6 REFRIGERANT PIPING

Tightening connection

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

CAUTION

Do not apply excess torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit : N•m)

 

 

Outer diam. of copper pipe

Tightening torque

 

 

6.35 mm (diam.)

14 to 18 (1.4 to 1.8 kgf•m)

 

 

9.52 mm (diam.)

33 to 42 (3.3 to 4.2 kgf•m)

 

 

12.7 mm (diam.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

15.9 mm (diam.)

63 to 77 (6.3 to 7.7 kgf•m)

 

 

Tightening torque of flare pipe connections

Pressure of R410A becomes higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten firmly the flare pipe connecting sections which connect the indoor and outdoor units up to the specified tightening torque.

Incorrect connections may cause not only a gas leakage, but also a trouble of the refrigeration cycle or compressor damage.

Flare at

indoor unit side

 

Flare at

 

outdoor unit side

Half union

Flare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

7 EVACUATING

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.

Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump.

Use a vacuum pump

Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops.

1.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.

2.Connect the charge hose to the port of vacuum pump.

3.Open fully the low pressure side handle of the gauge manifold valve.

4.Operate the vacuum pump to start for evacuating.

Perform evacuating for about 35 minutes if the piping length is total 30 meters for model SM560 and 50 meters for model SM800.

(assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is –101 kPa ( –76 cmHg).

5.Close the low pressure side valve handle of gauge manifold.

6.Open fully the valve stem of the packed valves (both sides of Gas and Liquid).

7.Remove the charging hose from the service port.

8.Securely tighten the caps on the packed valves.

99

Image 102
Contents Split Type Way Air Discharge Cassette Type Installation Manual Outdoor Unit --------- RAV-SM800AT-E/RAV-SM800AT-ETo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Installation Parts Accessory and RefrigerantSelection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSelection of Installation Installation of Outdoor UnitOptional Installation Parts Local Procure Refrigerant Piping ConnectionPiping connection Knockout procedure How to remove the front panelKnockout of Pipe Cover Flaring size a Unit mm Refrigerant PipingPipe Forming/End Positioning FlaringTightening of Connecting Part Refrigerant PipingRequirement Evacuating Air PurgeVacuum pump Evacuating Open CloseStripping length power cord and connecting cable SM560AT-E How to remove the valve coverHow to wire Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ARemote controller Screws two pcs AccessoriesPrecautions for Safety Standard 4-way cassette panel optional partsRAV-SM560UT-E RAV-SM800UT-E Parts Name Indoor unitOutdoor unit Parts Name of Remote Controller Display sectionOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation Stop StartPush button How to stop swinging How to set up the wind directionHow to start swinging Heat operationTimer Operation Timer operationCancel of timer operation Maintenance Hints for Economical OperationCleaning of Air Filters Cleaning of panel and air filterClean the panel and air filter with water If you do not plan to use the unit for more than 1 monthCleaning of discharge flap Be careful to the direction of the flap when mountingAIR Conditioner Operations and Performance Troubles and Causes RE-INSTALLATIONDo not install the air conditioner in the following places Be careful with noise or vibrationsInoperative Page Accessory parts and Parts to be procured locally Separate sold partsPrecautions for Safety Precautions for Safety Selection of Installation Place Installation spaceAvoid installing in the following places Advice Selection of Installation PlaceSelection of installation place Discharge direction Height list of ceiling possible to be installedExternal view Installation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Flexible hose Drain Piping WorkPiping/Heat insulating material Adhesive inhibitedCheck the draining Connection procedureDrain up Perform heat insulatingTightening connection Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Use a vacuum pumpOpen the valve fully Thermal insulation processPacked valve handling precautions For RAV-SM800AT-E modelSM800 type valve at gas side Be sure to connect earth wire. Grounding work Remote controller wiringCable connection Thermal insulation to cabling connecting portElectrical Work Cabling on the ceiling panelRemote Controller Cabling Cabling diagramCabling Test RUN How to execute a test runCase of wired remote controller Before test runTroubleshooting Confirmation of error historyConfirmation and check Accessories RAV-SM560BT-E RAV-SM800BT-E Connecting duct Operation mode display Fan mode displayTest run display Fan mode button Button Unit and Auto flap button No function Operation lampFilter UP/DOWN button Correct Usage Automatic Operation Auto Changeover Clear of timer operation Do not open doors and windows more often than necessary Cleaning of Return grille Clean the Return grilles with waterAIR Conditioner Operations and Performance RE-INSTALLATION Air flow changes without FAN button set to Auto mode Auto RAV-SM560BT-E RAV-SM800BT-E Precautions for Safety Precautions for Safety Selection of installation place Installation of Indoor Unit Installation procedureDimension Hanging down of indoor unitConcealed duct type Installation of Indoor UnitRestriction to installation Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting WorkConnecting method of the duct AIR Ducting WorkPoints at installation work General cautionsMounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit For referencePiping material Piping and cautionsConnection of the drain hose 13.2 13.0 12.7 16.6 16.2 15.9 19.7 19.4 SM800 type valve at gas side Electrical Work INSTALLATION/SERVICING Tools ToolsRemote controller RAV-SM560KRT-E RAV-SM800KRT-E Name and Functions of Indicators and Controls Display panelTemporary button Name and Operations of Indicators and Controls Louver operation button Set up temp. buttonCentral indication ON/OFF buttonPush ON/OFF button Turn on the power switchWhen restarting the operation after stop CoolingDRY Operation START/STOP buttonSTART/STOP button Adjusting AIR Flow Direction HOW the AIR Conditioner WorksAutomatic operation Temporary Operation Air filter resetCleaning of indoor unit and remote controller Temporary operationCheck before operation Cleaning the air filterClean the air filters as often as possible Open the air inlet grilleMinute protection function Heating operation characteristics Preheating operationCleaning the air inlet grille Warm air controlInoperative Problems and CausesRecheck Does not cool well or heat wellWired remote Precautions for Safety Precautions for Safety Mounting the Installation Plate Installation ProcedureInstallation Diagram of Indoor Unit When the installation plate is directly mounted on the wallGood location Bad location Case of downward pipe exit Piping and Drain Hose InstallationCase of right-side exit Piping via left-hand connectionDrain Piping Work DrainagePermissible Piping Length and Head Evacuating 100 For RAV-SM560AT-E model101 Additional refrigerantAdd Only R410A Refrigerant to These Units Heat insulation Wiring between units Wiring connections102 103 Installation of Remote ControllersPrecautions Flush wall mountingImproving System Efficiency Options104 Final Installation Checks 105Environment Environmental IssuesProduct maintenance 106

