Table 9. Demand Defrost Control (A108) Inputs, Outputs and Configurable Settings

Control

Control Label or

Purpose

Function

Locations

Description

 

 

 

 

 

 

 

P1

TEST

Test Mode

See Test Mode on page 39 for further details.

 

 

 

 

 

 

Defrost Temperature

The demand defrost control as illustrated in figure 25 has valid selections

 

 

which are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt

P1

50, 70, 90, 100

Termination Shunt (Jumper)

termination pin is factory set at 50°F (10°C). If the temperature shunt is

 

 

Pins

 

 

not installed, the default termination temperature is 90°F (32°C).

 

 

 

 

 

 

 

 

 

W1

24VAC Thermostat Input /

24VAC input / output from indoor thermostat to indoor unit.

 

Output

 

 

 

 

 

 

 

 

 

C

24VAC Common

24VAC common

 

 

 

 

 

L

Thermostat Service Light

Thermostat service light connection.

P2

 

 

 

 

R

24VAC

24VAC

 

 

 

 

 

 

Y2

Thermostat Input

Controls the second stage operation of the unit.

 

 

 

 

 

O

Thermostat Input

Reversing valve solenoid.

 

 

 

 

 

Y1

Thermostat Input

Controls the operation of the unit.

 

 

 

 

P3

55, 50, 45, 40

Low Ambient Thermostat

Provides selection of the Y2 compressor lock−in temperature. Valid

Pins

options are 40, 45, 50 and 55 degrees Fahrenheit.

 

 

 

 

 

 

 

DIS−YEL

Coil Sensor

(P4−5) Ground connection for outdoor coil temperature sensor.

 

(P4−6) Connection for outdoor coil temperature sensor.

 

 

 

 

 

 

 

P4

AMB−BLACK

Ambient Sensor

(P4−3) Ground connection for outdoor ambient temperature sensor.

 

(P4−4) Connection for outdoor ambient temperature sensor.

 

 

 

 

 

 

 

 

COIL−BROWN

Discharge Sensor

No discharge sensor is used; replaced by 10K resistor.

 

 

 

 

 

 

 

The demand defrost control has a field−selectable function to reduce

 

 

 

occasional sounds that may occur while the unit is cycling in and out of

 

 

 

the defrost mode. When a jumper is installed on the DELAY pins, the

P5

DELAY

Delay Mode

compressor will be cycled off for 30 seconds going in and out of the

defrost mode. Units are shipped with jumper installed on DELAY pins.

 

 

 

 

 

 

NOTE The 30 second off cycle is NOT functional when TEST pins on

 

 

 

P1 are jumpered.

 

 

 

 

P6

TST, PS DF, C, R, O, Y1, Y2

Factory Test Connectors

No field use.

 

 

 

 

DS1

RED LED

 

Valid states for demand defrost control two LEDs are OFF, ON and

 

 

Diagnostic LED

FLASHING which indicate diagnostics conditions that are described in

DS2

GREEN LED

 

table 10.

 

 

 

 

FAN

TWO CONNECTORS

Condenser Fan Operation

These two connections provide power for the condenser fan.

 

 

 

 

O OUT

O OUT

24 VAC output

24 VAC output connection for reversing valve.

 

 

 

 

 

 

 

When the low pressure switch trips, the demand defrost control will cycle

 

 

 

off the compressor, and the strike counter in the demand defrost control

 

 

 

will count one strike. The low pressure switch is ignored under the

 

 

 

following conditions:

LO−PS

LO−PS

Low−Pressure Switch

S

during the defrost cycle and 90 seconds after the termination of

 

defrost

 

 

 

 

 

 

 

S when the average ambient sensor temperature is below 0°F (−18°C)

 

 

 

S for 90 seconds following the start up of the compressor

 

 

 

S

during TEST mode

 

 

 

 

Y2 OUT

Y2 OUT

24 VAC Output

24 VAC output for second stage compressor solenoid.

 

 

 

 

Y1 OUT

Y1 OUT

24 VAC Common Output

24 VAC common output, switched for enabling compressor contactor.

 

 

 

 

 

 

 

When the high pressure switch trips, the demand defrost control will cycle

HS−PS

HS−PS

High−Pressure Switch

off the compressor, and the strike counter in the demand defrost control

 

 

 

will count one strike.

 

 

 

 

L

L

Service Light Output

24VAC service light output.

 

 

 

 

24V

24V

24 Volt output

24VAC typically used to supply power to the Lennox System Operation

Monitor (LSOM). Not used in this system.

 

 

 

 

 

 

 

 

Page 31

XP16 SERIES

Image 31
Contents Shipping and Packing List Table of ContentsGeneral XP16−024 Base Section XP16 Base with Legs Unit Dimensions − inches mmModel Number Identification Side ViewCaps and Fasteners Torque Requirements Typical Unit Parts ArrangementDetail a To Access Service Port Operating Ball−Type Service Valve Operating Gauge Set and Service ValvesOperating Service Valves Using Manifold Gauge SETMethod Method 2 Limitations Recovering Refrigerant from Existing System1DISCONNECT Power 3RECOVERING RefrigerantNew Outdoor Unit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal Adding Polyol Ester OIL Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Line Set RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SET2CONNECT Gauges and Equipment for Flushing Procedure Equalizer Line Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationTest for Leaks S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical ConnectionsLOW Voltage Connections 4HIGH Voltage Power Supply ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit START−UP Unit Start−UpConnect Manifold Gauge SET and Weigh in Charge Leak CHECK, Repair and EvacuateCalculating System Charge for Outdoor Unit Void of Charge Indoor Unit Connections for Optimizing System ChargeAdjusting Indoor Airflow Optimizing ProcedureOptimizing System Refrigerant Charge LIQº SATºSCº = XP16−048−230 XP16−036−230XP16−060−230 Normal Operating Pressures Temperature PressuresUnit Components System Operation24VAC DelayDS2 Green LED FAN TWO Connectors TestOFF Demand Defrost Control A108 Diagnostic LedsDS2 DS1 SlowSECOND−STAGE Operation Defrost System Overview Defrost Control CONNECTIONS, Jumpers Settings and FeaturesDefrost System Emergency Heat Amber LightOperational Mode Overview Compressor Delay Mode P5Defrost Cycle Actuation HOW did Defrost TERMINATE? Demand Mode Thirty 30 Minute TimeTemperature Mode TIME/TEMPERATURE Mode DefrostDegrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range S S Test Pin P1 FunctionsTools Required MaintenanceProcedure Two−Stage Modulation Compressors ChecksHomeowner Pressures TemperatureCompressor Outdoor Unit FAN MotorXP16 Start−Up and Performance Cooling ModeStart UP Checks