Lenox Elite Series XP16 Units Heat Pumps Line Set Requirements, Using Existing Line SET

Page 9

Line Set Requirements

This section provides information on: installation of new or replacement line set.

SAdding Polyol ester oil requirements

SNew or replacement line set installation

SUsing existing line set.

ADDING POLYOL ESTER OIL REQUIREMENTS

IMPORTANT

Mineral oils are not compatible with HFC−410A. If oil must be added, it must be a Polyol Ester oil.

The compressor is charged with sufficient Polyol Ester oil (POE) for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. Systems with 20 pounds or less of refrigerant required no oil to be added.

For systems over 20 pounds − add one ounce for every five

(5) pounds of HFC−410A refrigerant.

Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.

NEW OR REPLACEMENT LINE SET INSTALLATION

Field refrigerant piping consists of both liquid and vapor lines from the outdoor unit to the indoor coil. Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as specified in table 2.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 7 for recommended installation practices.

NOTE When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, CORP. 9351−L9, or contact Lennox Technical Support Product Applications for assistance. To obtain the correct information from Lennox, be sure to communicate the following information:

SModel (XP16) and size of unit (e.g. −036).

SLine set diameters for the unit being installed as listed in table 2 and total length of installation.

SNumber of elbows vertical rise or drop in the piping.

USING EXISTING LINE SET

Things to consider:

SLiquid line that meter the refrigerant, such as RFC1 liquid line, must not be used in this application.

SExisting line set of proper size as listed in table 2 may be reused.

SIf system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil on page 14).

If existing line set is being used, then proceed to Brazing Connections on page 11.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing Line Set and Indoor Coil on page 13.

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

Table 2. Refrigerant Line Set

Model

Field Connections

 

Recommended Line Set

 

 

 

 

 

 

Liquid Line

Suction Line

Liquid Line

Suction Line

L15 Line Set

 

 

 

 

 

 

XP16−024−230

3/8" (10 mm)

3/4" (19 mm)

3/8" (10 mm)

3/4" (19 mm)

L15−41

 

 

 

 

 

 

XP16−036−230

 

 

 

 

 

 

3/8" (10 mm)

7/8" (22 mm)

3/8" (10 mm)

7/8" (22 mm)

L15−65

XP16−048−230

 

 

 

 

 

 

 

 

 

 

 

XP16−060−230

3/8" (10 mm)

1−1/8" (29 mm)

3/8" (10 mm)

1−1/8" (29 mm)

Field Fabricated

 

 

 

 

 

 

NOTE

 

 

 

 

 

 

 

 

 

 

 

Page 9

XP16 SERIES

Image 9
Contents Table of Contents Shipping and Packing ListGeneral Model Number Identification Unit Dimensions − inches mmSide View XP16−024 Base Section XP16 Base with LegsTypical Unit Parts Arrangement Caps and Fasteners Torque RequirementsDetail a Operating Service Valves Operating Gauge Set and Service ValvesUsing Manifold Gauge SET To Access Service Port Operating Ball−Type Service Valve1DISCONNECT Power Recovering Refrigerant from Existing System3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal Using Existing Line SET NEW or Replacement Line SET InstallationLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing ProceduresFlow Nitrogen Wrap Service Valves6BRAZE Line SET 7PREPARATION for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Indoor Expansion Valve Installation Installing New Indoor Metering DeviceSensing Bulb Installation Equalizer Line InstallationTest for Leaks S S S Evacuating Line Set and Indoor Coil2INSTALL Thermostat Size Circuit and Install DisconnectElectrical Connections 24VAC TransformerLOW Voltage Connections 4HIGH Voltage Power Supply ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit START−UP Unit Start−UpLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and Weigh in ChargeCalculating System Charge for Outdoor Unit Void of Charge Indoor Unit Connections for Optimizing System ChargeOptimizing Procedure Adjusting Indoor AirflowOptimizing System Refrigerant Charge SATº LIQºSCº = XP16−036−230 XP16−048−230XP16−060−230 Normal Operating Pressures Temperature PressuresUnit Components System OperationDS2 Green LED FAN TWO Connectors DelayTest 24VACDS2 DS1 Demand Defrost Control A108 Diagnostic LedsSlow OFFSECOND−STAGE Operation Defrost System Defrost Control CONNECTIONS, Jumpers Settings and FeaturesEmergency Heat Amber Light Defrost System OverviewCompressor Delay Mode P5 Operational Mode OverviewDefrost Cycle Actuation Temperature Mode TIME/TEMPERATURE Mode Demand Mode Thirty 30 Minute TimeDefrost HOW did Defrost TERMINATE?Degrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range S S Test Pin P1 FunctionsProcedure MaintenanceTwo−Stage Modulation Compressors Checks Tools RequiredHomeowner Compressor TemperatureOutdoor Unit FAN Motor PressuresCooling Mode XP16 Start−Up and PerformanceStart UP Checks