Toshiba RAM-SM800UT-E, RAM-SM800KRT-E Use a vacuum pump, Open the valve fully, Gas leak check

Page 45

5 EVACUATING

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.

Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump.

Use a vacuum pump

Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops.

1.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.

2.Connect the charge hose to the port of vacuum pump.

3.Open fully the low pressure side handle of the gauge manifold valve.

4.Operate the vacuum pump to start evacuating.

Perform evacuating for about 35 minutes if the piping length is 30 meters total for model SM560 and 50 meters for model SM800

(assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is –101 kPa ( –76 cmHg).

5.Close the low pressure side valve handle of gauge manifold.

6.Open fully the valve stem of the packed valves (both sides of Gas and Liquid).

7.Remove the charging hose from the service port.

8.Securely tighten the caps on the packed valves.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

REQUIREMENT

Charging an excessive or too little amount of refrigerant causes a trouble of the compressor. Be sure to charge the refrigerant of specified amount.

A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit. It is necessary to troubleshoot the compressor and refrigeration cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4mm- hexagonal wrench is required for opening the valve.

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

Thermal insulation process

Apply thermal insulation for the pipes separately at liquid side and gas side.

For the thermal insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 120°C or higher.

Using the attached thermal insulation material, apply the thermal insulation to the pipe connecting section of the indoor unit securely without gap.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual.

Be sure to use a scale to charge the refrigerant of specified amount.

REQUIREMENT

Apply the thermal insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe exposed to the outside causes water leak.)

42

Image 45
Contents Split Type Way Air Discharge Cassette Type Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-E Installation ManualNew Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyInappropriate grounding may cause electric shock Selection of Installation Accessory and RefrigerantAccessory and Installation Parts Before installationNecessary Space for Installation Installation PlaceObstacle at rear side Upper side is free Obstacle at front side Upper side is freeInstallation of Outdoor Unit Selection of InstallationOptional Installation Parts Local Procure Refrigerant Piping ConnectionPiping connection Knockout procedure How to remove the front panelKnockout of Pipe Cover Pipe Forming/End Positioning Refrigerant PipingFlaring size a Unit mm FlaringTightening of Connecting Part Refrigerant PipingRequirement Evacuating Air PurgeVacuum pump Open Close EvacuatingHow to wire SM560AT-E How to remove the valve coverStripping length power cord and connecting cable Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsPrecautions for Safety AccessoriesRemote controller Screws two pcs Standard 4-way cassette panel optional partsRAV-SM560UT-E RAV-SM800UT-E Parts Name Indoor unitOutdoor unit Display section Parts Name of Remote ControllerOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation Stop StartPush button How to start swinging How to set up the wind directionHow to stop swinging Heat operationTimer Operation Timer operationCancel of timer operation Hints for Economical Operation MaintenanceClean the panel and air filter with water Cleaning of panel and air filterCleaning of Air Filters If you do not plan to use the unit for more than 1 monthBe careful to the direction of the flap when mounting Cleaning of discharge flapAIR Conditioner Operations and Performance Do not install the air conditioner in the following places RE-INSTALLATIONTroubles and Causes Be careful with noise or vibrationsInoperative Page Separate sold parts Accessory parts and Parts to be procured locallyPrecautions for Safety Precautions for Safety Selection of Installation Place Installation spaceAvoid installing in the following places Selection of installation place Discharge direction Selection of Installation PlaceAdvice Height list of ceiling possible to be installedExternal view Installation of ceiling opening and hanging bolt Installation of hanging boltInstallation of ceiling panel Sold separately Piping/Heat insulating material Drain Piping WorkFlexible hose Adhesive inhibitedDrain up Connection procedureCheck the draining Perform heat insulatingFlaring dia meter size a Unit mm Permissible Piping Length and HeatTightening connection Tightening torque of flare pipe connectionsOpen the valve fully Use a vacuum pumpGas leak check Thermal insulation processPacked valve handling precautions For RAV-SM800AT-E modelSM800 type valve at gas side Remote controller wiring Be sure to connect earth wire. Grounding workElectrical Work Thermal insulation to cabling connecting portCable connection Cabling on the ceiling panelRemote Controller Cabling Cabling diagramCabling Case of wired remote controller How to execute a test runTest RUN Before test runTroubleshooting Confirmation of error historyConfirmation and check Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Operation mode display Fan mode displayTest run display Fan mode button Button Unit and Auto flap button No function Operation lampFilter UP/DOWN button Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Clean the Return grilles with water Cleaning of Return grilleAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation procedure Installation of Indoor UnitHanging down of indoor unit DimensionRestriction to installation Installation of Indoor UnitConcealed duct type Ledge ceiling concealed duct typeAIR Ducting Work Static pressure characteristics of each modelAIR Ducting Work Connecting method of the ductGeneral cautions Points at installation workHanging of indoor unit Mounting of remote controllerMounting of filter and canvas for suction port For referencePiping material Piping and cautionsConnection of the drain hose 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work Tools INSTALLATION/SERVICING ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Name and Functions of Indicators and Controls Display panelTemporary button Name and Operations of Indicators and Controls Central indication Set up temp. buttonLouver operation button ON/OFF buttonWhen restarting the operation after stop Turn on the power switchPush ON/OFF button CoolingDRY Operation START/STOP buttonSTART/STOP button Adjusting AIR Flow Direction HOW the AIR Conditioner WorksAutomatic operation Cleaning of indoor unit and remote controller Air filter resetTemporary Operation Temporary operationClean the air filters as often as possible Cleaning the air filterCheck before operation Open the air inlet grilleCleaning the air inlet grille Heating operation characteristics Preheating operationMinute protection function Warm air controlRecheck Problems and CausesInoperative Does not cool well or heat wellWired remote Precautions for Safety Precautions for Safety Installation Diagram of Indoor Unit Installation ProcedureMounting the Installation Plate When the installation plate is directly mounted on the wallGood location Bad location Case of right-side exit Piping and Drain Hose InstallationCase of downward pipe exit Piping via left-hand connectionDrainage Drain Piping WorkPermissible Piping Length and Head Evacuating For RAV-SM560AT-E model 100101 Additional refrigerantAdd Only R410A Refrigerant to These Units Heat insulation Wiring between units Wiring connections102 Precautions Installation of Remote Controllers103 Flush wall mountingImproving System Efficiency Options104 105 Final Installation ChecksProduct maintenance Environmental IssuesEnvironment 106

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.