Rinnai RL75E, RL94E installation manual Code

Page 13

 

 

Error Codes

 

 

 

 

 

Code

Fault

Remedy

 

 

 

 

 

14

Thermal Fuse

Check gas type of unit and ensure it matches gas type being used.

 

 

 

Check for restrictions in air flow around unit and vent terminal.

 

 

 

Check for low water flow in a circulating system causing short-cycling.

 

 

 

Ensure dip switches are set to the proper position.

 

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

 

Check heat exchanger for cracks and/or separations.

 

 

 

Check heat exchanger surface for hot spots which indicate blockage due to scale build-up.

 

 

 

Refer to instructions in manual for flushing heat exchanger.

 

 

 

Measure resistance of safety circuit.

 

 

 

Ensure high fire and low fire manifold pressure is correct.

 

 

 

Check for improper conversion of product.

 

16

Over Temperature

Check for restrictions in air flow around unit and vent terminal.

 

 

Warning

Check for low water flow in a circulating system causing short-cycling.

 

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

 

Check for clogged heat exchanger.

 

31

Burner Sensor Error

Measure resistance of sensor.

 

 

 

Replace sensor.

 

32

Outgoing Water

Check sensor wiring for damage.

 

 

Temperature Sensor

Measure resistance of sensor.

 

 

Fault

Clean sensor of scale build-up.

 

 

 

Replace sensor.

 

33

Heat Exchanger

Check sensor wiring for damage.

 

 

Outgoing Temperature

Measure resistance of sensor.

 

 

Sensor Fault

Clean sensor of scale build-up.

 

 

 

Replace sensor.

 

34

Combustion Air

Check for restrictions in air flow around unit and vent terminal.

 

 

Temperature Sensor

Check sensor wiring for damage.

 

 

Fault

Measure resistance of sensor.

 

 

 

Clean sensor of scale build-up.

 

 

 

Ensure fan blade is tight on motor shaft and is in good condition.

 

 

 

Replace sensor.

 

52

Modulating Solenoid

Check modulating gas solenoid valve wiring harness for loose or damaged terminals.

 

 

Valve Signal Abnormal

Measure resistance of valve coil.

 

61

Combustion Fan Failure

Ensure fan will turn freely.

 

 

 

Check wiring harness to motor for damaged and/or loose connections.

 

 

 

Measure resistance of motor winding.

 

65

Water Flow Control Fault

The water flow control valve has failed to close during the bath fill function. Immediately turn

 

 

off the water and discontinue the bath fill function. Contact a state qualified or licensed

 

 

 

contractor to service the appliance.

 

71

Solenoid Valve Circuit

Replace the PC Board.

 

 

Fault

(The RL75, RL94, R98LS have SV0~SV04.)

 

72

Flame Sensing Device

Ensure flame rod is touching flame when unit fires.

 

 

Fault

Check all wiring to flame rod for damage.

 

 

 

Remove flame rod and check for carbon build-up; clean with sand paper.

 

 

 

Check inside burner chamber for any foreign material blocking flame at flame rod.

 

 

 

Measure micro amp output of sensor circuit with flame present.

 

 

 

Replace flame rod.

 

73

Burner Sensor Circuit

Check sensor wiring and PC board for damage.

 

 

Error

Replace sensor.

 

LC

Scale Build-up in Heat

Flush heat exchanger. Refer to instructions in manual.

 

 

Exchanger (when

Replace heat exchanger.

 

 

checking maintenance

NOTE: The LC code is the only error code that will allow the unit to keep running. The

 

 

code history, “00” is

display will alternate between the LC code and the temperature setting. The controller will

 

 

substituted for “LC”)

continue to beep. The LC code will reset if power is turned off and then on.

 

No

Nothing happens when

Clean inlet water supply filter.

 

code

water flow is activated.

On new installations ensure hot and cold water lines are not reversed.

 

 

 

Check for bleed over. Isolate unit from building by turning off cold water line to building.

 

 

 

Isolate the circulating system if present. Open your pressure relief valve; if water is

 

 

 

flowing, there is bleed over in your plumbing.

 

 

 

Ensure you have at least the minimum flow rate required to fire unit.

 

 

 

Ensure turbine spins freely.

 

 

 

Measure the resistance of the water flow control sensor.

 

 

 

Check for DC shorts at components.

 

 

 

VB Series Outdoor LS Manual

13

Image 13
Contents REU-VB2528WD-US Table of Contents RL75e RL94e R98LSe R98LSe-ASME SpecificationsSafety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features Features Features Available on Temperature ControllersDescription of Operation Operating InstructionsMC-91-1US & MCC-91-1US Temperature ControllerTemperature Controller Settings How to Set the TemperatureSetting the Sound Volume Voice Prompt Temperature Options Without a Temperature ControllerRe-setting the Maximum Temperature RL75 and RL94 only MCC-91 Temperature ControllerSetting the Water Volume Using the Water Smart / Bath Fill FunctionOverview Setting the Clock Setting Controller to MuteFilling the Tub Models MC-91 and MCC-91Maintenance Code Fault Remedy Error CodesCode Accessing Operating Information Trouble Shooting for Common IssuesWater Quality Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGas Piping Electrical ConnectionGeneral Instructions Pipe Sizing Procedure Example Pressure Relief Valve Installation Instructions Isolation Valves Installation InstructionsPressure Relief Valve Maintenance Water PipingFreeze Protection Pressure Relief ValveFreeze Protection When the water heater or external piping has frozenManual draining of the water heater KEY Freeze Protection PipingRinnai Water Heater Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFlue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US Installations Additional Clearances High Altitude Installations Connecting Multiple Water HeatersNumber Connected Accessories Necessary Water Heaters GuidelinesCanada only Configurations Temperature Controller InstallationLocation Cable Lengths and SizeOutline of Remote Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingPressure Drop Curve Technical DataOutlet Flow Data Replacement Temperature SettingSpace Heating PumpsDimensions Ladder Diagram for RL75e and RL94e HOT Ladder Diagram for R98LSe and R98LSe-ASMELimited Warranty Warranty InformationWhat is covered? Consumer SupportWhat will Rinnai do? How do I get service? What is not covered?Limitation on warranties Important In the State of Massachusetts 248 CMR 4.00 State RegulationsOu lappel 1-866-RINNAI1 Temp. d’eau Instructions dutilisationOptions de température sans contrôleur à distance Plages de température avec un contrôleur de températureLes températures suggérées sont de Entretien Instructions générales Fixation du chauffe-eau Écartements par rapport à lappareilRaccordement électrique Tuyauterie de gaz Installations à haute altitudeInstructions générales Tuyauterie deau Valve de dégagement de pression Instructions d’InstallationSoupape de sûreté Qualité de leauNiveau maximum Espacements pour terminaisons de cheminée ANS Z21.10.3, CSA Réf Description Installations Canada Installations USA Légende Tuyauterie recommandée pour installation de baseVanneMa ualmanuelleValve Instructions dutilisationPhase Diagramme en escalier RL75e, RL94eB C Diagramme en escalier R98LSe, R98LSeASMEInformations sur la garantie Support à la clientèleQuest-ce qui est couvert ? Combien de temps dure la couverture ?Limitation sur les garanties Que fait Rinnai pour exercer la garantie ?VB2528W VB2735W VA3237W