Flushing the Heat Exchanger (Error Code: LC or 00)

An “LC” or “00” error code indicates the unit is beginning to lime up and must be flushed. Failure to flush the appliance will cause damage to the heat exchanger. Damage caused by lime build-up is not covered by the unit’s warranty. After flushing, reset the LC fault code by turning off the power to the unit and turning the power back on.

1.Disconnect electrical power to the water heater.

2.Close the shutoff valves on both the hot water and cold water lines (V3 and V4).

3.Connect pump outlet hose (H1) to the cold water line at service valve V2.

4.Connect drain hose (H3) to service valve V1.

5.Pour 4 gallons of undiluted virgin, food grade, white vinegar into pail.

6.Place the drain hose (H3) and the hose (H2) to the pump inlet into the cleaning solution.

7.Open both service valves (V1 and V2) on the hot water and cold water lines.

8.Operate the pump and allow the cleaning solution to circulate through the water heater for 1 hour at a rate of 4 gallons per minute (.15.1 liters per minute.

9.Turn off the pump.

10.Rinse the cleaning solution from the water heater as follows:

a.Remove the free end of the drain hose (H3) from the pail.

b.Close service valve, (V2), and open shutoff valve, (V4). Do not open shutoff valve, (V3).

c.Allow water to flow through the water heater for 5 minutes

d.Close service valve, (V1), and open shutoff valve, (V3).

11.Disconnect all hoses.

12.With (V4) closed, remove the in-line filter at the cold water inlet and clean out any residue. Place filter back into unit and open (V4).

13.Restore electrical power to the water heater.

KEY

3/4" Ball Valve

Pressure Regulator

 

3/4" Union

Circulating Pump

Check Valve

Boiler Drain Valve

Pressure Relief Valve

S Solenoid Valve

Rinnai

Water Heater

In-line

Filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1

 

 

 

 

 

 

 

 

 

V2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLEAN THERMISTORS

Remove and clean thermistors with a soft cloth or sponge after removing O-rings.

Cleaning solution is 4 gallons of undiluted virgin, food grade, white vinegar.

H3

V3

V4

 

 

 

 

 

Hot

Cold

Gas

 

Supply

 

Water

 

Water

 

 

Line

 

 

Line

 

 

 

 

H2

H1

Circulating Pump

VB Series Outdoor LS Manual

15

Image 15
Contents REU-VB2528WD-US Table of Contents RL75e RL94e R98LSe R98LSe-ASME SpecificationsConsumer Safety Information Safety DefinitionsSafety Behavior and Practices Safety Features Operating Instructions Features Available on Temperature ControllersFeatures Description of OperationMC-91-1US & MCC-91-1US Temperature ControllerTemperature Controller Settings How to Set the TemperatureMCC-91 Temperature Controller Temperature Options Without a Temperature ControllerSetting the Sound Volume Voice Prompt Re-setting the Maximum Temperature RL75 and RL94 onlyUsing the Water Smart / Bath Fill Function Setting the Water VolumeOverview Models MC-91 and MCC-91 Setting Controller to MuteSetting the Clock Filling the TubMaintenance Code Fault Remedy Error CodesCode Trouble Shooting for Common Issues Accessing Operating InformationWater Quality Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceElectrical Connection Gas PipingGeneral Instructions Pipe Sizing Procedure Example Water Piping Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Pressure Relief Valve MaintenanceFreeze Protection Pressure Relief ValveWhen the water heater or external piping has frozen Freeze ProtectionManual draining of the water heater KEY Freeze Protection PipingRinnai Water Heater Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFlue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US Installations Additional Clearances Guidelines Connecting Multiple Water HeatersHigh Altitude Installations Number Connected Accessories Necessary Water HeatersCanada only Cable Lengths and Size Temperature Controller InstallationConfigurations LocationOutline of Remote Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingTechnical Data Pressure Drop CurveOutlet Flow Data Pumps Temperature SettingReplacement Space HeatingDimensions Ladder Diagram for RL75e and RL94e HOT Ladder Diagram for R98LSe and R98LSe-ASMEConsumer Support Warranty InformationLimited Warranty What is covered?How do I get service? What is not covered? What will Rinnai do?Limitation on warranties Important In the State of Massachusetts 248 CMR 4.00 State RegulationsOu lappel 1-866-RINNAI1 Temp. d’eau Instructions dutilisationPlages de température avec un contrôleur de température Options de température sans contrôleur à distanceLes températures suggérées sont de Entretien Instructions générales Fixation du chauffe-eau Écartements par rapport à lappareilRaccordement électrique Installations à haute altitude Tuyauterie de gazInstructions générales Tuyauterie deau Valve de dégagement de pression Instructions d’InstallationQualité de leau Soupape de sûretéNiveau maximum Espacements pour terminaisons de cheminée ANS Z21.10.3, CSA Réf Description Installations Canada Installations USA Légende Tuyauterie recommandée pour installation de baseVanneMa ualmanuelleValve Instructions dutilisationPhase Diagramme en escalier RL75e, RL94eB C Diagramme en escalier R98LSe, R98LSeASMECombien de temps dure la couverture ? Support à la clientèleInformations sur la garantie Quest-ce qui est couvert ?Limitation sur les garanties Que fait Rinnai pour exercer la garantie ?VB2528W VB2735W VA3237W