Flare at indoor unit side

6 REFRIGERANT PIPING

Refrigerant Piping

1.If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.

2.Use copper pipe with 0.8 mm or more thickness.

3.Flare nut and flare works are also different from those of the conventional refrigerant.

Take out the flare nut attached to the main unit of the air conditioner, and use it.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1.Remove dust and moisture from the inside of the connecting pipes.

2.Tight connection (between pipes and unit)

3.Evacuate the air in the connecting pipes using

VACUUM PUMP.

4.Check the gas leakage. (connected points)

Permissible Piping Length and Heat

The maximum piping length from the outdoor to indoor unit

30 m (Chargeless 20m)

50 m (Chargeless 20m)

(RAV-SM560AT-E)

(RAV-SM800AT-E)

The maximum height difference outdoor/indoor unit

Outdoor unit is above

Outdoor unit is below

 

 

30m

15m

 

 

Flaring

Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for

R410A are recommended.

B

However, the conventional tools can be used by adjusting projection margin of the copper pipe.

• Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

Outer diam. of

R410A tool used

Conventional tool used

 

 

 

 

copper pipe

 

R410A

R22

R410A

R22

 

 

 

 

 

 

 

6.35 to 9.52

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

Imperial (Wing nut type)

Outer diam. of copper pipe

R410A

R22

 

 

 

6.35 or 9.52

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7 or 15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

• Flaring dia meter size : A (Unit : mm)

 

 

A +0

Outer diam. of copper pipe

 

- 0.4

R410A

 

R22

 

 

 

 

 

 

6.35

9.1

 

9.0

 

 

 

 

9.52

13.2

 

13.0

 

 

 

 

12.7

16.6

 

16.2

 

 

 

 

15.9

19.7

 

19.4

 

 

 

 

*In the case of flaring for R410A with the conventional flare tool, pull out it approx.

0.5 mm more than that for R22 to

 

 

 

A

 

adjust to the specified flare size.

 

 

 

 

 

 

 

 

 

 

The copper pipe gauge is useful

 

 

 

 

 

 

 

 

 

for adjusting projection margin size.

 

 

 

Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit : N•m)

 

 

Outer diam. of copper pipe

Tightening torque

 

 

6.35 mm (diam.)

14 to 18 (1.4 to 1.8 kgf•m)

 

 

9.52 mm (diam.)

33 to 42 (3.3 to 4.2 kgf•m)

 

 

12.7 mm (diam.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

15.9 mm (diam.)

63 to 77 (6.3 to 7.7 kgf•m)

 

 

Tightening torque of flare pipe connections

Pressure of R410A becomes higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten firmly the flare pipe connecting

sections which connect the indoor and outdoor units up to the specified tightening torque.

Incorrect connections may cause not only a gas leakage, but also a trouble of the refrigeration cycle or compressor damage.

Flare at outdoor unit side

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union

Flare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

75

Image 78
Contents Split Type Way Air Discharge Cassette Type Installation Manual Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-ETo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Installation Parts Accessory and RefrigerantSelection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSelection of Installation Installation of Outdoor UnitOptional Installation Parts Local Procure Refrigerant Piping ConnectionPiping connection Knockout procedure How to remove the front panelKnockout of Pipe Cover Flaring size a Unit mm Refrigerant PipingPipe Forming/End Positioning FlaringTightening of Connecting Part Refrigerant PipingRequirement Evacuating Air PurgeVacuum pump Evacuating Open CloseStripping length power cord and connecting cable SM560AT-E How to remove the valve coverHow to wire Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ARemote controller Screws two pcs AccessoriesPrecautions for Safety Standard 4-way cassette panel optional partsRAV-SM560UT-E RAV-SM800UT-E Parts Name Indoor unitOutdoor unit Parts Name of Remote Controller Display sectionOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation Stop StartPush button How to stop swinging How to set up the wind directionHow to start swinging Heat operationTimer Operation Timer operationCancel of timer operation Maintenance Hints for Economical OperationCleaning of Air Filters Cleaning of panel and air filterClean the panel and air filter with water If you do not plan to use the unit for more than 1 monthCleaning of discharge flap Be careful to the direction of the flap when mountingAIR Conditioner Operations and Performance Troubles and Causes RE-INSTALLATIONDo not install the air conditioner in the following places Be careful with noise or vibrationsInoperative Page Accessory parts and Parts to be procured locally Separate sold partsPrecautions for Safety Precautions for Safety Selection of Installation Place Installation spaceAvoid installing in the following places Advice Selection of Installation PlaceSelection of installation place Discharge direction Height list of ceiling possible to be installedExternal view Installation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Flexible hose Drain Piping WorkPiping/Heat insulating material Adhesive inhibitedCheck the draining Connection procedureDrain up Perform heat insulatingTightening connection Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Use a vacuum pumpOpen the valve fully Thermal insulation processPacked valve handling precautions For RAV-SM800AT-E modelSM800 type valve at gas side Be sure to connect earth wire. Grounding work Remote controller wiringCable connection Thermal insulation to cabling connecting portElectrical Work Cabling on the ceiling panelRemote Controller Cabling Cabling diagramCabling Test RUN How to execute a test runCase of wired remote controller Before test runTroubleshooting Confirmation of error historyConfirmation and check Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Operation mode display Fan mode displayTest run display Fan mode button Button Unit and Auto flap button No function Operation lampFilter UP/DOWN button Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Cleaning of Return grille Clean the Return grilles with waterAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation of Indoor Unit Installation procedureDimension Hanging down of indoor unitConcealed duct type Installation of Indoor UnitRestriction to installation Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting WorkConnecting method of the duct AIR Ducting WorkPoints at installation work General cautionsMounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit For referencePiping material Piping and cautionsConnection of the drain hose 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work INSTALLATION/SERVICING Tools ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Name and Functions of Indicators and Controls Display panelTemporary button Name and Operations of Indicators and Controls Louver operation button Set up temp. buttonCentral indication ON/OFF buttonPush ON/OFF button Turn on the power switchWhen restarting the operation after stop CoolingDRY Operation START/STOP buttonSTART/STOP button Adjusting AIR Flow Direction HOW the AIR Conditioner WorksAutomatic operation Temporary Operation Air filter resetCleaning of indoor unit and remote controller Temporary operationCheck before operation Cleaning the air filterClean the air filters as often as possible Open the air inlet grilleMinute protection function Heating operation characteristics Preheating operationCleaning the air inlet grille Warm air controlInoperative Problems and CausesRecheck Does not cool well or heat wellWired remote Precautions for Safety Precautions for Safety Mounting the Installation Plate Installation ProcedureInstallation Diagram of Indoor Unit When the installation plate is directly mounted on the wallGood location Bad location Case of downward pipe exit Piping and Drain Hose InstallationCase of right-side exit Piping via left-hand connectionDrain Piping Work DrainagePermissible Piping Length and Head Evacuating 100 For RAV-SM560AT-E model101 Additional refrigerantAdd Only R410A Refrigerant to These Units Heat insulation Wiring between units Wiring connections102 103 Installation of Remote ControllersPrecautions Flush wall mountingImproving System Efficiency Options104 Final Installation Checks 105Environment Environmental IssuesProduct maintenance 106

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.