Lenox P506640-01 Operating Gauge Set and Service Valves, Operating Service Valves

Page 4

Operating Gauge Set and Service Valves

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for refrigerant recovery, flushing, leak testing, evacuating, weighing in refrigerant and optimizing system charge.

Each valve is equipped with a service port which has a factory−installed valve core. Figure 2 provides information on how to access and operate both angle− and ball−type service valves.

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings.

Manifold gauge set used for HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The manifold gauges should be rated for:

SHigh side

square inch gauge (psig)

SLow side sig with dampened speed to 500 psig

SManifold gauge set hoses must be rated for use to 800 psig of pressure with a 4000 psig burst rating.

Operating Angle−Type Service Valve:

1.Remove stem cap with an appropriately sized wrench.

2.Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go to open

the service valve.

 

SERVICE PORT CAP

TO INDOOR

 

 

 

 

UNIT

 

 

SERVICE PORT CORE

 

 

 

SERVICE PORT

 

 

TO OUTDOOR

 

CORE

(VALVE STEM SHOWN OPEN)

UNIT

VALVE STEM

 

INSERT HEX WRENCH HERE

 

SHOWN

 

 

 

 

 

 

 

 

CLOSED

2INSERT HEX−HEAD EXTENSION HERE

TO INDOOR

UNIT

TO OUTDOOR UNIT

STEM CAP

1 REMOVE

When service valve stem is in the CLOSED position,STEM CAP the service port is open to the line set and indoor unit.

When service valve is OPEN, the service port is open to line set, indoor and outdoor unit.

To Access Service Port:

Operating Ball−Type Service Valve:

1.Remove stem cap with an appropriately sized wrench.

2.Use an appropriately sized wrenched to open.

A service port cap protects the service port core from contamination and serves as the primary leak seal.

1.

Remove service port cap with an appropriately sized

 

wrench.

2.

Connect gauge set to service port.

1/6 TURN

11 12 1

10 2

98 543

A To open rotate stem

counterclockwise

TO INDOOR UNIT

3. When testing is completed, replace service port cap and

tighten as follows:

7 6

90°.

BTo close rotate stem

clockwise 90°.

SERVICE PORT SERVICE PORT CORE SERVICE PORT CAP

BALL (SHOWN CLOSED)

2 VALVE STEM

SWith torque wrench: Finger tighten and torque cap per table 1.

SWithout torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

 

 

 

 

 

1/12 TURN

Reinstall Stem Cap:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stem cap protects the valve stem from damage and

 

11

12 1

 

serves as the primary seal. Replace the stem cap and

 

2

tighten as follows:

10

 

 

 

 

 

 

S With Torque Wrench: Finger tighten and then

9

 

 

 

 

3

 

 

 

 

8

7

6

5

4

 

 

torque cap per table 1.

 

 

 

 

 

 

 

 

TO OUTDOOR UNIT

REMOVE

 

1 STEM CAP

SWithout Torque Wrench: Finger tighten and use an

appropriately sized wrench to turn an additional 1/12 turn clockwise.

NOTE

que.

Figure 2. Angle and Ball−Type Service Valves

Page 4

Image 4
Contents Shipping and Packing List Table of ContentsGeneral Unit Dimensions − inches mm Model Number IdentificationSide View XP16−024 Base Section XP16 Base with LegsCaps and Fasteners Torque Requirements Typical Unit Parts ArrangementDetail a Operating Gauge Set and Service Valves Operating Service ValvesUsing Manifold Gauge SET To Access Service Port Operating Ball−Type Service ValveRecovering Refrigerant from Existing System 1DISCONNECT Power3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Detail a Outside Unit Placement Placement, Slab Mounting and Stabilizing UnitLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal NEW or Replacement Line SET Installation Using Existing Line SETLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and DeburWrap Service Valves Flow Nitrogen6BRAZE Line SET 7PREPARATION for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Installing New Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationTest for Leaks Evacuating Line Set and Indoor Coil S S SSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical Connections 24VAC Transformer4HIGH Voltage Power Supply Connections LOW Voltage ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit Start−Up Unit START−UPConnect Manifold Gauge SET and Weigh in Charge Leak CHECK, Repair and EvacuateCalculating System Charge for Outdoor Unit Void of Charge Connections for Optimizing System Charge Indoor UnitAdjusting Indoor Airflow Optimizing ProcedureOptimizing System Refrigerant Charge LIQº SATºSCº = XP16−048−230 XP16−036−230XP16−060−230 Temperature Pressures Normal Operating PressuresSystem Operation Unit ComponentsDelay DS2 Green LED FAN TWO ConnectorsTest 24VACDemand Defrost Control A108 Diagnostic Leds DS2 DS1Slow OFFSECOND−STAGE Operation Defrost Control CONNECTIONS, Jumpers Settings and Features Defrost SystemEmergency Heat Amber Light Defrost System OverviewOperational Mode Overview Compressor Delay Mode P5Defrost Cycle Actuation Demand Mode Thirty 30 Minute Time Temperature Mode TIME/TEMPERATURE ModeDefrost HOW did Defrost TERMINATE?Degrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range Test Pin P1 Functions S SMaintenance ProcedureTwo−Stage Modulation Compressors Checks Tools RequiredHomeowner Temperature CompressorOutdoor Unit FAN Motor PressuresXP16 Start−Up and Performance Cooling ModeStart UP Checks