RAM-SM560BT-E, RAM-SM560KRT-E, RAM-SM800UT-E, RAM-SM800AT-E, RAM-SM560UT-E specifications

Toshiba has established itself as a leader in the memory module market with a range of products tailored for various computing needs. Among its offerings, the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E stand out due to their advanced features, high performance, and reliable technologies.

The RAM-SM560AT-E is engineered for optimal efficiency and speed, specifically targeting the demands of modern applications. With a capacity of up to 8GB, this module leverages DDR4 technology, allowing for faster data transfers and improved energy efficiency compared to previous generations. The design focuses on low power consumption which is crucial for laptop users who seek longer battery life without compromising performance.

Next in line, the RAM-SM560UT-E offers similar capacities but is tailored with higher clock speeds. This model is particularly beneficial for gamers and professionals engaging in graphics-intensive tasks. Its enhanced throughput enables smoother multitasking and significantly reduces latency during operations that require extensive computational power.

The RAM-SM800KRT-E is a powerhouse within the lineup, boasting increased bandwidth and specifications that cater to high-end systems. Its capacity reaches up to 16GB, and it supports advanced features like dual-channel configuration, which maximizes performance by allowing simultaneous data transfer across channels. This is ideal for users working with large datasets, as it significantly accelerates processing times.

On the other hand, the RAM-SM800UT-E is designed for versatility, accommodating a broader range of devices, from ultrabooks to gaming laptops. Its emphasis on thermal management ensures reliability during extended usage. Coupled with error-correcting code (ECC) technology, it provides enhanced data integrity, making it suitable for mission-critical applications.

Lastly, the RAM-SM560BT-E is geared towards users who value balance between performance and cost. It features a robust construction and is compatible with a variety of motherboards. This makes it an excellent choice for upgrades in systems that require reliable performance without extensive investment.

In summary, Toshiba's RAM lineup, featuring the RAM-SM560AT-E, RAM-SM560UT-E, RAM-SM800KRT-E, RAM-SM800UT-E, and RAM-SM560BT-E, showcases a diverse array of memory solutions. Each model is built with cutting-edge technology, meeting the diverse demands of users ranging from casual home users to high-power gaming enthusiasts. With high capacity options, advanced data handling features, and energy-efficient designs, Toshiba continues to be at the forefront of memory technology.