Lenox P506640-01 Two−Stage Modulation Compressors Checks, Maintenance, Tools Required, Procedure

Page 40

Two−Stage Modulation Compressors Checks

Use this checklist on page 42 to verify part-load and full-load capacity operation of two-stage modulation compressors.

TOOLS REQUIRED

SRefrigeration gauge set

SDigital volt/amp meter

SElectronic temperature thermometer

SOn-off toggle switch

IMPORTANT

This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning proper to correctly perform compressor modulation operational check. (Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).

PROCEDURE

NOTE − Block outdoor coil to maintain a minimum of 375 psig during testing).

1.Turn main power OFF to outdoor unit.

2.Adjust room thermostat set point 5ºF above the room temperature.

3.Remove control access panel. Install refrigeration gauges on unit. Attach the amp meter to the common (black wire) wire of the compressor harness. Attach thermometer to discharge line as close as possible to the compressor.

4.Turn toggle switch OFF and install switch in series with Y2 wire from room thermostat.

5.Cycle main power ON.

6.Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).

7.Record all of the readings for the Y1 demand.

8.Close switch to energize Y2 demand. Verify power is going to compressor solenoid.

9.Allow pressures and temperatures to stabilize before taking measurements (may take up to 10 minutes).

10.Record all of the readings with the Y1 and Y2 demand.

11.If temperatures and pressures change in the direction noted in Two−Stage Modulation Compressor Field Operational Checklist on page 42, the compressor is properly modulating from low to high capacity. (If no amperage, pressures or temperature readings change when this test is performed, the compressor is not modulating between low and high capacity and replacement is necessary).

12. After testing is complete, return unit to original set up.

Maintenance

DEALER

Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:

Outdoor Unit

1.Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.

2.Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.

3.Visually inspect all connecting lines, joints and coils for evidence of oil leaks.

4.Check all wiring for loose connections.

5.Check for correct voltage at unit (unit operating).

6.Check amp draw on outdoor fan motor.

Motor Nameplate:_________ Actual:__________.

7.Inspect drain holes in coil compartment base and clean if necessary.

NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.

Outdoor Coil

It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)

SOutdoor Coil door coil may be flushed with a water hose.

SOutdoor Coil (Sea Coast) air in ocean

locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.

Indoor Unit

1.Clean or change filters.

2.Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.

3.Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.

4.Belt Drive Blowers − Check belt for wear and proper tension.

5.Check all wiring for loose connections.

6.Check for correct voltage at unit. (blower operating)

7.Check amp draw on blower motor.

Motor Nameplate:_________ Actual:__________.

Page 40

Image 40
Contents Shipping and Packing List Table of ContentsGeneral Unit Dimensions − inches mm Model Number IdentificationSide View XP16−024 Base Section XP16 Base with LegsCaps and Fasteners Torque Requirements Typical Unit Parts ArrangementDetail a Operating Gauge Set and Service Valves Operating Service ValvesUsing Manifold Gauge SET To Access Service Port Operating Ball−Type Service ValveRecovering Refrigerant from Existing System 1DISCONNECT Power3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal NEW or Replacement Line SET Installation Using Existing Line SETLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and DeburWrap Service Valves Flow Nitrogen6BRAZE Line SET 7PREPARATION for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Installing New Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationTest for Leaks Evacuating Line Set and Indoor Coil S S SSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical Connections 24VAC Transformer4HIGH Voltage Power Supply Connections LOW Voltage ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit Start−Up Unit START−UPConnect Manifold Gauge SET and Weigh in Charge Leak CHECK, Repair and EvacuateCalculating System Charge for Outdoor Unit Void of Charge Connections for Optimizing System Charge Indoor UnitAdjusting Indoor Airflow Optimizing ProcedureOptimizing System Refrigerant Charge LIQº SATºSCº = XP16−048−230 XP16−036−230XP16−060−230 Temperature Pressures Normal Operating PressuresSystem Operation Unit ComponentsDelay DS2 Green LED FAN TWO ConnectorsTest 24VACDemand Defrost Control A108 Diagnostic Leds DS2 DS1Slow OFFSECOND−STAGE Operation Defrost Control CONNECTIONS, Jumpers Settings and Features Defrost SystemEmergency Heat Amber Light Defrost System OverviewOperational Mode Overview Compressor Delay Mode P5Defrost Cycle Actuation Demand Mode Thirty 30 Minute Time Temperature Mode TIME/TEMPERATURE ModeDefrost HOW did Defrost TERMINATE?Degrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range Test Pin P1 Functions S SMaintenance ProcedureTwo−Stage Modulation Compressors Checks Tools RequiredHomeowner Temperature CompressorOutdoor Unit FAN Motor PressuresXP16 Start−Up and Performance Cooling ModeStart UP Checks