AIR CONDITIONER OPERATIONS AND PERFORMANCE

3 minutes protection function

3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power switch/circuit breaker is turned on for re-starting the air conditioner.

Power failure

Power failure during operation will stop the unit completely.

To restart the operation, push the START/STOP button on the remote controller.

Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main power switch or circuit breaker and then turn them on again. Push the START/STOP button on the remote controller to restart.

Heating characteristics

Preheating operation

The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out after approximately 5 minutes when the indoor heat exchanger warmed up.

Warm air control (In heating operation)

When the room temperature reaches the set temperature, the fan speed is automatically reduced to prevent to blow cold draft. At this time, the outdoor unit will stop.

Defrosting operation

If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately 2 to 10 minutes) to maintain the heating capacity.

The fans in both indoor and outdoor units will stop during the defrosting operation.

During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor unit.

Heating capacity

In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating is called heat pump system. When the outside temperature is too low, it is recommended to use another heating apparatus in combination with the air conditioner.

Attention to snowfall and freeze on the outdoor unit

In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up. If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.

In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside for freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine failure or poor warming.

Air conditioner operating conditions

For proper performance, operate the air conditioner under the following temperature conditions:

Cooling

Outdoor temperature

: –5°C to 43°C

operation

 

 

Room temperature

: 21°C to 32°C (Dry valve temp.), 15°C to 24°C (Wet valve temp.)

 

 

 

 

CAUTION Room relative humidity – less than 80 %. If the air conditioner operates

 

in excess of this figure, the surface of the air conditioner may cause dewing.

 

 

 

Dry operation

Outdoor temperature

: 15°C to 43°C (Maximum suction air temp. 46°C)

 

 

 

 

Room temperature

: 17°C to 32°C

 

 

 

Heating

Outdoor temperature

: –15°C to 15°C (Wet valve temp.)

operation

 

 

Room temperature

: 15°C to 28°C (Dry valve temp.)

 

 

 

 

If air conditioner is used outside of the above conditions, safety protection may work.

59

Image 62
Contents Split Type Way Air Discharge Cassette Type Installation Manual Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-ETo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Installation Parts Accessory and RefrigerantSelection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSelection of Installation Installation of Outdoor UnitPiping connection Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe Cover Knockout procedureHow to remove the front panel Flaring size a Unit mm Refrigerant PipingPipe Forming/End Positioning FlaringRequirement Tightening of Connecting PartRefrigerant Piping Vacuum pump EvacuatingAir Purge Evacuating Open CloseStripping length power cord and connecting cable SM560AT-E How to remove the valve coverHow to wire Electrical WorkSelf-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation Changes in the product and components New tools for R410ARemote controller Screws two pcs AccessoriesPrecautions for Safety Standard 4-way cassette panel optional partsRAV-SM560UT-E RAV-SM800UT-E Outdoor unit Parts NameIndoor unit Parts Name of Remote Controller Display sectionOperation section Preparation Turn on the main power switch and/or the leakage breakerCorrect Usage Push button StopStart How to stop swinging How to set up the wind directionHow to start swinging Heat operationCancel of timer operation Timer OperationTimer operation Maintenance Hints for Economical OperationCleaning of Air Filters Cleaning of panel and air filterClean the panel and air filter with water If you do not plan to use the unit for more than 1 monthCleaning of discharge flap Be careful to the direction of the flap when mountingAIR Conditioner Operations and Performance Troubles and Causes RE-INSTALLATIONDo not install the air conditioner in the following places Be careful with noise or vibrationsInoperative Page Accessory parts and Parts to be procured locally Separate sold partsPrecautions for Safety Precautions for Safety Avoid installing in the following places Selection of Installation PlaceInstallation space Advice Selection of Installation PlaceSelection of installation place Discharge direction Height list of ceiling possible to be installedExternal view Installation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Flexible hose Drain Piping WorkPiping/Heat insulating material Adhesive inhibitedCheck the draining Connection procedureDrain up Perform heat insulatingTightening connection Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Use a vacuum pumpOpen the valve fully Thermal insulation processSM800 type valve at gas side Packed valve handling precautionsFor RAV-SM800AT-E model Be sure to connect earth wire. Grounding work Remote controller wiringCable connection Thermal insulation to cabling connecting portElectrical Work Cabling on the ceiling panelCabling Remote Controller CablingCabling diagram Test RUN How to execute a test runCase of wired remote controller Before test runConfirmation and check TroubleshootingConfirmation of error history Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Test run display Operation mode displayFan mode display Filter UP/DOWN button Fan mode button ButtonUnit and Auto flap button No function Operation lamp Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Cleaning of Return grille Clean the Return grilles with waterAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation of Indoor Unit Installation procedureDimension Hanging down of indoor unitConcealed duct type Installation of Indoor UnitRestriction to installation Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting WorkConnecting method of the duct AIR Ducting WorkPoints at installation work General cautionsMounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit For referenceConnection of the drain hose Piping materialPiping and cautions 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work INSTALLATION/SERVICING Tools ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Temporary button Name and Functions of Indicators and ControlsDisplay panel Name and Operations of Indicators and Controls Louver operation button Set up temp. buttonCentral indication ON/OFF buttonPush ON/OFF button Turn on the power switchWhen restarting the operation after stop CoolingSTART/STOP button DRY OperationSTART/STOP button Automatic operation Adjusting AIR Flow DirectionHOW the AIR Conditioner Works Temporary Operation Air filter resetCleaning of indoor unit and remote controller Temporary operationCheck before operation Cleaning the air filterClean the air filters as often as possible Open the air inlet grilleMinute protection function Heating operation characteristics Preheating operationCleaning the air inlet grille Warm air controlInoperative Problems and CausesRecheck Does not cool well or heat wellWired remote Precautions for Safety Precautions for Safety Mounting the Installation Plate Installation ProcedureInstallation Diagram of Indoor Unit When the installation plate is directly mounted on the wallGood location Bad location Case of downward pipe exit Piping and Drain Hose InstallationCase of right-side exit Piping via left-hand connectionDrain Piping Work DrainagePermissible Piping Length and Head Evacuating 100 For RAV-SM560AT-E modelAdd Only R410A Refrigerant to These Units Heat insulation 101Additional refrigerant 102 Wiring between unitsWiring connections 103 Installation of Remote ControllersPrecautions Flush wall mounting104 Improving System EfficiencyOptions Final Installation Checks 105Environment Environmental IssuesProduct maintenance 106

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.