Lenox P506640-01 Electrical Connections, 24VAC Transformer, Size Circuit and Install Disconnect

Page 18

IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

Electrical Connections

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)

SIZE CIRCUIT AND INSTALL DISCONNECT

1ReferSWITCHto the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.

MAIN FUSE BOX/

BREAKER PANEL

DISCONNECT

SWITCH

2INSTALL THERMOSTAT

Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.

THERMOSTAT

5FEET (1.5M)

NOTE Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.

NOTE 24VAC, Class II circuit connections are made in the control panel.

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

Page 18

Image 18
Contents Table of Contents Shipping and Packing ListGeneral Side View Unit Dimensions − inches mmModel Number Identification XP16−024 Base Section XP16 Base with LegsTypical Unit Parts Arrangement Caps and Fasteners Torque RequirementsDetail a Using Manifold Gauge SET Operating Gauge Set and Service ValvesOperating Service Valves To Access Service Port Operating Ball−Type Service Valve3RECOVERING Refrigerant Recovering Refrigerant from Existing System1DISCONNECT Power Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal Line Set Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and Debur6BRAZE Line SET Wrap Service ValvesFlow Nitrogen 7PREPARATION for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Sensing Bulb Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Equalizer Line InstallationTest for Leaks Evacuating Line Set and Indoor Coil S S SElectrical Connections Size Circuit and Install Disconnect2INSTALL Thermostat 24VAC Transformer4HIGH Voltage Power Supply Connections LOW Voltage ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit Start−Up Unit START−UPLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and Weigh in ChargeCalculating System Charge for Outdoor Unit Void of Charge Connections for Optimizing System Charge Indoor UnitOptimizing Procedure Adjusting Indoor AirflowOptimizing System Refrigerant Charge SATº LIQºSCº = XP16−036−230 XP16−048−230XP16−060−230 Temperature Pressures Normal Operating PressuresSystem Operation Unit ComponentsTest DelayDS2 Green LED FAN TWO Connectors 24VACSlow Demand Defrost Control A108 Diagnostic LedsDS2 DS1 OFFSECOND−STAGE Operation Emergency Heat Amber Light Defrost Control CONNECTIONS, Jumpers Settings and FeaturesDefrost System Defrost System OverviewCompressor Delay Mode P5 Operational Mode OverviewDefrost Cycle Actuation Defrost Demand Mode Thirty 30 Minute TimeTemperature Mode TIME/TEMPERATURE Mode HOW did Defrost TERMINATE?Degrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range Test Pin P1 Functions S STwo−Stage Modulation Compressors Checks MaintenanceProcedure Tools RequiredHomeowner Outdoor Unit FAN Motor TemperatureCompressor PressuresCooling Mode XP16 Start−Up and PerformanceStart UP Checks