Rinnai RL75E, RL94E Space Heating, Temperature Setting, Pumps, Replacement, Iron Components

Page 35

Space Heating

If the water heater is to be used for both water (potable) heating and space heating then the following apply.

The piping and components connected to the water heater shall be suitable for use with potable water.

Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water.

The water heater shall not be connected to any heating system or components previously used with a nonpotable water heating appliance.

When the system requires water for space heating at temperatures higher than required for other uses, a means such as a mixing valve shall be installed to temper the water for other uses in order to reduce the scald hazard potential.

Space heating applications are considered commercial applications for warranty purposes.

Temperature Setting

When using this appliance to provide domestic hot water it is recommended that the domestic hot water temperature be reduced to acceptable temperatures in accordance with local codes. In the absence of local codes it is recommended that the domestic hot water temperature be set to 140º F (60º C) or lower in accordance with UPC 501.6 by using mixing valves or the temperature controller for the water heater.

Pumps

Only use pumps of brass or stainless steel construction. Do not use pumps of iron construction as they will oxidize and clog the inlet filter on the appliance.

Pumps circulating water through the water heater must be sized to overcome the pressure loss through the water heater, the heating system, and any additional plumbing pressure losses. The pressure drop curve based on the water heater model is provided in this manual.

Replacement

When replacing an existing space heating application’s water heating source (boiler, tank water heater, tankless water heater, etc.) with Rinnai water heaters, ensure that the water heaters are sized to adequately provide the necessary BTU input for the desired space heating application. Rinnai water heaters are designed to maintain a constant outlet temperature and will supply only the necessary amount of BTU’s to maintain that temperature. Depending on the application the maximum BTU rating of the unit may not be achieved. Contact Rinnai’s Applications Engineering Department for assistance at (800) 621-9419 ext. 4490.

Iron Components

Do not use Rinnai water heaters directly for space heating applications involving iron radiators or applications with any iron components. Iron components may oxidize creating rust that will clog the inlet filter of the Rinnai water heater.

VB Series Outdoor LS Manual

35

Image 35
Contents REU-VB2528WD-US Table of Contents RL75e RL94e R98LSe R98LSe-ASME SpecificationsSafety Behavior and Practices Safety Features Consumer Safety InformationSafety Definitions Operating Instructions Features Available on Temperature ControllersFeatures Description of OperationMC-91-1US & MCC-91-1US Temperature ControllerTemperature Controller Settings How to Set the TemperatureMCC-91 Temperature Controller Temperature Options Without a Temperature ControllerSetting the Sound Volume Voice Prompt Re-setting the Maximum Temperature RL75 and RL94 onlyOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Models MC-91 and MCC-91 Setting Controller to MuteSetting the Clock Filling the TubMaintenance Code Fault Remedy Error CodesCode Water Quality Trouble Shooting for Common IssuesAccessing Operating Information Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGeneral Instructions Electrical ConnectionGas Piping Pipe Sizing Procedure Example Water Piping Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Pressure Relief Valve MaintenanceFreeze Protection Pressure Relief ValveManual draining of the water heater When the water heater or external piping has frozenFreeze Protection KEY Freeze Protection PipingRinnai Water Heater Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFlue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US Installations Additional Clearances Guidelines Connecting Multiple Water HeatersHigh Altitude Installations Number Connected Accessories Necessary Water HeatersCanada only Cable Lengths and Size Temperature Controller InstallationConfigurations LocationOutline of Remote Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingOutlet Flow Data Technical DataPressure Drop Curve Pumps Temperature SettingReplacement Space HeatingDimensions Ladder Diagram for RL75e and RL94e HOT Ladder Diagram for R98LSe and R98LSe-ASMEConsumer Support Warranty InformationLimited Warranty What is covered?Limitation on warranties How do I get service? What is not covered?What will Rinnai do? Important In the State of Massachusetts 248 CMR 4.00 State RegulationsOu lappel 1-866-RINNAI1 Temp. d’eau Instructions dutilisationLes températures suggérées sont de Plages de température avec un contrôleur de températureOptions de température sans contrôleur à distance Entretien Instructions générales Fixation du chauffe-eau Écartements par rapport à lappareilRaccordement électrique Instructions générales Installations à haute altitudeTuyauterie de gaz Tuyauterie deau Valve de dégagement de pression Instructions d’InstallationNiveau maximum Qualité de leauSoupape de sûreté Espacements pour terminaisons de cheminée ANS Z21.10.3, CSA Réf Description Installations Canada Installations USA Légende Tuyauterie recommandée pour installation de baseVanneMa ualmanuelleValve Instructions dutilisationPhase Diagramme en escalier RL75e, RL94eB C Diagramme en escalier R98LSe, R98LSeASMECombien de temps dure la couverture ? Support à la clientèleInformations sur la garantie Quest-ce qui est couvert ?Limitation sur les garanties Que fait Rinnai pour exercer la garantie ?VB2528W VB2735W VA3237W