Toshiba RAM-SM560UT-E Connection procedure, Drain up, Check the draining, Perform heat insulating

Page 43

Connection procedure

Connect a socket and a hard vinyl chloride pipe.

Using adhesive agent for vinyl chloride pipe, connect the drain pipes certainly so that water does not leak.

It takes approx. 10 hours to dry and harden the adhesive agent. During this period, do not apply force to the connecting part with the drain pipe.

Perform heat insulating.

As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap.

Flexible hose

Hose band

Attached heat insulator

Heat insulator to be

 

procured locally

 

Hard vinyl chloride pipe

Drain up

When a downward grading cannot be secured on the drain pipe, drain-up up to 640mm is possible.

Set downward grading immediately after raising up vertically.

Rising up 640mm or less

850mm or less

 

up

360mm

Rising

or less

 

Indoor unit

Underneath of ceiling

Check the draining

In the test run, check that water drain is properly performed and water does not leak from the connecting part of the pipes.

Be sure to check draining also when installed in heating period.

Using a pitcher or hose, pour water (1500 to 2000cc) into the discharge port before installation of the ceiling panel.

Pour water gradually so that water does not spread on the motor of the drain pump.

Heat exchanger

Drain pan

After the electric work has finished, pour water during COOL mode operation.

If the electric work has not yet finished, pull out the float switch connector (CN34 : Red) from the electric parts box, and check draining by plugging the single phase 220/230/240V power to the terminal blocks 1 and 2.

If doing so, the drain pump motor operates.

Test water drain while checking the operation sound of the drain pump motor.

(If the operation sound changes from continuous sound to intermittent sound, water is normally drained.)

After the check, the drain pump motor runs, connecting the float switch connector.

(In case of check by pulling out the float switch connector, be sure to return the connector to the original position.)

 

 

Single phase 220/230/240V

 

1

2

 

 

White

CN34

 

Red

(RED)

Black

 

 

 

Pull out connector CN34 (Red) from P.C. board. Black

40

Image 43
Contents Split Type Way Air Discharge Cassette Type Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-E Installation ManualConnect the connecting cable correctly Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyInappropriate grounding may cause electric shock Before installation Accessory and RefrigerantSelection of Installation Accessory and Installation PartsObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeInstallation of Outdoor Unit Selection of InstallationRefrigerant Piping Connection Optional Installation Parts Local ProcurePiping connection How to remove the front panel Knockout procedureKnockout of Pipe Cover Flaring Refrigerant PipingPipe Forming/End Positioning Flaring size a Unit mmRefrigerant Piping Tightening of Connecting PartRequirement Air Purge EvacuatingVacuum pump Open Close EvacuatingElectrical Work SM560AT-E How to remove the valve coverHow to wire Stripping length power cord and connecting cableCheck and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsStandard 4-way cassette panel optional parts AccessoriesPrecautions for Safety Remote controller Screws two pcsRAV-SM560UT-E RAV-SM800UT-E Indoor unit Parts NameOutdoor unit Display section Parts Name of Remote ControllerOperation section Correct Usage Turn on the main power switch and/or the leakage breakerPreparation Start StopPush button Heat operation How to set up the wind directionHow to start swinging How to stop swingingTimer operation Timer OperationCancel of timer operation Hints for Economical Operation MaintenanceIf you do not plan to use the unit for more than 1 month Cleaning of panel and air filterClean the panel and air filter with water Cleaning of Air FiltersBe careful to the direction of the flap when mounting Cleaning of discharge flapAIR Conditioner Operations and Performance Be careful with noise or vibrations RE-INSTALLATIONDo not install the air conditioner in the following places Troubles and CausesInoperative Page Separate sold parts Accessory parts and Parts to be procured locallyPrecautions for Safety Precautions for Safety Installation space Selection of Installation PlaceAvoid installing in the following places Height list of ceiling possible to be installed Selection of Installation PlaceSelection of installation place Discharge direction AdviceExternal view Installation of ceiling opening and hanging bolt Installation of hanging boltInstallation of ceiling panel Sold separately Adhesive inhibited Drain Piping WorkPiping/Heat insulating material Flexible hosePerform heat insulating Connection procedureDrain up Check the drainingTightening torque of flare pipe connections Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening connectionThermal insulation process Use a vacuum pumpOpen the valve fully Gas leak checkFor RAV-SM800AT-E model Packed valve handling precautionsSM800 type valve at gas side Remote controller wiring Be sure to connect earth wire. Grounding workCabling on the ceiling panel Thermal insulation to cabling connecting portElectrical Work Cable connectionCabling diagram Remote Controller CablingCabling Before test run How to execute a test runCase of wired remote controller Test RUNConfirmation of error history TroubleshootingConfirmation and check Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Fan mode display Operation mode displayTest run display Unit and Auto flap button No function Operation lamp Fan mode button ButtonFilter UP/DOWN button Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Clean the Return grilles with water Cleaning of Return grilleAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation procedure Installation of Indoor UnitHanging down of indoor unit DimensionLedge ceiling concealed duct type Installation of Indoor UnitRestriction to installation Concealed duct typeAIR Ducting Work Static pressure characteristics of each modelAIR Ducting Work Connecting method of the ductGeneral cautions Points at installation workFor reference Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portPiping and cautions Piping materialConnection of the drain hose 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work Tools INSTALLATION/SERVICING ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Display panel Name and Functions of Indicators and ControlsTemporary button Name and Operations of Indicators and Controls ON/OFF button Set up temp. buttonCentral indication Louver operation buttonCooling Turn on the power switchWhen restarting the operation after stop Push ON/OFF buttonSTART/STOP button DRY OperationSTART/STOP button HOW the AIR Conditioner Works Adjusting AIR Flow DirectionAutomatic operation Temporary operation Air filter resetCleaning of indoor unit and remote controller Temporary OperationOpen the air inlet grille Cleaning the air filterClean the air filters as often as possible Check before operationWarm air control Heating operation characteristics Preheating operationCleaning the air inlet grille Minute protection functionDoes not cool well or heat well Problems and CausesRecheck InoperativeWired remote Precautions for Safety Precautions for Safety When the installation plate is directly mounted on the wall Installation ProcedureInstallation Diagram of Indoor Unit Mounting the Installation PlateGood location Bad location Piping via left-hand connection Piping and Drain Hose InstallationCase of right-side exit Case of downward pipe exitDrainage Drain Piping WorkPermissible Piping Length and Head Evacuating For RAV-SM560AT-E model 100Additional refrigerant 101Add Only R410A Refrigerant to These Units Heat insulation Wiring connections Wiring between units102 Flush wall mounting Installation of Remote ControllersPrecautions 103Options Improving System Efficiency104 105 Final Installation Checks106 Environmental IssuesProduct maintenance Environment

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.