Lenox Elite Series XP16 Units Heat Pumps Recovering Refrigerant from Existing System, Method

Page 5

Recovering Refrigerant from Existing System

1DISCONNECT POWER

Disconnect all power to the existing outdoor unit at the disconnect switch and/or main fuse box/breaker panel.

MAIN FUSE

BOX/BREAKER

PANEL

DISCONNECT

SWITCH

2CONNECT MANIFOLD GAUGE SET Connect a manifold gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit..

NOTE recovery machine instructions to make the correct manifold gauge set connections for recovery refrigerant. The illustration below is a typical connection.

MANIFOLD GAUGES

RECOVERY MACHINE

LOW HIGH

3RECOVERING REFRIGERANT

CLEAN RECOVERY

OUTDOOR UNIT

CYLINDER

 

Remove existing HCFC−22 refrigerant using one of the following procedures:

METHOD 1:

METHOD 2 LIMITATIONS

Use Method 1 if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.

Recover all HCFC−22 refrigerant from the existing system using a recovery machine and clean recovery cylinder. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.

METHOD 2:

Use Method 2 if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.

Perform the following task:

AStart the existing HCFC−22 system in the cooling mode and close the liquid line valve.

BUse the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.

NOTE

ensure complete refrigerant evacuation.

CWhen the low side system pressures reach 0 psig, close the vapor line valve.

DCheck gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

NOTEMethod 2, the listed devices below could prevent full system charge recovery into the outdoor unit:

SOutdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.

SCompressor can stop pumping due to tripped internal pressure relief valve.

SCompressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)

Once the compressor can not pump down to a lower pressure due to any of the above mentioned system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

Figure 3. Refrigerant Recovery

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

Page 5

XP16 SERIES

Image 5
Contents General Table of ContentsShipping and Packing List Model Number Identification Unit Dimensions − inches mmSide View XP16−024 Base Section XP16 Base with LegsDetail a Typical Unit Parts ArrangementCaps and Fasteners Torque Requirements Operating Service Valves Operating Gauge Set and Service ValvesUsing Manifold Gauge SET To Access Service Port Operating Ball−Type Service Valve1DISCONNECT Power Recovering Refrigerant from Existing System3RECOVERING Refrigerant Method Method 2 LimitationsNew Outdoor Unit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Removal Removing and Installing PanelsLouvered Panel Installation Using Existing Line SET NEW or Replacement Line SET InstallationLine Set Requirements Adding Polyol Ester OIL RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing ProceduresFlow Nitrogen Wrap Service Valves6BRAZE Line SET 7PREPARATION for Next Step2CONNECT Gauges and Equipment for Flushing Procedure Indoor Expansion Valve Installation Installing New Indoor Metering DeviceSensing Bulb Installation Equalizer Line InstallationTest for Leaks S S S Evacuating Line Set and Indoor Coil2INSTALL Thermostat Size Circuit and Install DisconnectElectrical Connections 24VAC TransformerLOW Voltage Connections 4HIGH Voltage Power Supply ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit START−UP Unit Start−UpCalculating System Charge for Outdoor Unit Void of Charge Leak CHECK, Repair and EvacuateConnect Manifold Gauge SET and Weigh in Charge Indoor Unit Connections for Optimizing System ChargeOptimizing System Refrigerant Charge Optimizing ProcedureAdjusting Indoor Airflow SCº = SATºLIQº XP16−060−230 XP16−036−230XP16−048−230 Normal Operating Pressures Temperature PressuresUnit Components System OperationDS2 Green LED FAN TWO Connectors DelayTest 24VACDS2 DS1 Demand Defrost Control A108 Diagnostic LedsSlow OFFSECOND−STAGE Operation Defrost System Defrost Control CONNECTIONS, Jumpers Settings and FeaturesEmergency Heat Amber Light Defrost System OverviewDefrost Cycle Actuation Compressor Delay Mode P5Operational Mode Overview Temperature Mode TIME/TEMPERATURE Mode Demand Mode Thirty 30 Minute TimeDefrost HOW did Defrost TERMINATE?Degrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range S S Test Pin P1 FunctionsProcedure MaintenanceTwo−Stage Modulation Compressors Checks Tools RequiredHomeowner Compressor TemperatureOutdoor Unit FAN Motor PressuresStart UP Checks Cooling ModeXP16 Start−Up and Performance