Auxiliary Controls on your Zoneline. | ge.com |
Safety
Auxiliary Controls—Dip Switches
The auxiliary dip switch controls are located behind the room cabinet, through an opening in the control panel.
Remove the room cabinet. See the To Remove the Room Cabinet section.
The factory settings will be in the DOWN position.
The owner is responsible for checking switches and ensuring they are in the desired position.
Dip Switches
Access Cover
Instructions
Operating
UP
DOWN
ALLI2R (All Electric Heat) (3800 Series models only)
C:FAN CN (Cooling–Smart Fan)
H:FAN CY
LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel)
CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor)
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
1 | 2 |
3 |
HIGH | |
4 | 5 |
COOL |
6 | 7 | 8 |
UP
DOWN
HEAT BOOST
(3800 Series models only)
Heat Sentinel
TL1 (H) (Temp. Limit
TL1 (C) (Temp. Limit
Instructions
Care and
All Electric Heat
This electric heat option functions only on the |
|
3800 Series models. When this switch is enabled |
|
(UP), heat pump operation is locked out, causing |
|
the unit to provide only electric resistance heat. | ALLI2R (All Electric Heat) |
Cooling—Smart Fan
When this switch is enabled (UP), it allows the |
|
indoor fan to cycle on/off with the compressor. |
|
When this switch is disabled (DOWN), it allows |
|
the indoor fan to run continuously. | C: FAN CN |
|
| |
When this switch is enabled (UP), it allows the |
| |
indoor fan to run continuously. When this |
| |
switch is disabled (DOWN), it allows the indoor |
| |
fan to cycle on/off with the heat pump or | H: FAN CY | |
heater operation. | ||
|
5
Cleaning
Troubleshooting Tips