Lenox Elite Series XP16 Units Heat Pumps, P506640-01 Detail a Outside Unit Placement

Page 7

DETAIL A Outside Unit Placement

Install unit away from windows.

TWO 90° ELBOWS INSTALLED IN LINE SET WILL

REDUCE LINE SET VIBRATION.

DETAIL B

Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.

BUILDING

STRUCTURE

MOUNTING

SLAB

GROUND LEVEL

DETAIL C

 

Elevated Slab Mounting

 

using Feet Extenders

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASE

LEG DETAIL

DETAIL D Slab Side Mounting

#10 1/2" LONG SELF−DRILLING SHEET METAL SCREWS

STABILIZING BRACKET (18 GAUGE

METAL

REQUIRED)

#10 1−1/4" LONG HEX HD SCREW AND FLAT WASHER

Concrete slab plastic anchors (hole drill 1/4")

Wood or plastic slab drill 1/8")

Stabilizing bracket (18 gauge metal right angle as exampled below.

COIL

BASE PAN

CORNER POST

2" (50.8MM) SCH 40 FEMALE THREADED ADAPTER

2" (50.8MM) SCH 40 MALE THREADED ADAPTER

Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.

DETAIL E Deck Top Mounting

DETAIL F Roof Top Mounting

If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds as illustrated.

PREVAILING WINTER WINDS

WIND BARRIER

INLET AIR

One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.

SAME FASTENERS AS

SLAB SIDE MOUNTING.

MINIMUM ONE PER SIDE

FOR EXTRA

STABILITY

INLET AIR

INLET AIR

INLET AIR

Figure 5. Placement, Slab Mounting and Stabilizing Unit

Page 7

XP16 SERIES

Image 7
Contents Shipping and Packing List Table of ContentsGeneral XP16−024 Base Section XP16 Base with Legs Unit Dimensions − inches mmModel Number Identification Side ViewCaps and Fasteners Torque Requirements Typical Unit Parts ArrangementDetail a To Access Service Port Operating Ball−Type Service Valve Operating Gauge Set and Service ValvesOperating Service Valves Using Manifold Gauge SETMethod Method 2 Limitations Recovering Refrigerant from Existing System1DISCONNECT Power 3RECOVERING RefrigerantNew Outdoor Unit Placement Placement, Slab Mounting and Stabilizing Unit Detail a Outside Unit PlacementLouvered Panel Installation Removing and Installing PanelsLouvered Panel Removal Adding Polyol Ester OIL Requirements NEW or Replacement Line SET InstallationUsing Existing Line SET Line Set RequirementsRefrigerant Line SET Alling Horizontal Runs Refrigerant Line SET From Vertical to HorizontalBrazing Connections 1CUT and Debur Brazing Procedures7PREPARATION for Next Step Wrap Service ValvesFlow Nitrogen 6BRAZE Line SET2CONNECT Gauges and Equipment for Flushing Procedure Equalizer Line Installation Installing New Indoor Metering DeviceIndoor Expansion Valve Installation Sensing Bulb InstallationTest for Leaks S S S Evacuating Line Set and Indoor Coil24VAC Transformer Size Circuit and Install Disconnect2INSTALL Thermostat Electrical ConnectionsLOW Voltage Connections 4HIGH Voltage Power Supply ConnectionsTypical Field Wiring Typical Unit Wiring Diagram −024, −036 and −048 Only Typical Unit Wiring Diagram −060 Only Unit START−UP Unit Start−UpConnect Manifold Gauge SET and Weigh in Charge Leak CHECK, Repair and EvacuateCalculating System Charge for Outdoor Unit Void of Charge Indoor Unit Connections for Optimizing System ChargeAdjusting Indoor Airflow Optimizing ProcedureOptimizing System Refrigerant Charge LIQº SATºSCº = XP16−048−230 XP16−036−230XP16−060−230 Normal Operating Pressures Temperature PressuresUnit Components System Operation24VAC DelayDS2 Green LED FAN TWO Connectors TestOFF Demand Defrost Control A108 Diagnostic LedsDS2 DS1 SlowSECOND−STAGE Operation Defrost System Overview Defrost Control CONNECTIONS, Jumpers Settings and FeaturesDefrost System Emergency Heat Amber LightOperational Mode Overview Compressor Delay Mode P5Defrost Cycle Actuation HOW did Defrost TERMINATE? Demand Mode Thirty 30 Minute TimeTemperature Mode TIME/TEMPERATURE Mode DefrostDegrees Resistance Fahrenheit 136.3 2680 High Discharge Sensor RT28 Temperature / Resistance Range S S Test Pin P1 FunctionsTools Required MaintenanceProcedure Two−Stage Modulation Compressors ChecksHomeowner Pressures TemperatureCompressor Outdoor Unit FAN MotorXP16 Start−Up and Performance Cooling ModeStart UP Checks