TEST

Placing the jumper on the field test pins (P1) allows the technician to:

S S S S

Clear short cycle lockout

Clear five−strike fault lockout

Cycle the unit in and out of defrost mode

Place the unit in defrost mode to clear the coil

When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to normal operation.

The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.

Y1 Active

Place a jumper on TEST pins for longer than one second but less than two seconds.

Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.

Place a jumper on TEST pins for more than two seconds.

Clears any short cycle lockout and five strike fault lockout function, if applicable.

ACTIVE

O Line Status

INACTIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

If in COOLING Mode

If in DEFROST Mode

If in HEATING Mode

No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.

The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for 45 minute test.

If no ambient or coil sensor fault exist, unit will go into DEFROST MODE.

If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.

NOTE Placing a jumper on the TEST pins will not bring the unit out of inactive mode. The only way manually activate the heat pump from an inactive mode is to cycle the 24VAC power to the Control.

If jumper on TEST pins remains in place for more than five seconds.

The unit will return to HEAT MODE un−calibrated with defrost timer set for 34 minutes.

If jumper on TEST pins is removed before a maximum of five seconds.

The unit will remain in DEFROST MODE until termination on time or temperature.

Figure 27. Test Pin (P1) Functions

Page 39

XP16 SERIES

Image 39
Contents Table of Contents Shipping and Packing ListGeneral XP16−024 Base Section XP16 Base with Legs Unit Dimensions − inches mmModel Number Identification Side ViewTypical Unit Parts Arrangement Caps and Fasteners Torque RequirementsDetail a To Access Service Port Operating Ball−Type Service Valve Operating Gauge Set and Service ValvesOperating Service Valves Using Manifold Gauge SETMethod Method 2 Limitations Recovering Refrigerant from Existing System1DISCONNECT Power 3RECOVERING RefrigerantNew Outdoor Unit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementRemoving and Installing Panels Louvered Panel InstallationLouvered Panel Removal Adding Polyol Ester OIL Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Line Set RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SET2CONNECT Gauges and Equipment for Flushing Procedure Equalizer Line Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationTest for Leaks S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical ConnectionsLOW Voltage Connections 4HIGH Voltage Power Supply ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit START−UP Unit Start−UpLeak CHECK, Repair and Evacuate Connect Manifold Gauge SET and Weigh in ChargeCalculating System Charge for Outdoor Unit Void of Charge Indoor Unit Connections for Optimizing System ChargeOptimizing Procedure Adjusting Indoor AirflowOptimizing System Refrigerant Charge SATº LIQºSCº = XP16−036−230 XP16−048−230XP16−060−230 Normal Operating Pressures Temperature PressuresUnit Components System Operation24VAC DelayDS2 Green LED FAN TWO Connectors TestOFF Demand Defrost Control A108 Diagnostic LedsDS2 DS1 SlowSECOND−STAGE Operation Defrost System Overview Defrost Control CONNECTIONS, Jumpers Settings and FeaturesDefrost System Emergency Heat Amber LightCompressor Delay Mode P5 Operational Mode OverviewDefrost Cycle Actuation HOW did Defrost TERMINATE? Demand Mode Thirty 30 Minute TimeTemperature Mode TIME/TEMPERATURE Mode DefrostDegrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range S S Test Pin P1 FunctionsTools Required MaintenanceProcedure Two−Stage Modulation Compressors ChecksHomeowner Pressures TemperatureCompressor Outdoor Unit FAN MotorCooling Mode XP16 Start−Up and PerformanceStart UP Checks