installation of Indoor UnitRestriction to installation Concealed duct typeAIR Ducting Work Static pressure characteristics of each modelAIR Ducting Work Connecting method of the ductGeneral cautions Points at installation workFor reference Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portPiping material Piping and cautionsConnection of the drain hose 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work Tools INSTALLATION/SERVICING ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Name and Functions of Indicators and Controls Display panelTemporary button Name and Operations of Indicators and Controls ON/OFF button Set up temp. buttonCentral indication Louver operation buttonCooling Turn on the power switchWhen restarting the operation after stop Push ON/OFF buttonDRY Operation START/STOP buttonSTART/STOP button Adjusting AIR Flow Direction HOW the AIR Conditioner WorksAutomatic operation Temporary operation Air filter resetCleaning of indoor unit and remote controller Temporary OperationOpen the air inlet grille Cleaning the air filterClean the air filters as often as possible Check before operationWarm air control Heating operation characteristics Preheating operationCleaning the air inlet grille Minute protection functionDoes not cool well or heat well Problems and CausesRecheck InoperativeWired remote Precautions for Safety Precautions for Safety When the installation plate is directly mounted on the wall Installation ProcedureInstallation Diagram of Indoor Unit Mounting the Installation PlateGood location Bad location Piping via left-hand connection Piping and Drain Hose InstallationCase of right-side exit Case of downward pipe exitDrainage Drain Piping WorkPermissible Piping Length and Head Evacuating For RAV-SM560AT-E model 100101 Additional refrigerantAdd Only R410A Refrigerant to These Units Heat insulation Wiring between units Wiring connections102 Flush wall mounting Installation of Remote ControllersPrecautions 103Improving System Efficiency Options104 105 Final Installation Checks106 Environmental IssuesProduct maintenance Environment

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.